BEGA 24 357 Ceiling and Wall Luminaire Instruction Manual

June 12, 2024
BEGA

BEGA 24 357 Ceiling and Wall Luminaire

Product Information

Product Name| Decken- und Wandleuchte Ceiling and wall luminaire Plafonnier
et applique
---|---
Model Number| 24 357
Application| Unshielded ceiling and wall luminaire with high protection
class. A luminaire made of die cast aluminium and with an impact
resistant synthetic diffuser.
Safety| The installation and operation of this luminaire are subject to
national safety regulations. Installation and commissioning may
only be carried out by a qualified electrician. The manufacturer
accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the
luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage Protection| The electronic components installed in the luminaire are
protected against overvoltage in accordance with DIN EN 61547. To
achieve an additional protection against e.g. transients, etc. we
recommend separate overvoltage protection components. You can find
them on our website at www.bega.com.

Product Usage Instructions

  1. Install the luminaire in any burning position.
  2. Fix the luminaire base with the provided or suitable fixing material onto the mounting surface.
  3. Tighten the screw cable gland for the cable connection.
  4. Make the earth conductor connection and the electrical connection.

Ceiling and wall luminaire

Instructions for use

Application
Unshielded ceiling and wall luminaire with high protection class.
A luminaire made of die cast aluminium and with an impact-resistant synthetic diffuser.

Product Description

  • Luminaire made of aluminium alloy,aluminium and stainless steel
  • BEGA Unidure® coating technology
  • White synthetic diffuser 2 mounting holes ø 4.2 mm
  • Distance apart 175 mm 2 screw cable glands with strain relief for through-wiring power connecting cable ø 7–12 mm
  • 1 screw cable gland closed at the factory with a dummy plug
  • Connecting terminal and earth conductor terminal 2.5@
  • BEGA Ultimate Driver®
  • LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DC 176-264 V
  • BEGA Thermal Switch®
  • Temporary thermal shutdown to protect temperature-sensitive components
  • Safety class I
  • Protection class IP 65
  • Dust-tight and protection against water jets Impact strength IK10
  • Protection against mechanical impacts < 20 joule
  • – Safety mark
  • – Conformity mark
  • Weight: 0.95 kg

This product contains light sources of energy efficiency class(es) C, D

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Lamp

  • Module connected wattage 6 W
  • Luminaire connected wattage 7.1 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 50 °C

24 357 K3

  • Module designation LED-1054/830
  • Colour temperature 3000 K
  • Colour rendering index CRI > 80
  • Module luminous flux 995 lm
  • Luminaire luminous flux 515 lm
  • Luminaire luminous efficiency 72,5 lm / W

24 357 K4

  • Module designation LED-1054/840
  • Colour temperature 4000 K
  • Colour rendering index CRI > 80
  • Module luminous flux 1045 lm
  • Luminaire luminous flux 541 lm
  • Luminaire luminous efficiency 76,2 lm / W

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Installation

  • The luminaire can be installed in any burning position.
  • Undo hexagon socket head screws (wrench size 3 mm) through the opening in the luminaire housing up to the stop and lift luminaire top.
  • Disconnect the earth conductor connection from the plug connection.
  • Disconnect plug-connection of the LED connecting cable.
  • Lead the mains supply cable through the screw cable gland into the luminaire back housing.
  • The installed black gasket insert is intended for cables ø < 10 mm.
  • For cables ø 10-12 mm the enclosed grey gasket insert must be used.
  • In case of through-wiring replace the factory installed dummy plug with the enclosed corresponding gasket insert.
  • At the same time, use the enclosed synthetic cone-thrust collar between gasket insert and thrust screw (wrench size 22 mm) (see sketch).

Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface.
Tighten screw cable gland.
Make the earth conductor connection and the electrical connection.

In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.

Connect the LED connection cable by means of a plug connector.
Make earth conductor connection between luminaire top and luminaire base.
Push plug into coupler as far as it will go.
Make sure that gasket is positioned correctly.
Install the luminaire top, press on and tighten screws evenly.

Cleaning · Maintenance

  • Clean dirt and debris from the luminaire regularly with a clean, soft, lint-free cloth that is kept damp throughout the cleaning.
  • If possible, please use water for this, adding a little commercial dishwashing detergent.
  • For lacquered surfaces we recommend the use of BEGA Lacquer Care Set 71 179.
  • Cleaning agents containing solvents and highpressure cleaners are unsuitable for cleaning and maintenance.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Inspect and, if necessary, replace the luminaire gaskets.
  • Defective glass must be replaced.
  • Close the luminaire.

Spares

  • Synthetic cover 15 000 595
  • LED power supply unit DEV-0304/350
  • LED module 3000 K LED-1054/830
  • LED module 4000 K LED-1054/840
  • Gasket glass 83 002 010
  • Gasket housing 83 002 015

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals