CERBERUS PYROTRONICS FM-200 Extinguishing Systems Instructions

June 9, 2024
CERBERUS PYROTRONICS

CERBERUS PYROTRONICS FM-200 Extinguishing Systems

Features

  • Available in both 22 inch and 30 inch Sizes
  • Easier to Install than Copper Tubing
  • Easier Servicing of Cylinders
  • Minimum Bursting Pressure of 5000 psi
  • UL Listed

MODELS

Description

To simplify installation and to ease servicing of cylinders, ¼ inch flexible hose can be used in place of ¼ inch copper tubing. The need to flare tubing is thus eliminated. Hoses are fitted with swivel nuts for connection to the ¼ inch checkvalve in the master cylinder and to ¼ inch tees on pressure actuators on slave cylinders. The tees used with flexible hoses are fitted with swivel nuts for connection to pressure actuators. The hoses are furnished in 2 lengths to suit all cylinder sizes 10 lb. through 500 lb.

Architect/Engineer Specifications

Interconnection between cylinders for pressure operation shall be made using stainless steel reinforced braided hose with swivel nut connections which fit standard male 37° flared tubing fittings. It shall have a minimum working pressure of 3000 psi and a minimum burst pressure of 15000 psi

Ordering Information

Model No. Description Part No.
AC-30 ¼ inch Flexible Braided Hose, 30” Length 500-264986
AC-22 ¼ inch Flexible Braided Hose, 22” Length 500-264987

Cerberus Pyrotronics 8 Ridgedale Avenue Cedar Knolls, NJ 07927

6/96 2.5M CPY-IG Printed in U.S.A.

Cerberus Pyrotronics 50 East Pearce Street Richmond Hill, Ontario L4B, 1B7 CN