BEGA 50218.2 LED Ceiling and Wall Luminaire Instruction Manual

June 13, 2024
BEGA

BEGA 50218.2 LED Ceiling and Wall Luminaire

BEGA 50218.2 LED Ceiling and Wall Luminaire

Dimension

Dimension

Instructions for Use

Application

Ceiling and wall luminaire · indoor luminaire made of impact resistant synthetic diffuser and aluminium housing.
Luminaire with free-radiating and uniform light distribution for linear illumination in interior.

Product Description

Luminaire made of aluminium, matt surface finish
Light-diffusing synthetic luminaire cover 4 elongated fixing holes
Width Ø 5.5mm
Connection terminal 2.5@
Earth conductor connection 2-pole connecting terminal for digital control
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-276 V
During DC operation the LED power is reduced to 15%
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
Safety class I
Safety mark
Conformity mark
Weight: 5.0 kg
This product contains light sources of energy efficiency class(es) D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage Protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Lamp
Module connected wattage 70.4 W
Luminaire connected wattage 80 W
Rated temperature ta=25 °C
Ambient temperature ta max=45 °C

50 218.2K3
Module designation 8x LED-0694/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 10960 lm
Luminaire luminous flux 9425 lm
Luminaire luminous efficiency 117,8 lm/W

Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface, it is mandatory to make sure that the mounting surface is connected conductive to the earth conductor of the luminaire!

Note :
If you a planning a linear arrangement of several luminaires, you must keep a minimum distance of 30mm between the luminaire caps for installation reasons.

Installation

LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or relamping.
Remove the luminaire from the packaging and put it down so that the open rear side of its housing rests on a soft surface.
Undo the lateral Torx countersunk screw T25 and remove the luminaire cap.
Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection to the terminals.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light output.
Drill mounting holes into the mounting surface.
Secure the luminaire housing to the installation surface with the fixing materials provided or other suitable materials.
For wall installation note the position of application “arrow down”.
Installation

To prevent dirt accumulating on the LED modules, press the supplied plugs into the housing holes of the luminaire profile above the screw-fitting points.
Clip the luminaire cover into the groove of the aluminium profile and push it until the stop of the luminaire housing.
Replace the housing cap and tighten lateral Torx countersunk screw T25.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED Module

The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Defective luminaire cover must be replaced.
Close the luminaire.

Spares

Synthetic cover 15 000 481 .1
LED power supply unit DEV-0214/2100i
LED module 3000 K LED-0694/930

Customer Support

BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals