BEGA 24 730 Ceiling and Wall Luminaire Instruction Manual

June 12, 2024
BEGA

Ceiling and wall luminaire

BEGA 24 730 Ceiling and Wall Luminaire IP 65
24 730
Instructions for use

Application

Ceiling and wall luminaire with impact-resistant cover made of synthetic material.
Large-area luminaire with a very high light output and uniform light distribution.
The used LED technique offers durability and optimal light output with low power consumption at the same time.

Product description

Luminaire made of aluminium and stainless steel BEGA Unidure® coating technology Colour white
White synthetic diffuser Silicone gasket Mounting plate with 4 fixing holes ø 9.5 mm Pitch circle ø 800 mm 2 cable entries for through- wiring of mains supply cable ø 7-10.5 mm, max. 5 G 1.5@ Connecting terminal 2.5@ with plug connection Earth conductor connection LED power supply unit 220-240 V x 0/50-60 Hz DC 176-280 V DALI-controllable Number of DALI  addresses: 1
Basic insulation is provided between the mains and control cables BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire Safety class I Protection class IP 65
Dust-tight and protection against water jets Impact strength IK10
Protection against mechanical impacts < 20 joule
– Safety mark
– Conformity mark
Weight: 19.8 kg

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Lamp

Module connected wattage
Luminaire connected wattage
Rated temperature
Ambient temperature| 92.4 W
102 W
ta = 25 °C
ta max = 40 °C
---|---

24 730 K3

Module designation
Colour temperature
Colour rendering index
Module luminous flux
Luminaire luminous flux
Luminaire luminous efficiency| 4x LED-0704/930
3000 K
CRI > 90
14960 lm
12365 lm
121,2 lm / W
---|---

24 730 K4

Module designation
Colour temperature
Colour rendering index
Module luminous flux
Luminaire luminous flux
Luminaire luminous efficiency| 4x LED-0704/940
4000 K
CRI > 90
15420 lm
12745 lm
125 lm / W
---|---

Notice prior to installation :
Please note that 2 persons are imperatively required for the installation of the luminaire!
In order to avoid deformation under its own weight, do not deposit luminaire on its domed synthetic cover outside the package!
When mounting the luminaires, it must be ensured that the ceiling surface has sufficient load-bearing capacity.
The fixing material included in delivery must be checked for suitability with the specific mounting plate used. If necessary, replace with suitable fixing material.
Please check the secure mounting of the luminaires after installation.BEGA
24 730 Ceiling and Wall Luminaire - secure mountingUndo lateral grub screw 1 (wrench size 3) turn the mounting plate 2 counter-clockwise and remove it from the luminaire housing.

Installation

Fix the mounting plate with enclosed or any other suitable fixing material onto the mounting surface.BEGA 24 730 Ceiling and Wall Luminaire - mounting
surfaceUndo the Allen screws (wrench size 4) and remove the connection cover from the luminaire housing to make the electrical connection.
Lead mains supply cable through the cable entry of the connecting compartment cover.
Make the earth conductor connection and the electrical connection.
The two loose plug-in terminals marked DALI are provided for digital control purposes.
If these terminals are not assigned, the floodlight will work with full light output.

BEGA 24 730 Ceiling and Wall Luminaire - floodlightThe steel retention wires must be used to install the luminaire on the ceiling.
Hook the ends of the 4 steel wires from the luminaire housing into the recesses of the mounting brackets on the mounting plate.
To secure the steel wires, screw the hexagon socket screws (Pos. A) into the holes (Pos. B).
Push plug into coupler as far as it will go.
Assemble connecting compartment cover.
Make sure that the gasket is positioned correctly. BEGA 24 730 Ceiling and
Wall Luminaire - gasketInsert the luminaire housing into the mounting plate and turn it clockwise into the four guides as far as the stop.
As you do so, make sure that all four retention bolts of the luminaire housing are firmly seated in the guides of the mounting plate and that it is no longer possible to remove the luminaire.
Screw in the grub screw on the side as far as the stop in order to lock the luminaire in place.
You must not feel any resistance when you do this. If you do, check that the luminaire housing
is correctly seated in the mounting plate.

Cleaning · Maintenance`

Clean dirt and debris from the luminaire  regularly with a clean, soft, lint- free cloth that is kept damp throughout the cleaning.
If possible, please use water for this, adding a little commercial dishwashing detergent.
For lacquered surfaces we recommend the use of BEGA Lacquer Care Set 71 179.
Cleaning agents containing solvents and high-pressure cleaners are unsuitable for cleaning and maintenance. Replacing the LED power supply unit
Disconnect the electrical installation.
Undo the hexagon socket screws (wrench size 4) and remove the connection cover from the luminaire housing to replace the power supply unit.
Undo the hex nut, slide the carrier plate with the power supply unit and remove it from the luminaire housing.
Install in reverse order.

Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the
LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.

Spares
Synthetic cover
LED power supply unit
LED module 3000 K
LED module 4000 K
Gasket cover

Technical amendments reserved
BEGA Gantenbrink-Leuchten KG
· Postfach 31 60
· 58689 Menden
· info@bega.com
· www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals