Product Information

  • Product Name: Mini PIR Detector for Luminaire Integration (Batten Mount)
  • Model: EBMPIR-MB-B-BP
  • Weight: 0.100 kg
  • Supply Voltage: 230 VAC +/- 10% at 50Hz
  • Parasitic Power Consumption: 807mW
  • Max Load: 2A
  • Humidity Range: 5% to 95% (non-condensing)
  • Material (Casing): Flame-retardant ABS/PC
  • IP Rating: IP65
  • Compliance: EMC-2014/30/EU, LVD2014/35/EU Product Usage

Instructions

  1. Installation: – This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations. – Use a M20 x 1.5 nut and IP spacer for mounting the device. – Mount the device with the key, ensuring that the key is
    at the top of the sensor. – If the luminaire has a draft angle, use spacers for proper installation.

  2. Wiring: – Connect the neutral wire to Key 1. – Connect the live wire to Key 2. – If required, connect a 10A circuit protection to Key

  3. Connect the load to Key 4. 3. Settings: – Time out: The device has a fixed time out of 10 minutes. – LUX on level: Set the Lux level at which the device turns on to 9. – LUX off level: Set the Lux level at which the device turns off to 9. – Sensitivity: Set the sensitivity level to 9. – Detection: The device detects presence. Note: For detailed installation and wiring instructions, refer to the user manual
    available at cpelectronics.co.uk/cp/993

Basic switching, miniature, luminaire mounted, PIR, presence detector (20 pack)

Warning

This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.

Dimensions (mm)

Downloads and Videos

Wiring

Key

  1. Neutral
  2. Live
  3. 10A circuit protection if required
  4. Load

Detection pattern

Walk across

Walk towards

Walk towards & walk across explained

Standard luminaire fitting

Wire in plugs & connect to detector

Key

  1. M20 nut
  2. IP spacer

IP luminaire fitting | IP-Leuchtenausstattung

Wire in plugs & connect to detector

Key

  1. M20 nut
  2. 5° washer (optional)
  3. Silicone washer
  4. IP spacer

Default Settings

  • Time out: Fixed 10 minutes only.
  • LUX on level: 9
  • LUX off level: 9
  • Sensitivity: 9
  • Detection: Presence

Technical Data

Device EBMPIR-MB-B- BP
Weight kg 0.100
Supply voltage AC at 50Hz 230 VAC +/- 10%
Parasitic power consumption mW 807mW
Max load:
Incandescent lighting 2A
Fluorescent lighting 2A
Compact fluorescent lighting 2A
LED lighting 2A
Operational temp. ºC -10 to 50°C
Humidity 5 to 95% non- condensing

Testing

  1. Power up the sensor. The load should come on immediately.
  2. Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
  3. Enter the room or make some movement and check that the load switches on.

Presence Detection

Accessories & associated products

CP Electronics
A Business unit of Legrand Electric Limited,
Brent Crescent, London NW10 7XR, UK
t.+44 (0)333 900 0671
enquiry@cpelectronics.co.uk

www.cpelectronics.co.uk

connect with us

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

CP electronics User Manuals

Related Manuals