BEGA 50807.5 Wall Luminaire Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
50 807.5 ****
Wall luminaire for indoor use
Instructions for use
Application
Wall luminaire · indoor luminaire for the glare free illumination of wall surfaces with the mounting surface being the reflection surface. The light emits upwards and downwards.
Product description
Luminaire housing made of aluminium, finish Colour velvet black
Synthetic cover with light diffusing structure Reflector made of pure anodised
aluminium 2 elongated fixing holes
Width 5.5 mm · 1450 mm spacing 1 cable entry for through-wiring for mains
cable
Connection terminal 2.5@
Earth conductor connection
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-280 V
During DC operation the LED power is reduced to 15 %
DALI-controllable
Number of DALI addresses: 1
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
Impact strength IK04
Protection against mechanical impacts < 0.5 joule
– Safety mark
****– Conformity mark
Weight: 9.3 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Komponenten sind nach DIN EN 61547 gegen
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components. You can find them on our
website at www.bega.com.
Lamp
Module connected wattage | 122 W |
---|---|
Luminaire connected wattage | 130 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 45 °C |
50 807.5 K3
Module designation | 10x LED-1049/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 18300 lm |
Luminaire luminous flux | 15595 lm |
Luminaire luminous efficiency | 120 lm / W |
Installation
LED are high-quality electronic components! Please avoid touching the light
output opening of the LED directly during installation or relamping. Undo the
hexagon socket head screws (wrench size 3 mm) and lift luminaire top. Loosen
earth connection (plug connection) and LED-connection between luminaire top
and luminaire base. Lead the mains supply cable through the cable entry of the
luminaire base. Note position of application “arrow down”. Fix luminaire base
with enclosed or any other suitable fixing material onto the mounting surface.
Make earth conductor connection. Push silicone sleeves over the lines and make
electrical connection. For digital control please use the connecting terminal
DA, DA. In case this terminal is not used the luminaire will be operated at
full light output. Make earth connection (plug connection) and LED-connection
between luminaire top and luminaire base again.
Note position of application of the luminaire “arrow down”. Install luminaire
top part, adjust it and tighten screws evenly.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified persons using standard tools.
Disconnect the system and open the luminaire. Undo one of the two external
locking screws (Torx) in the luminaire housing and remove the lateral housing
cover. Remove the synthetic cover from the profile of the luminaire housing.
Remove the LED module. Install the replacement LED module. Please follow the
installation instructions for the LED module. A defective synthetic cover must
be replaced. Close up the luminaire again in reverse order.
Spares
Synthetic cover | 15 000 631 |
---|---|
LED power supply unit | DEV-0390/700i |
LED module 3000 K | LED-1049/930 |
Reflector short | 76 001 896 B1 |
Reflector long | 76 001 896 B2 |
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden