BEGA 50141.2 LED Recessed Wall Luminaire Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
50 141.2
Recessed wall luminaire for indoor use
Instructions for use
Application
Recessed wall luminaire · indoor luminaire with crystal glass, inside white
and metal housing.
Luminaire with unshielded light for directing and conducting lighting.
Product description
Recessed ceiling luminaire »ACCENTA« Die-cast zinc luminaire housing
Metal cover frame with safety glass, white inside Stainless steel finish
Cavity-wall box with 2 fixing claws and fixing screws
Ceiling aperture ø 68 mm
Free space installation depth required 65 mm
Mains cable up to ø 10.5 mm, max. 3 × 1.5@
Connecting terminal 1.5@
Earth conductor connection
LED power supply unit 220-240 V 0/50-60 Hz DC 176-264 V
Safety class I
– Safety mark
– Conformity mark
Weight: 0.27 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage| 1 W
Luminaire connected wattage| 2.1 W
Rated temperature| ta = 25 °C
Ambient temperature| ta max = 45 °C
When installed in heat-insulating material| ta max = 35 °C
50 141.2 K27
Module designation| LED-0815/927
Colour temperature| 2700 K
Colour rendering index| CRI > 90
Module luminous flux| 155 lm
Luminaire luminous flux| 50 lm
Luminaire luminous efficiency| 23,8 lm / W
50 141.2 K3
Module designation| LED-0815/930
Colour temperature| 3000 K
Colour rendering index| CRI > 90
Module luminous flux| 160 lm
Luminaire luminous flux| 52 lm
Luminaire luminous efficiency| 24,8 lm / W
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Installation into solid walls
For this purpose a recess box, ø 68 mm and a recessed depth of min. 62 mm is
necessary.
Installation into wall panels
A recessed opening of ø 68 mm is necessary to accept the cavity-wall box.
Recessed depth min. 65 mm.
The lateral distance between cavity-wall box and standard combustible building
parts must be at least 40 mm.
The claws of the cavity-wall box catch the wall panel from the back side. If
minimum thickness is less than 7 mm, it must be reinforced from the back side.
Maximum thickness of the panel must be no more than 35 mm.
Pass the mains cable through a cable entry of the cavity-wall box and fit the
cavity-wall box.
Make sure that the countersunk screws of the cavity-wall box are horizontal
relative to the ground.
Connect the earth conductor to the link on the luminaire housing.
Make electrical connection to the terminal of the power supply unit.
Insert the luminaire into the cavity-wall box and use the two countersunk
screws to adjust and secure it.
Use retention pins to mount the cover frame with glass on the luminaire
housing such that the two rear magnets are seated on the countersunk screws.
Note:
This luminaire is supplied with a matching cavity-wall box.
If cavity-wall boxes of other manufacturers are used, they must be made of
electrical insulating material such as plastic!
Through-wiring
Please note: Through wiring of the luminaire is only possible by means of
an electronic box.
We recommend the use of a flush-mounted box Kaiser 1068-02 for flush-mounting
and a cavity-wall box Kaiser 9268-94 for cavity wall mounting.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Defective glass must be replaced.
Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Defective glass must be replaced.
Close the luminaire.
Spares
Glass/Trim frame| 20 000 041 M1
LED power supply unit| DEV-0231/350
LED module 2700 K| LED-0815/927
LED module 3000 K| LED-0815/930
Technical amendments reserved
BEGA Gantenbrink-Leuchten KG · Postfach 31 60
58689 Menden
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>