BEGA 84567 In-Ground Luminaire Instruction Manual

June 12, 2024
BEGA

BEGA LOGO In-ground luminaire

84567 In-Ground Luminaire

BEGA 84567 In Ground Luminaire - Instructions

Instructions for use
Application
Floodlight with symmetrical wide beam light distribution.
For embedding in gravel, lawns, flower beds, or in compacted, non-inflammable surfaces. Drive-over luminaire for vehicles with pneumatic tyres.
Please note:
Luminaire must not be used for installation in road lanes, where the fixture is exposed to a horizontal strain due to braking, acceleration and change of direction. For walk-through public areas, we recommend skid-blocking glass – see accessories.

Product description

Luminaire made of stainless steel
Steel grade no. 1.4301
Clear safety glass
Reflector surface made of pure aluminium
Optical silicone lens · BEGA Hybrid Optics®
1,8 m water-resistant connecting cable
07RN8-F 5 G 1◻ with implemented water
stopper and 1.2 m PVC cable conduit
BEGA Ultimate Driver®
LED power supply unit
220-240 V ≂ 0/50-60 Hz
DC 176-264 V
DALI controllable
A basic isolation exists between power cable and control line
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
Safety class I
Protection class IP 68 10 m
Dust-tight and water pressure tight
Maximum submersion depth 10 m
Not suitable for permanent operation under water
Pressure load 2,000 kg (~20 kN)
Impact strength IK10
Protection against mechanical impacts < 20 joule
Maximum surface temperature 30 °C
(measured according to EN 60598 of ta 15 °C)c
**** – Conformity mark
– Safety mark
Weight: 7.2 kg
This product contains light sources of energy efficiency classes D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
We recommend fuse protection via a residual current circuit breaker to be provided by the customer.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

BEGA 84567 In Ground Luminaire - Installation

Installation

Luminaire housing must not be installed in heat-insulating material.
Luminaire for recessed mounting in gravel, lawns and flower beds.
The recessed depth must be arranged such that the trim ring is above ground level.
When installed in compacted surfaces make sure that the housing is firmly fixed and that the trim ring is not directly resting on the pavement or other surfaces (Fig. A).
For this purpose installation housing 70 688 can be practical (Fig. B).
The electrical connection must be carried out with matching protection class and safety class with suitable connection terminals (not included in the scope of delivery) at the luminaire power supply cable.
We recommend that you use distribution box 70 730 or 71 053 for this purpose.
Ensure that the connection cable is correctly connected.
Make the mains connection to the brown (L), blue (N) and green-yellow wires ( ****).
The control cables are connected via the two wires marked DALI.
If these wires are not assigned, the luminaire will work with full light output.
Tighten the screws in the trim ring evenly crosswise.
Torque = 5 Nm.

Please note:
Do not remove the desiccant bag from the luminaire housing.
It is needed to remove residual moisture.

Lamp

Module connected wattage| 35.7 W
Luminaire connected wattage| 38.4 W
Rated temperature| ta = 25 °C
Ambient temperature| ta max = 40 °C
84 567 K27
Module designation| LED-0785/827
Colour temperature| 2700 K
Colour rendering index| CRI > 80
Module luminous flux| 5760 lm
Luminaire luminous flux| 3886 lm
Luminaire luminous efficiency| 101,2 lm / W
84 567 R K27
Module designation| LED-0785/827
Colour temperature| 2700 K
Colour rendering index| CRI > 80
Module luminous flux| 5760 lm
Luminaire luminous flux| 3370 lm
Luminaire luminous efficiency| 87,8 lm / W
84 567 K3
Module designation| LED-0785/830
Colour temperature| 3000 K
Colour rendering index| CRI > 80
Module luminous flux| 6010 lm
Luminaire luminous flux| 4055 lm
Luminaire luminous efficiency| 105,6 lm / W
84 567 R K3
Module designation| LED-0785/830
Colour temperature| 3000 K
Colour rendering index| CRI > 80
Module luminous flux| 6010 lm
Luminaire luminous flux| 3517 lm
Luminaire luminous efficiency| 91,6 lm / W
84 567 K4
Module designation| LED-0785/840
Colour temperature| 4000 K
Colour rendering index| CRI > 80
Module luminous flux| 6165 lm
Luminaire luminous flux| 4160 lm
Luminaire luminous efficiency| 108,3 lm / W
84 567 R K4
Module designation| LED-0785/840
Colour temperature| 4000 K
Colour rendering index| CRI > 80
Module luminous flux| 6165 lm
Luminaire luminous flux| 3608 lm
Luminaire luminous efficiency| 94 lm / W

Lighting technology
Half beam angle 35°

Cleaning · Maintenance

After installation, the luminaire should first be cleaned. Building dust, residues from contact adhesives, paint splashes and rust film must be completely removed. Never use high pressure cleaners and cleaning implements made of normal steel, steel brushes or steel wool because they cause extraneous rust to form. When using stainless steel cleaners, please read the directions carefully.
Cleaning agents containing hydrochloric acid and chlorides should never be used. We recommend cleaning the luminaires regularly.

Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the electrical installation.
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during relamping.
Clean dirt and deposits from key openings of screw head. Do not use a high pressure cleaner. Open the luminaire and clean.
Use only solvent-free cleaners.
The luminaire housing must be completely clean and absolutely dry.
Please follow the installation instructions for the LED module.
Check all screws and threads thoroughly and grease them.
Check the gasket and replace, if necessary.
A broken glass must be replaced.
Insert glass with gasket – with stepped side turned upward and the groove structure of the gasket turned downward – into the luminaire housing. Make sure that the glass is correctly positioned in the gasket bed.
Place trim ring onto glass step and tighten screws crosswise.
Torque = 5 Nm.

Accessories

14000233R Skid-blocking glass BEGA skid-blocking glass with the highest rating R 13 according to DIN 51130 can be used without restriction for all public areas. Abrasion resistance according to EN ISO 10545-7 Class 3
70 688 Installation housing
Distribution box for installation in soil
70 730 Distribution box with 7 cable entries Connection terminals 5 x 4▢
71 053
Distribution box with 10 cable entries Connection terminals 6 x 16▢
For the accessories a separate instructions for use can be provided upon request.

Spares

Spare glass skid blocking 14 000 233 R
Spare glass 14 001 523
LED power supply unit DEV-0270/700
LED module 2700 K LED-0785/827
LED module 3000 K LED-0785/830
LED module 4000 K LED-0785/840
Reflector 76 001 817
Gasket glass 83 002 037

BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
[email protected]
www.bega.com 84 567

Documents / Resources

| BEGA 84567 In-Ground Luminaire [pdf] Instruction Manual
84567, 84567 In-Ground Luminaire, In-Ground Luminaire, Luminaire
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BEGA User Manuals

Related Manuals