BEGA 51 075.6 Recessed Ceiling Luminaire for Indoor Use Instruction Manual

June 12, 2024
BEGA

BEGA 51 075.6 Recessed Ceiling Luminaire for Indoor Use

BEGA-51-075-6-Recessed-Ceiling-Luminaire-for-Indoor-Use-
product

Application

  • Recessed ceiling luminaire · indoor luminaire with symmetrical broad spread light distribution and a remote controllable power supply unit.
  • For surface-mounted installation in indoor suspended ceilings of 5-30 mm thickness.

Product Description

  • Recessed ceiling luminaire »STUDIO LINE« with a remote power supply unit
  • Luminaire housing made of cast aluminum
  • Ceiling trim ring finish, Colour velvet black inside hue matt copper
  • Fixing is achieved by using 2 fastening springs
  • Recessed opening ø 120 mm
  • Required installation depth of 80 mm
  • Light-diffusing disc
  • External LED power supply unit: 220-240 V x 0/50-60 Hz
  • DC 176-275 V
  • DALI controllable
  • Basic isolation exists between the power cable and the control line
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class: II
  • CE: Conformity mark
  • Weight: 0.45 kg
  • This product contains light sources of energy efficiency class(es) E

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation.
  • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Specifications

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage: 10 W
  • Luminaire connected wattage: 11.8 W
  • Rated temperature: ta = 25 °C
  • Ambient temperature: ta max = 45 °C

51 075.6 K3

  • Module designation: LED-0859/930
  • Colour temperature: 3000 K
  • Colour rendering index: CRI > 90
  • Module luminous flux: 1450 lm
  • Luminaire luminous flux:  537 lm
  • Luminaire luminous efficiency:  45,5 lm / W

preliminary data

Lighting technology

  • Symmetrical wide beam light distribution Half beam angle 65°

Installation

  • Luminaire housing and external LED power supply unit must not be covered by any heat insulating materials.
  • LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
  • Cover the recessed opening with the stop ring of the luminaire housing.
  • The luminaire housing is then fixed in the recessed opening via two springs.

Installation in suspended ceilings

  • A recessed opening of 120 mm with a minimum depth of 80 mm is required.
  • The minimal thickness of the ceiling panel must be 5 mm and must not be greater than 30 mm.
  • A ceiling panel with less than 5 mm thickness must be reinforced on the reverse.
  • The electrical connection must be made on site in the appropriate safety class on the LED power supply unit connecting cable. A distribution box must be used.
  • Ensure the correct assignment of the connecting cable. Establish the mains connection on the brown (L) and blue (N) wires.
  • The connection of the control cables is achieved by means of the both leads marked with – DALI.
  • In case these leads are not used the luminaire will be operated at full light output.
  • Guide the LED power supply unit through the opening in the ceiling and position it on the suspended ceiling.
  • Compress the fastening springs of the luminaire housing on both sides and slide the luminaire housing into the recessed opening.
  • The fastening springs lock into place behind the ceiling panel.

Maintenance

Cleaning ·Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Close the luminaire.

Spares

  • LED power supply unit: DEV-0385/350i
  • LED module 3000 K: LED-0859/930
  • Reflector:  71 003 294 L3

BEGA Gantenbrink-Leuchten KG

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals