CP electronics EBDSPIR-KNX Presence Detectors Installation Guide
- June 12, 2024
- CP electronics
Table of Contents
WD686 Issue 8 Installation Guide
EBDSPIR-KNX
EBDSPIR-KNX
KNX, ceiling PIR presence/absence detector
Attention
To be installed by competent technician with good understanding of network devices.
Dimensions (mm)
Downloads and Videos
http://cpelectronics.co.uk/cp/686qr
Detection pattern
Wiring
Key
- Switches, as configured in the ETS software.
- Low voltage only.
- KNX bus
Presence or absence detection
The unit requires configuration by an appropriate software.
Absence detection activation and switches configurations are set using the ETS
KNX software supplied by others.
It is designed to work with other KNX devices such as other detectors and
switches from other manufacturers.
Presence & absence explain
http://cpelectronics.co.uk/cp/paqr
Installation
This device is designed to be flush ceiling-mounted.
- Do not site the unit where direct sunlight might enter the sensor.
- Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
- Do not fix the sensor to an unstable or vibrating surface.
Create cut out
Cut a 64mm diameter hole in the ceiling.
Wire in plugs & connect to detector
Wire in plug/s, using wiring diagram on page 2 as a guide. Connect the plug/s to the detector.
Clamp cable
Continue tightening the screws until the clamp bar snaps out and is tightly engaged against the cable/s. The cable clamp must clamp the outer sheath only.
Install detector
Bend the springs up and push detector through hole in ceiling. When fully
inserted the springs snap back to hold the device in place.
To avoid injury, take care when bending springs.
Technical Data
Part code | EBDSPIR-KNX |
---|---|
Weight | 0.150kg |
Supply voltage DC | 30 VDC over KNX bus |
Current consumption | 5.9mA |
Terminal capacity | KNX: 1.2mm² over KNX connector Switch input: 2.5mm² |
Working temperature range | -10 to 35ºC |
Humidity | 5 to 95% noncondensing |
Material (casing) | Flame retardant ABS and PC/ABS |
Insulation class | 2 |
IP rating | 40 |
Compliance **** | EMC-2014/30/EU, |
LVD-2014/35/EU
Accessories & associated products
Part Number | Description |
---|---|
Extended wiring housing | |
Masking shields for EBDSPIR range | |
Compact, programming/commissioning handset | |
Compact, user handset | |
CP Electronics |
Brent Crescent, London NW10 7XR
t. +44 (0)333 900 0671
enquiry@cpelectronics.co.uk|
---|---|---
www.cpelectronics.co.uk|
Due to our policy of continual product improvement CP Electronics reserves the
right to alter the specification of this product without prior notice.
WD686 Issue 8 Installation Guide, EBDSPIR-KNX