BEGA 50893.4 Recessed Ceiling Light Instruction Manual

June 13, 2024
BEGA

BEGA 50893.4 Recessed Ceiling Light

DIMENSION

Instructions for use

Application
Recessed ceiling luminaire · indoor luminaire with impact resistant synthetic diffuser, translucent white and aluminium housing for connection to an external LED power supply unit. For installation in suspended ceilings of 9-25 mm in interior applications.

Product description

  • Recessed ceiling luminaire downlight
  • »STUDIO LINE« without power supply unit
  • Luminaire housing made of aluminium
  • inside hue matt brass
  • Impact resistant synthetic diffuser, translucentwhite,
  • with bayonet closure
  • Recessed opening ø 380 mm
  • Required installation depth 155 mm
  • Luminaire housing with 3 fastening springs and
  • guide screws
  • 2 connecting cables with strain relief and plug
  • connector system for BEGA power supply unit,
  • on/off or DALI
  • Safety class III 3
    • c – Conformity mark
  • Weight: 2.1 kg

This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Installation

  • Luminaire housing must not be installed in heat-insulating material.
  • A separate power supply unit is required to operate the luminaire.
  • For connection to external LED power supply unit – accessory 13 178 or 13 174– the luminaire is equipped with two 2-pin connectors.
  • Observe the instructions for use for LED power supply units.
  • LED are high-quality electronic components!
  • Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Connect to the LED power supply unit.
  • Guide the LED power supply unit through the opening in the ceiling and position it on the suspended ceiling.
  • The recessed opening is covered by the frame of the luminaire housing.
  • Fixing of the installation housing in the recessed opening is achieved by using three adjustable springs.

Luminaire housing and external LED power supply unit must not be covered by any heat-insulating materials.

Installation into inserted ceilings:

  • A recessed opening of 380 mm with a minimum depth of 155 mm is required.
  • Push luminaire housing into the ceiling cut-out and tighten evenly screws (T 20) of the three mounting springs.
  • The mounting springs catch the ceiling facing from the back side. The minimum thickness of the panel must be 9 mm and the maximum thickness 25 mm. If the ceiling facing has a thickness of less than 3 mm, the facing thickness in the region of the mounting springs must be increased from the back side.
  • Connect the two 2-pin plug connectors between the luminaire and the external LED power supply unit.
  • Unpack the LED unit, lift it with enclosed gloves, and insert it into the luminaire housing – keyholes –.
  • Turn the LED device anticlockwise until it stops and tighten the screws (T 10) evenly.
  • Place the synthetic diffuser into the luminaire housing and observe that the cam pins fit into the notches of the synthetic diffuser.
  • Screw in the synthetic diffuser by turning it clockwise.
  • Thus, you reach a safe and vibration resistant holding of the synthetic diffuser.
  • To release the synthetic diffuser from the luminaire housing, turn it counterclockwise.

Lamp

  • Module connected wattage 28.1 W
  • Luminaire connected wattage 32 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 45 °C

50 893.4 K3

  • Module designation LED-0832/930
  • Color temperature 3000 K
  • Color rendering index CRI > 90
  • Module luminous flux 3735 lm
  • Luminaire luminous flux 2173 lm
  • Luminaire luminous efficiency 67,9 lm / W

Cleaning Maintenance

Clean the luminaire regularly with solvent-free cleaning agents to remove dirt. A defective synthetic cover must be replaced.

Replacement of the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light color and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect the system.
  • Unscrew the synthetic diffuser from the luminaire housing by turning it counterclockwise.
  • Please follow the installation instructions for the
  • LED module.
  • Screw in the synthetic diffuser by turning it clockwise.
  • The defective synthetic diffuser must be replaced.

Accessories

  • Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain relief and plug connector system.
  • 13 178 Power supply unit on/off
  • 13 174 Power supply unit DALI
  • The power supply units are only suitable for the operation of one LED luminaire.

For the accessories separate instructions for use can be provided upon request.

Spares

  • Synthetic cover 15 000 633
  • LED module 3000 K LED-0832/930

CONTACT

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals