BEGA 24049 Wall Luminaire Instruction Manual

June 13, 2024
BEGA

Technical amendments reserved
24 049
IP 65
Wandleuchte
BEGA 24049 Wall Luminaire

Instructions for use

Application

Wall luminaire with shielded light.
Light emission 90° / 15°.
The light is deflected by means of a conical reflector onto the surface to be illuminated.
The luminaire can be installed in any burning position.

Product description

Luminaire made of aluminium alloy, aluminium and stainless steel BEGA Unidure® coating technology Borosilicate glass Silicone gasket Reflector made of pure anodised aluminium Light sector 90° / 15° 2 mounting holes ø 4.8 mm Distance apart 134 mm 2 cable entries for through-wiring of mains supply cable ø 7-10.5 mm Connecting terminal and earth conductor terminal 2.5@ LED power supply unit 220-240 V x 0/50-60 Hz DC 170-280 V BEGA Thermal Switch®  Temporary thermal shutdown to protect temperature-sensitive components Safety class I Protection class IP 65 Dust-tight and protection against water jets Impact strength IK09 Protection against mechanical impacts < 10 joule
– Safety mark
****– Conformity mark Weight: 2.0 kg This product contains light sources of energy efficiency class(es) C, D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Lamp

Module connected wattage 9.5 W
Luminaire connected wattage 12.3 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 45 °C

24 049 K3
Module designation| LED-0793/830
Colour temperature| 3000 K
Colour rendering index| CRI > 80
Module luminous flux| 1545 lm
Luminaire luminous flux| 216 lm
Luminaire luminous efficiency| 17,6 lm / W
24 049 K4
Module designation| LED-0793/840
Colour temperature| 4000 K
Colour rendering index| CRI > 80
Module luminous flux| 1695 lm
Luminaire luminous flux| 238 lm
Luminaire luminous efficiency| 19,3 lm / W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
Undo hexagon socket head screws – wrench size 3 – up to the stop and lift luminaire top. Pull plug-connection of the LED connecting cable carefull out of the luminaire top.
Disconnect plug connection.
Lead the mains supply cable through the cable entry of the luminaire base.
Notice position of use “arrow down” of the luminaire back plate. Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface. Be sure to use the gasket rings supplied. Make the earth conductor connection and the electrical connection.
In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire. Make earth conductor connection between luminaire top and luminaire base. Push plug into coupler as far as it will go. Make sure that gasket is positioned correctly. Install the luminaire top, press-on and tighten screw.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt and deposits. Do not use high pressure cleaners.

Replacing the LED module
The designation of the LED module is noted on a label in the luminaire. The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module. Inspect and, if necessary, replace the luminaire gaskets. Defective glass must be replaced. Close the luminaire.
Spares

Spare glass 11 003 184
LED power supply unit DEV-0277/700
LED module 3000 K LED-0793/830
LED module 4000 K LED-0793/840
Reflector 76 001 483
Gasket housing 83 001 523
Gasket glass 83 001 555

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden
info@bega.com
www.bega.com

Documents / Resources

| BEGA 24049 Wall Luminaire [pdf] Instruction Manual
24049K3, 24049K4, 24049 Wall Luminaire, Wall Luminaire, Luminaire
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals