BEGA 24 752 Wall Ceiling Light LED Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
BEGA 24 752 Wall Ceiling Light LED
DIMENSION
Instructions for use
Application
Compact downlight with symmetrically focused wide beam light distribution.
BEGA Ultradark Optics® offer a maximum of illumination and eye comfort due to
a minimised diffuse light percentage and highly efficient glare suppression.
Product Description
Luminaire made of aluminum alloy, aluminum and stainless steel BEGA Unidure®
coating technology Colour graphite or white Safety glass with optical
structure Internal louvres and polymer lens BEGA Ultradark Optics® Louvres and
the interior surface of the anti-glare ring with maximum light-absorbing
ultra-black nano-coating 2 mounting holes ø 4.8 mm Distance apart 160 mm 2
cable entries for through-wiring of mains supply cable ø 7-12 mm, max. 5 x
2,5@ Connection terminal 2.5@ Earth conductor connection BEGA Ultimate Driver®
LED power supply unit 220-240 V x 0/50-60 Hz DC 176-264 V DALI-controllable
Number of DALI addresses: 1 Basic insulation is provided between the mains and
control cables BEGA Thermal Control® Temporary thermal regulation to protect
temperature-sensitive components without switching off the luminaire Safety
class I Protection class IP 65 Dust-tight and protection against water jets
Impact strength IK07 Protection against mechanical impacts < 2 joule r –
Safety mark c – Conformity mark Weight: 2.8 kg This product contains light
sources of energy efficiency class(es) D
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Lamp
- Module connected wattage 40.3 W
- Luminaire connected wattage 44 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 35 °C
24 752 K3
- Module designation LED-1263/830
- Colour temperature 3000 K
- Colour rendering index CRI > 80
- Module luminous flux 6010 lm
- Luminaire luminous flux 4185 lm
- Luminaire luminous efficiency 95,1 lm / W
24 752 K4
- Module designation LED-1263/840
- Colour temperature 4000 K
- Colour rendering index CRI > 80
- Module luminous flux 6190 lm
- Luminaire luminous flux 4310 lm
- Luminaire luminous efficiency 98 lm / W
Lighting technology
Half beam angle 25°
Please note:
Contact with the inner surface of the luminaire reflector should be avoided in
order to permanently protect the special stray lightminimising properties of
the nano-coating.
Installation
Pass the power connecting cable through the cable entry in the mounting plate.
Fix the mounting plate with enclosed or any other suitable fixing material
onto the mounting surface. Be sure to use the gasket rings supplied. Make the
earth conductor connection and the electrical connection. For digital control
please use the connecting terminal DA, DA. In case this terminal is not used
the luminaire will be operated at full light output. In order to guarantee the
maximum service life of the electrical components, the enclosed desiccant
pouch must be placed in the luminaire. Remove the desiccant pouch from the
foil packaging and place it in the position marked by the red information
label immediately before finally closing the luminaire. Make earth conductor
connection between luminaire housing and mounting plate.
Push plug into coupler as far as it will go. Make sure that gasket is
positioned correctly. Insert the luminaire housing into the mounting plate and
turn it as far as it will go.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits. Do not use high pressure cleaners.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire. The
light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by qualified
persons using standard tools. Disconnect the system. LED are high-quality
electronic components! Please avoid touching the light output opening of the
LED directly during relamping. Remove luminaire housing from mounting plate by
turning it counter-clockwise. Disconnect the plug-in devices. Undo retaining
screw (wrench size 2.5 mm) in the luminaire housing. Remove the trim ring
along with the glass and reflector from the luminaire housing by turning it
counter-clockwise. Replace LED module. Please follow the installation
instructions for the LED module. Screw the trim ring along with the glass and
reflector into the luminaire housing by turning it clockwise. Tighten
retaining screw in the luminaire housing firmly. Make earth conductor
connection between luminaire housing and mounting plate. Push plug into
coupler as far as it will go. Make sure that gasket is positioned correctly.
Insert the luminaire housing into the mounting plate and turn it as far as it
will go.
Spares
- LED power supply unit DEV-0270/1050i
- LED module 3000 K LED-1263/830
- LED module 4000 K LED-1263/840
- Gasket 83 002 048