BEGA 24 175 Ceiling and Wall Luminaire Instruction Manual

June 12, 2024
BEGA

BEGA 24 175 Ceiling and Wall Luminaire

BEGA 24 175 Ceiling and Wall Luminaire

Dimension

Dimension

Application

Unshielded ceiling and wall luminaire with high protection class
A luminaire made of aluminium alloy and crystal glass.

Product description

Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Crystal glass, white inside 2 mounting holes ø 4.5mm
Distance apart 236mm 2 screw cable glands with strain relief
for through-wiring power connecting cable ø 7–12mm
1 screw cable gland closed at the factory with a dummy plug
Connection terminal 2.5@
Earth conductor connection
LED power supply unit
220-240 V 0/50-60 Hz
DC 176-280 V
BEGA Thermal Switch®
Temporary thermal shutdown to protect temperature-sensitive components
Safety class I
Ballproof – The testing of ball impact safety was carried out exclusively with handballs in accordance with DIN 18032-3: 2018-11.
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK10
Protection against mechanical impacts < 20 joule
– Safety mark
– Conformity mark
Weight: 2.5 kg
This product contains light sources of energy efficiency class(es) C, D

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp

Module connected wattage: 12.9 W
Luminaire connected wattage: 15 W
Rated temperature: ta=25 °C
Ambient temperature: ta max=30 °C

24 175K3

Module designation: LED-0985/830
Colour temperature: 3000 K
Colour rendering index: CRI >80
Module luminous flux: 2155 lm
Luminaire luminous flux: 1450 lm
Luminaire luminous efficiency: 96,7 lm/W

24 175K4

Module designation: LED-0985/840
Colour temperature: 4000 K
Colour rendering index: CRI >80
Module luminous flux: 2265 lm
Luminaire luminous flux: 1524 lm
Luminaire luminous efficiency: 101,6 lm/W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.

Undo hexagon socket head screw (wrench size 3mm) through the opening in the luminaire housing up to the stop and lift luminaire top. Disconnect the earth conductor connection from the plug connection.
Disconnect plug-connection of the LED connecting cable.
Lead the mains supply cable through the screw cable gland into the luminaire back housing.
The installed black gasket insert is intended for cables ø < 10mm.
For cables ø 10-12mm the enclosed grey gasket insert must be used.
In case of through-wiring replace the factory installed dummy plug with the enclosed corresponding gasket insert.
At the same time, use the enclosed synthetic cone-thrust collar between gasket insert and thrust screw (wrench size 22 mm) (see sketch).

Installation

Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface.
Tighten screw cable gland.
Make the earth conductor connection and the electrical connection.

In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.

Connect the LED connection cable by means of a plug connector. Make earth conductor connection between luminaire top and luminaire base. Push plug into coupler as far as it will go.

In order to ensure the tightness of the  luminaire, the grub screw for fixing the luminaire upper part must not lie in the marked area.

Installation

Make sure that gasket is positioned correctly. Tighten grub screw firmly.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.

Spares

Spare glass: 11 003 518
LED power supply unit:DEV-0150/350
LED module 3000 K: LED-0985/830
LED module 4000 K: LED-0985/840
Gasket glass: 83 001 907
Gasket housing: 83 002 167B1

Symbols

Customer Support

BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals