BEGA 24712 Ceiling and Wall Luminaire
Dimension
Instructions for use
Application
Unshielded ceiling and wall luminaire with high protection class. For a
variety of interior and exterior lighting applications.
Product description
Luminaire made of aluminium alloy, aluminium and stainless steel BEGA Unidure®
coating technology Opal glass 2 mounting holes ø 4.8 mm Distance apart 150 mm
2 screw cable glands with strain relief for through-wiring power connecting
cable ø 7–12 mm 1 screw cable gland closed at the factory with a dummy plug
Connection terminal 2.5@ Earth conductor connection LED power supply unit
220-240 V x 0/50-60 Hz DC 170-276 V BEGA Thermal Switch® Temporary thermal
shutdown to protect temperature-sensitive components safety class I
Protection class IP 65Dust-tight and protection against water jets Impact
strength IK02Protection against mechanical impacts < 0.2 jouler – Safety markc
– Conformity mark Weight: 3.8 kgThis product contains light sources of
energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. To achieve an additional
protection against e. g. transients, etc. we recommend separate overvoltage
protection components. You can find them on our website at
www.bega.com.
- Lamp
- Module connected wattage 13.8 W
- Luminaire connected wattage 16 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 40 °C
- 24 712 K3
- Module designation LED-0803/830
- Colour temperature 3000 K
- Colour rendering index CRI > 80
- Module luminous flux 2465 lm
- Luminaire luminous flux 1598 lm
- Luminaire luminous efficiency 99,9 lm / W
- 24 712 K4
- Module designation LED-0803/840
- Colour temperature 4000 K
- Colour rendering index CRI > 80
- Module luminous flux 2590 lm
- Luminaire luminous flux 1679 lm
- Luminaire luminous efficiency 104,9 lm / W
Lighting technology
Luminaire data for the DIALux lighting design program for outdoor lighting,
street lighting and indoor lighting, as well as luminaire data inEULUMDAT and
IES format are available on the BEGA website at
www.bega.com.
Installation
LED are high-quality electronic components! Please avoid touching the light
output opening of the LED directly during installation or relamping.. Undo
hexagon socket head screws (wrench size 3 mm) through the opening in the
luminaire housing up to the stop and lift luminaire top. Disconnect the earth
conductor connection from the plug connection. Disconnect the plug-connection
of the LED connecting cable. Lead the mains supply cable through the screw
cable gland into the luminaire back housing. The installed black gasket insert
is intended for cables ø < 10 mm. For cables ø 10-12 mm the enclosed grey
gasket insert must be used. In case of through-wiring replace the factory-
installed dummy plug with the enclosed corresponding gasket insert. At the
same time, use the enclosed synthetic cone-thrust collar between gasket insert
and thrust screw (wrench size 22 mm) (see sketch).
Fix luminaire base with enclosed or any other suitable fixing material onto
the mounting surface. Be sure to use the gasket rings supplied. Tighten the
screw cable gland. Make the earth conductor connection and the electrical
connection. Make earth conductor connection between luminaire top and
luminaire base. Connect the LED connection cable by means of a plug connector.
Make sure that gasket is positioned correctly. Install the luminaire top,
press-on and tighten screws evenly.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high-pressure cleaners.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire. The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools. Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module. Inspect and, if necessary, replace the luminaire gaskets. Defective glass must be replaced. Close the luminaire.
- Spares
- Spare glass 25 000 100
- LED power supply unit DEV-0341/500
- LED module 3000 K LED-0803/830
- LED module 4000 K LED-0803/840