BEGA 34021.1 Ceiling Luminaire for Indoor Use Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
34 021.1
Technical amendments reserved
Ceiling luminaire for indoor use
Instructions for use
34021.1 Ceiling Luminaire for Indoor Use
Application
Ceiling mounted luminaire · indoor luminaire with handblown opal glass, satin
matt and aluminium housing, for all lighting tasks in interior applications.
They are ideal for places where a soft and uniform lighting distribution is
required.
Product description
Luminaire made of Aluminium, finish Colour white
Opal glass, satin matt, with screw neck Silicone gasket
2 mounting holes ø 5.5 mm
Distance apart 144 mm
2 cable entries for through-wiring of mains supply cable ø 7-10.5 mm, max. 5 G
1.5@
Connecting terminal and earth conductor terminal 2.5@
2-pole connecting terminal for digital control
LED power supply unit
220-240 V **0/50-60 Hz
DC 176-280 V
DC Start ≥ 190 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
– Safety mark
– Conformity mark
Weight:** 1.6 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage | 13.6 W |
---|---|
Luminaire connected wattage | 17 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 45 °C |
34 021.1 K3
Module designation | LED-0328/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 2190 lm |
Luminaire luminous flux | 1266 lm |
Luminaire luminous efficiency | 74,5 lm / W |
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Remove glass from luminaire housing by turning it counter-clockwise.
Undo knurled screws and remove cover plate.
Lead the mains supply cable through the cable entry into the luminaire
housing.
Fasten the luminaire housing with the supplied fastening material or other
suitable fastening material to the mounting surface.
It is absolutely essential to use the enclosed protection against accidental
contact.
Establish earth conductor connection and make the electrical connection to the
terminals.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light
output.
Make earth conductor connection between cover plate and luminaire housing.
Assemble cover plate.
Screw glass with gasket into luminaire housing.
Make sure that gasket is positioned correctly.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Spares
Spare glass | 11 003 046 40R G |
---|---|
LED power supply unit | DEV-0366/700 |
LED module 3000 K | LED-0328/930 |
Gasket glass | 83 001 447 |
Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>