Table 1 Software Version

Date Version Note
2021-06-08 1.0 Original release.
2021-07-19 1.1 Update pictures in the manual.
2021-11-06 1.2 Update pictures in the manual.

 OVERVIEW

SG485-3 is the expansion module of the RS485 interface, which has 3 interfaces, namely the RS485 host interface, RS485 slave 1 interface, and RS485 slave 2 interfaces. It can convert 1# RS485 interface to 2# RS485 interface, providing convenience for customers to monitor and collect data via Modbus-RTU protocol.

PERFORMANCE AND CHARACTERISTICS

Its main characteristics are as follows:
─ With 32-bit ARM SCM, high hardware integration, and improved reliability;
─ DC(8~35)V continuous power supply;
─ 35mm guide rail installation method;
─ Modular design and pluggable connection terminals; compact structure with easy mounting.

SPECIFICATION

Table 2 Performance Parameters

Items Contents
Working Voltage DC(8~35)V
**** RS485 Interface Baud rate: 9600bps, max. communication distance can

reach 1,000m when a 120Ω shielded twisted pair line is applied.
Stop bit: 1-bit’
Parity bit: None
Case Dimension| 71.6mmx92.7mmx60.7mm (LxWxH)
Working Temperature| (-40~+70)°C
Working Humidity| (20~93)%RH
Storage Temperature| (-40~+80)°C
Protection Level| IP20
Weight| 0.14kg

WIRING

Fig.1 Mask Diagram

Table 3 Indicators Description

No. Indicator Description
1. POWER Power indicator, always on when powered on.
2. RS485 RS485 HOST communication indicator flashes 100ms when sending or

receiving data.
3.| RS485(1)| RS485 SLAVE(1) communication indicator, flashes 100ms when sending or receiving data.
4.| RS485(2)| RS485 SLAVE(2) communication indicator, flashes 100ms when sending or receiving data.

Table 4 Wiring Terminals Description

No. Function Cable Size Remark
1. B- 1.0mm2 DC power negative.
2. B+ 1.0mm2 DC power is positive.
3. ****

RS485 HOST

| TR| ****

0.5mm2

| RS485 host interface communicates with controller, TR can be shortly connected with A(+), which is equivalent to connecting 120Ω matching the resistor between A(+) and B(-).
4.| A(+)
5.| B(-)
6.| ****

RS485 SLAVE(1)

| TR| ****

0.5mm2

| RS485 slave interface communicates with PC monitoring interface, TR can be shortly connected with A(+), which is equivalent to connecting 120Ω the matching resistor between A(+) and B(-).
7.| A(+)
8.| B(-)
9.| ****

RS485 SLAVE(2)

| B(-)| ****

0.5mm2

| RS485 slave interface communicates with PC monitoring interface, TR can be shortly connected with A(+), which is equivalent to connecting 120Ω the matching resistor between A(+) and B(-).
10.| A(+)
11.| TR

Table 5 Communication Address Setting

Communication Address Setting

Address| Host Address| Slave 1 Address| Slave 2 Address
Dial Switch No.| 1| 2| 3| 4| 5| 6| 7| 8



The corresponding relation between dial switch combination and communication address

| 00:1| 000:1| 000:1
01:2| 001:2| 001:2
10:3| 010:3| 010:3
11:4| 011:4| 011:4
/| 100:5| 100:5
/| 101:6| 101:6
/| 110:7| 110:7
/| 111:8| 111:8

ELECTRICAL CONNECTION DIAGRAM

This module is applied for the expansion of the RS485 interface, which can convert 1# RS485 interface to 2# RS485 interface. Common connection examples are as follows: SmartGen SG485 3 Interface Expansion Module -
DIAGRAM

OVERALL DIMENSION AND INSTALLATION

SmartGen SG485 3 Interface Expansion Module - OVERALL
DIMENSION

SmartGen — make your generator smart
SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Zhengzhou
Henan Province
P. R. China
Tel: +86-371-67988888/67981888/67992951 +86-371-67981000(overseas)
Fax: +86-371-67992952
Web : www.smartgen.com.cn/
www.smartgen.cn/
Email: sales@smartgen.cn

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals