BEGA 50 002.2 Recessed Ceiling Downlight Instructions

June 13, 2024
BEGA

BEGA 50 002.2 Recessed Ceiling Downlight

Instructions for use

Application
Recessed ceiling luminaire · indoor luminaire with a crystal glass for wide beam light. For installation in suspended ceilings of 10-45 mm in interior applications. A remote power supply unit is required to operate this luminaire. If this luminaire should be integrated into a LCN or Zigbee- controlled building management system we recommend our BEGA Control light control system.

Product description
LED recessed luminaire without power supply unit Luminaire made of cast aluminum, aluminum and stainless steel Crystal glass with thread, partially frosted Silicone gasket Reflector made of pure anodized aluminium Ceiling frame ring made of stainless steel Luminaire housing with 2 fixing claws and guide screws Ceiling aperture ø 97 mm Free space installation depth required 110 mm 1 connecting cable with strain relief and plug connector system for BEGA power supply unit, on/off or DALI Safety Class III 3 Protection class IP 65 Dust-tight and protection against water jets Impact strength IK06 Protection against mechanical impacts < 1 joule c  – Conformity mark Weight: 0.6 kg This product contains light sources of energy efficiency class(es) E

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 11.5 W
  • Luminaire connected wattage 13.3 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 40 °C

50 002.2 K3

  • Module designation LED-0430/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1735 lm
  • Luminaire luminous flux 851 lm
  • Luminaire luminous efficiency 64 lm / W

Lighting technology

  • Half beam angle 51°

Installation

A separate power supply unit is required to operate the luminaire. For connection to external LED-power supply unit – accessory 13 191 or 10 520 – the luminaire is equipped with a connector. Note operating instructions of the LED-power supply units. LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.

Installation into concrete ceilings:
For the installation of luminaire and external power supply unit we recommend to use installation housing 10 440.

Installation into inserted ceilings:
A recessed opening of ø 97 mm is necessary to accept the luminaire housing. Free space depth min. 110 mm. The lateral distance between recessed luminaire and other building parts must be at least 50 mm. The claws catch the ceiling facing from the back side. Minimum thickness of the ceiling facing is 10 mm. If the ceiling facing has a thickness of less than 10 mm or in case of an installation into plasterboard ceilings, the facing thickness in the region of the claws must be increased from the back side. Remove glass with reflector from luminaire housing by turning counter-clockwise. Connect plug part of the luminaire with power supply unit.

Push external LED power supply unit and luminaire housing into the ceiling cut-out. Tighten guide screws. When tightening the screws, the fixing claws must swivel onto the inside of the suspended ceiling. The luminaire is fixed. When undoing the guide screws, the fixing claws swivel back and the luminaire can be removed. Lead enclosed trim ring with gasket over the screw-neck of the glass. Make sure that gasket is positioned correctly. Insert glass with mounted reflector and frame ring by turning it clockwise into luminaire housing.

Cleaning · Maintenance

Clean the luminaire regularly with solvent-free cleansers from dirt. Defective glass must be replaced.

Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire. The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools. Disconnect from the main supply. Unscrew glass with ceiling frame ring from luminaire housing by turning it counter- clockwise. Please follow the installation instructions for the LED module. Check gasket. Screw in glass with ceiling frame ring by turning it clockwise beyond the stop. The defective glass must be replaced.

Accessories

Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain relief and plug connector system.

  • 13 191 Power supply unit on/off
  • 10 520 Power supply unit DALI

The power supply units are only suitable for the operation of one LED luminaire.

  • 10 440 Installation housing

For the accessories, a separate instructions for use can be provided upon request.

Spares

  • Spare glass 11 003 090 10R G
  • LED module 3000 K LED-0430/930
  • Trim ring 71 001 571 M1
  • Reflector 76 001 334

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals