BEGA 24732 Wall Luminaire
DIMENSIONS
Instructions for use
Application
- Wall luminaire with single-sided light output for illumination and design tasks in architecture.
- The luminaire can be installed with the light distribution opening upwards or downwards.
Product Description
- Luminaire made of aluminium alloy, aluminium and stainless steel
- BEGA Unidure® coating technology
- Matt safety glass
- Reflector surface made of pure aluminium
- Mounting plate with 2 fixing holes ø 5.4 mm · 70 x 125 mm spacing 2 screw cable glands with strain relief
- for through-wiring power connecting cable ø 7–12 mm
- 1 screw cable gland closed at the factory with a dummy plug
- Connecting terminal 2.5@ with plug connection
- Earth conductor connection
- LED power supply unit
- 220-240 V 0/50-60 Hz
- DC 176-275 V
- DALI-controllable
- Basic insulation is provided between the mains and control cables
- BEGA Thermal Control®
- Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
- Safety class I
- Protection class IP 65
- Dust-tight and protection against water jets
- Impact strength IK03
- Protection against mechanical impacts < 0.35 joule
- – Conformity mark
- Weight: 3.7 kg
- This product contains light sources of energy efficiency classes D
Safety
- The installation and operation of this luminaire are subject to national safety regulations.
- Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation.
- If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Lamp
- Module connected wattage 17.7 W
- Luminaire connected wattage 20.5 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 50 °C
24 732 K3
- Module designation LED-0800/830
- Colour temperature 3000 K
- Colour rendering index CRI > 80
- Module luminous flux 2980 lm
- Luminaire luminous flux 2125 lm
- Luminaire luminous efficiency 103,7 lm / W
24 732 K4
- Module designation LED-0800/840
- Colour temperature 4000 K
- Colour rendering index CRI > 80
- Module luminous flux 3060 lm
- Luminaire luminous flux 2182 lm
- Luminaire luminous efficiency 106,4 lm / W
Light technique
- Broad spread light distribution.
- Half beam angle 70°
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
- To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at www.bega.com.
Installation
-
Undo hexagon socket head screws (wrench size 3 mm) up to the stop and disassemble the mounting plate.
-
Pass the power connecting cable through the cable entry in the mounting plate.
-
The installed black gasket insert is intended for cables ø < 10 mm.
-
For cables ø 10-12 mm the enclosed grey gasket insert must be used.
-
In case of through-wiring replace the factory installed dummy plug with the enclosed corresponding gasket insert.
-
At the same time, use the enclosed synthetic cone-thrust collar between gasket insert and thrust screw (wrench size 22 mm) (see sketch).
-
Ensure correct directionality towards the area to be illuminated.
-
Fix the mounting plate with enclosed or any other suitable fixing material onto the mounting surface.
-
Tighten screw cable gland.
-
Make earth conductor connection and electrical connection to the connecting terminal (plug connection).
-
For digital control please use the connecting terminal DA, DA.
-
In case this terminal is not used the luminaire will be operated at full light output.
-
Make sure that gasket is positioned correctly.
-
Push plug into coupler as far as it will go.
-
Place the luminaire onto the mounting plate and fix it.
Cleaning · Maintenance
- Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
- Do not use high pressure cleaners.
Please note
- Do not remove the desiccant bag from the luminaire housing.
- It is needed to remove residual moisture.
Replacing the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
- The module can be replaced by qualified persons using standard tools.
- Disconnect the system and open the luminaire.
- Please follow the installation instructions for the LED module.
- Inspect and, if necessary, replace the luminaire gaskets.
- Defective glass must be replaced.
- Close the luminaire.
Spares
- LED power supply unit DEV-0402/520i
- LED module 3000 K LED-0800/830
- LED module 4000 K LED-0800/840
- Reflector 76 001 978
- Gasket 83 002 077
BEGA Gantenbrink-Leuchten KG
- Postfach 31 60
- 58689 Menden
- info@bega.com
- www.bega.com
References