BEGA 51143.6 LED Wall Luminaire Instruction Manual

June 12, 2024
BEGA

**BEGA 51143.6 LED Wall Luminaire Instruction Manual

**

Instructions for use

Dimension

Application
Wall luminaire · indoor luminaire with velvet white luminaire housing and inside hue. The light emits upwards and downwards.

Product description

  • Wall luminaire “STUDIO LINE”
  • Aluminium luminaire housing, finish Colour velvet white inside hue matt copper
  • Light-diffusing synthetic LED cover 2 elongated fixing holes
  • Width 4.5mm · 90 x 38mm spacing 1 cable entry for through-wiring for mains cable
  • Connecting terminals 2.5@
  • Earth conductor terminal
  • LED power supply unit 220-240 V x 0/50-60 Hz
  • DC 176-275 V
  • DALI-controllable
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I
  •  Conformity mark
  • Weight: 0.93 kg
  • This product contains light sources of energy efficiency class(es) E

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp
Module connected wattage 17 W
Luminaire connected wattage 19.5 W
Rated temperature ta=25 °C
Ambient temperature ta max=35 °C

51 143.6K3
Module designation 2x LED-0986/930
Colour temperature 3000 K
Colour rendering index CRI > 80
Module luminous flux 2400 lm
Luminaire luminous flux 886 lm
Luminaire luminous efficiency 45,4 lm/W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping. Undo the hexagon socket head screws (wrench size 2.5 mm) and lift luminaire housing. Unplug the earth conductor connection (plug contact). Pass the power connecting cable through the cable entry in the mounting plate. Fasten the mounting plate with the supplied fastening material or other suitable fastening material to the installation surface. Note position of application of the mounting plate “arrow down”. Establish the earth conductor connection on the earthing screw ( ) of the mounting plate. Push silicone sleeves over the lines. Make the electrical connection to the terminals. Observe the correct configuration of the connecting cable. Connect the live conductor to the brown wire (L) and the neutral conductor to the blue wire (N). The two connecting terminals marked DA, DA are provided for digital control purposes. If these terminals are not assigned, the luminaire will work with full light output. Make earth conductor connection between luminaire housing and mounting plate (plug contact). Place connecting terminals inside the luminaire housing. Note position of application of the luminaire “arrow down”. Install luminaire housing over mounting plate and tighten hexagon socket head screws (wrench size 2.5 mm) evenly

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module ·
Replacing the power supply unit
The designation of the LED module is noted on a label in the luminaire. The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The replacement can be carried out by a qualified person using standard tools. Disconnect the system from the power supply. Unscrew the hexagon socket screws (SW 2.5) underneath and lift off the luminaire housing. Remove the wires on the luminaire side from the terminals marked (L), (N), DA DA. Disconnect the earth conductor connection with the mounting plate (plug contact). Insert hex wrench (SW 2–2.5) in the bore holes in the diffuser lenses. Release the diffuser lenses from their magnetic holders by rotating them slightly and carefully pull them out of the luminaire housing together with the hex wrench. Unscrew the two nuts (M 2.5) with serrated washers in the connection compartment of the luminaire housing, and remove the die-cast housing with LED modules and power supply unit from the luminaire housing. Remove the LED module. Install the replacement LED module. Please follow the installation instructions for the LED module. Replace defective LED power supply unit. Install in reverse order.

Spares
LED power supply unit DEV-0402/500i
LED module 3000 K LED-0986/930
Diffuser disk 75 004 704

BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden ·
[email protected]
www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BEGA User Manuals

Related Manuals