- Application
- Product description
- Safety
- Overvoltage protection
- Lamp
- Light technique
- Installation
- Installation into concrete ceilings:
- Installation into inserted ceilings:
- Cleaning · Maintenance
- Replacing the LED module
- Accessories
- Spares
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BEGA 50904.5 Indoor Recessed Ceiling Downlight Instruction Manual
50 904.5
Application
Recessed ceiling luminaire · indoor luminaire with symmetrical wide beam light distribution for connection to external LED power supply unit.
For installation into suspended ceilings with a shallow depth in interior areas.
BEGA Hybrid Optics® : Highly efficient and lowloss light distribution, thanks to reflector and optical lens.
Product description
Recessed LED ceiling luminaire downlight »GENIUS« without power supply unit Cast aluminium luminaire housing, finish Colour velvet black,
Reflector surface made of pure aluminium Optical silicone lens · BEGA Hybrid
Optics®
Trim ring · Chrome finish
Matt safety glass
Fixing is achieved by using two adjustable wedge-shaped claws
1 connecting cable with strain relief and plug connector system for BEGA power supply unit, on/off or DALI
Safety
The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Light technique
Symmetrical wide beam light distribution
Half beam angle 27°
Installation
Luminaire housing and external LED power supply unit must not be covered by
any heat insulating materials.
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
A separate power supply unit is required to operate the luminaire.
For connection to external LED-power supply unit – accessory 13 143 or 13 168
– the
luminaire is equipped with a 2-pin connector.
Note operating instructions of the LED-power supply units.
The recessed opening is covered by the frame of the luminaire housing.
Fixing of the luminaire in the structure is achieved by using two adjustable
wedgeshaped claws.
Installation into concrete ceilings:
For the installation of luminaire and external power supply unit we recommend to use installation housing 10 440.
Please note:
To ensure that the luminaire is securely held in the plastered installation
housing, it is essential to unscrew the screws on the underside of the
fastening claws and remove the adapter for the fastening claws (see drawing).
Installation into inserted ceilings:
A recessed opening of ø 95 mm is necessary to accept the luminaire housing.
Recessed depth min. 55 mm.
The claws catch the ceiling facing from the back side. The minimum thickness of the panel must be 3 mm and the maximum thickness 18 mm. If the ceiling facing has a thickness of less than 3 mm or in case of an installation into plasterboard ceilings, the facing thickness in the region of the claws must be increased from the back side.
If the ceiling cladding is thicker, it is essential to unscrew the screws on the underside of the mounting claws and remove the adapter for the mounting claws (see drawing).
The minimum thickness of the ceiling cladding must be 13 mm and the maximum 33 mm.
Connect plug part of the luminaire with power supply unit.
Push external LED power supply unit and luminaire housing into the ceiling cut-out. Tighten evenly screws of claw fasteners.
Screw enclosed trim ring with attached reflector into the luminaire housing by turning it clockwise.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the electrical installation.
Open the luminaire.
Please follow the installation instructions for the LED module.
Close the luminaire.
Accessories
For the accessories a separate instructions for use can be provided upon request.
Spares
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com