BEGA 51189.5 Ceiling Luminaire or Downlight with Zoom Optics for Indoor Use Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
BEGA 51189.5 Ceiling Luminaire or Downlight with Zoom Optics for Indoor Use
Ceiling luminaire · downlight with zoom optics for indoor use
Dimension
Application
Ceiling luminaire downlight · Indoor luminaire with focusable zoom optics.
Adjustable light distribution.
To change the light distribution, optical filters are available as accessory
parts.
Changing the half beam angle between 15° and 50° by twisting the lens unit.
Product description
Cast aluminium luminaire housing, finish Colour velvet black, 2 mounting holes
ø 4.5mm
Distance apart 96mm
Optical lens made of silicate glass
Adjustable metal adapter ring with PMMA lens
combination and integrated optical filter.
Connecting terminals 2.5◻
Earth conductor connection
LED power supply unit
220-240 V ≂ 0/50-60 Hz
DC 176-275 V
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire Safety class I
– Conformity mark
Weight: 1.0 kg
This product contains light sources of energy efficiency class(es) F
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend
separate overvoltage protection components. You can find them on our website
at www.bega.com.
Lamp
Module connected wattage 22 W
Luminaire connected wattage 25 W
Rated temperature ta=25 °C
Ambient temperature ta max=30 °C
51 189.5K3
Module designation LED-1145/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 2810 lm
Luminaire luminous flux 1767 lm
Luminaire luminous efficiency 70,7 lm/W
Light technique
Adjustable light distribution
Half beam angle 15° – 50°
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Remove mounting plate from the luminaire housing.
Unplug the earth conductor connection (plug contact).
Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface,
it is mandatory to make sure that the mounting surface is connected conductive
to the earth conductor of the luminaire!
Lead the power connecting cable through the mounting plate.
Fix the mounting plate with enclosed or any other suitable fixing material
onto the mounting surface.
Establish the earth conductor connection on the earthing screw of the mounting
plate.
Establish the earth conductor connection to the luminaire housing (plug
contact).
Push silicone hoses over connecting wires and make the electrical connection
at the terminal marked (L) and (N).
The two connecting terminals marked DA, DA are provided for digital control
purposes.
If these terminals are not assigned, the luminaire will work with full light
output.
IMPORTANT:
To ensure secure connection, the luminaire housing must be positioned
precisely in relation to the mounting plate.
Make sure that the vertical bar inside the luminaire housing is positioned
precisely in the area of the mounting hole on the long bar of the mounting
plate.
Press the luminaire housing firmly against the mounting plate and turn it
clockwise firmly against the stop.
The desired half beam angle of the luminaire can be set by turning the
adjustment ring with the marked cam.
The range of the half beam angles on the trim ring includes a tolerance of ±
2.5°.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified personnel using standard tools.
Disconnect the system from the mains.
Grasp the internal adapter ring with optical filter by one of its metal tabs
and pull it out of the recess in the luminaire housing against the magnetic
resistance.
Loosen the trim ring counter-clockwise from the housing of the zoom downlight.
Remove the reflector with optical lens unit from the housing.
Remove the black insulating foil from the LED module.
Remove the LED module. Install the replacement LED module.
Apply the replacement insulating foil to the LED module.
Please follow the installation instructions for the new LED module.
IMPORTANT: Before inserting the reflector into the luminaire housing,
make sure that the polycarbonate sign (>PC<) embossed in the lens holder
points in the direction of the LED connection terminal.
Guide the recesses of the lens holder over the two bolts and insert the
reflector.
Place the trim ring with the scale on the luminaire housing. Make sure that
the 15° position is correctly positioned in relation to the embossed
polycarbonate sign (>PC<) in the lens holder.
Insert the trim ring into the recess of the luminaire housing (note 15°
position) and tighten clockwise.
Set the desired half beam angle of the luminaire by turning the marked
adjustment ring cam.
Reinsert the adapter ring with optical filter into the housing of the zoom
downlight.
The magnetic housing recess allows the adapter ring to lock precisely into
place. If the disc combination of the adapter ring with optical filter is
defective, it must be replaced.
Accessories · Optical filters
13 294 flat beam
13 296 symmetrical, diffuse
13 295 asymmetrical
For the accessories a separate instructions for use can be provided upon request.
Spares
Insulating foil 16 006 443 B1
Trim ring 20 000 086 B8
LED power supply unit DEV-0402/610i
LED module 3000 K LED-1145/930
Lens unit 75 004 802
Adapter ring with optical filter 75 004 849
Customers Support
4/4 BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden
info@bega.com
www.bega.com
References