BEGA 12277.1 Wall Luminaire Instructions

June 13, 2024
BEGA

12277.1 Wall Luminaire
Instructions
BEGA 12277.1 Wall Luminaire -fig1
Wall luminaire for indoor use

BEGA 12277.1 Wall Luminaire

BEGA 12277.1 Wall Luminaire

Instructions for use

Application
Shielded wall luminaire · indoor luminaire for many lighting tasks in interior applications.
The light emits upwards and downwards.

Product description

Aluminium alloy housing, finish Colour white Crystal glass, inside white 2 elongated fixing holes Width 4.5 mm · 176 mm spacing 2 cable entries for through-wiring for mains cable up to ø 10.5 mm max. 3 × 1.5@
Connection terminal 2.5@ Earth conductor connection LED power supply unit 220-240 x 0/50-60 Hz DC 170-280 V Safety class I
Safety mark
Conformity mark
Weight: 1.1 kg
This product contains light sources of energy efficiency class(es) D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Lamp

Module connected wattage 8.2 W
Luminaire connected wattage 10.5 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 40 °C

12 277.1 K3

Module designation LED-0598/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 1205 lm
Luminaire luminous flux 674 lm
Luminaire luminous efficiency 64,2 lm / W

Installation

Undo set screws and lift off luminaire housing.
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or relamping.
Loosen earth connection (plug connection) and LED-connection between luminaire housing and mounting plate.
Lead the mains supply cable through the cable entry of the mounting plate.
Note position of application “arrow down”.
Fix mounting plate with enclosed or any other suitable fixing material onto the mounting surface.
It is imperative to use the enclosed gaskets.
Make earth connection.
Pull silicone sleeves over the wires and make electrical connection to the terminals.
Make earth connection (plug connection) and LED-connection between luminaire housing and mounting plate again.
Install luminaire onto the mounting plate and tighten set screws evenly.
Note position of application “arrow down”.

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Defective glass must be replaced.

Replacement of the LED module

he designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.

Spares

LED power supply unit DEV-0141/350
LED module 3000 K LED-0598/930

BEGA Gantenbrink-Leuchten KG ·
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com

Documents / Resources

| BEGA 12277.1 Wall Luminaire [pdf] Instructions
12277.1 Wall Luminaire, 12277.1, Wall Luminaire, Luminaire
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals