SmartGen SGQ_ATS Automatic Transfer Switch User Manual
- June 2, 2024
- SmartGen
Table of Contents
SmartGen SGQ_ATS Automatic Transfer Switch
SUMMARY
SGQ Automatic Transfer Switch (ATS) is used under conditions of AC660V 50/60Hz or DC250V It is two-stage PC class type with an electromagnetism drive structure, which can make fast load transfer (transfer time ≤80ms) of two power circuits. It can be widely used for national one-class load, for example: high buildings, post, telecommunications, coal mines, ships, industrial assembly lines, health care, military facilities etc. The two power circuits can be grid, auto start genset, storage battery etc.
STRUCTURE AND CHARACTERISTICS
SGQ Automatic Transfer Switch (ATS) adopts an electromagnetic coil drive, electrical and mechanical interlocking structure, main loop structure of two static contacts and one dynamic contact. Dynamic contact applies V type, which ensures two power circuits shall not be short circuit. N-type and T type apply double coils; M-type applies single coil. Coils are only energized at the time of transfer and this extends the usage life of switch to a great degree. Coil control power can be supplied by master/slave AC or DC power and it is not needed to add another control power. Switch itself has mechanical or electrical close indication, and at the same time it provides volts-free auxiliary contact.
APPEARANCE AND CLASSIFICATION
ILLUSTRATION
SGQ ATS can be classified into 3 types by appearance: N type, T type, M type.
Each type has 3P and 4P, and N type still has 2P.
The rated current series are: 63A, 125A, 160A, 200A, 250A, 400A, 630A, 800A,
1000A and 1250A. Switch appearances are as below.
Table 2 Switch Appearance
N TYPE CASE DIMENSIONS AND TECHNICAL DATA
Table 3 N Type Case Dimensions
**** Model| Overall size (mm)| Installation size (mm)| Copper bar and
location hole (mm)
---|---|---|---
A| D| C| B| E| M| U| T
2P| 3P| 4P| 2P| 3P| 4P
SGQ63N| 172| 200| 228| 186| 155| 139| 167| 195| 165| 5| 12| 27
SGQ125N| 192| 228| 265| 186| 155| 159| 195| 232| 165| 7| 20| 37
Table 4 N Type Technical Data
Type | SGQ63N | SGQ125N |
---|---|---|
Rated current | 63A | 125A |
Rated limited short-circuit current | 35kA | |
Coil operating voltage | AC220V (176~265)V | |
Coil operating current | 3.5A | |
Auxiliary contact | 1A 250VAC, N/O, Free Voltage, Each side has 2. | |
Operation time | Mechanical | 10000 times |
Electrical | 4000 times | |
Number of poles | 2P | 3P |
Net weight (kg) | 3.5 | 4 |
Operation cycle | 15 seconds /time |
T TYPE CASE DIMENSIONS AND TECHNICAL DATA
Table 5 T Type Case Dimensions
**** Model| Overall size(mm)| Installation size (mm)| Copper bar and location
hole (mm)
---|---|---|---
A| D| C| B| E| M| NM| U| NU| T
3P| 4P| 3P| 4P
SGQ160T| 326| 375| 292| 146| 307| 356| 200| 9| 9| 20| 20| 49
SGQ200T| 326| 375| 292| 146| 307| 356| 200| 9| 9| 20| 20| 49
SGQ250T| 326| 375| 292| 146| 307| 356| 200| 9| 9| 20| 20| 49
SGQ400T| 356| 405| 292| 146| 337| 386| 200| 11| 9| 30| 20| 59
SGQ630T| 368| 427| 310| 146| 349| 408| 200| 14| 14| 40| 30| 63
Table 6 T Type Technical Data
Type | SGQ160T | SGQ200T | SGQ250T | SGQ400T | SGQ630T |
---|---|---|---|---|---|
Rated current | 160A | 200A | 250A | 400A | 630A |
Rated limited short-circuit current | 35kA | ||||
Coil operating voltage | AC220V (176~265)V | ||||
Coil operating current | 7A | ||||
Auxiliary contact | 1A 250VAC, N/O, Free Voltage, Each side has 2. | ||||
**** Operation time | Mechanical | 8000 times | |||
Electrical | 3000 times | ||||
Number of poles | 3P | 4P | 3P | 4P | 3P |
Net weight (kg) | 18 | 20 | 18 | 20 | 18 |
Operation cycle | 10 seconds/time |
M TYPE CASE DIMENSIONS AND TECHNICAL DATA
Table 7 M Type Case Dimensions
Models| Overall size(mm)| Installation size(mm)| Copper bar and location
hole (mm)
---|---|---|---
A|
D
| ****
C
| B| ****
E
| ****
M
| ****
U
| ****
T
3P| 4P| 3P| 4P
SGQ630M| 530| 600| 280| 345| 490| 560| 210| 12| 30| 90
SGQ800M| 530| 600| 280| 345| 490| 560| 210| 12| 40| 90
SGQ1000M| 530| 600| 280| 345| 490| 560| 210| 12| 45| 90
SGQ1250M| 530| 600| 280| 345| 490| 560| 210| 12| 55| 90
Table 8 M Type Technical Data
Type | SGQ630M | SGQ800M | SGQ1000M | SGQ1250M |
---|---|---|---|---|
Rated current | 630A | 800A | 1000A | 1250A |
Rated limited short-circuit current | 50 kA | |||
Coil operating voltage | AC220V (176~265)V | |||
Coil operating current | 16A | |||
Secondary contact | 1A 250VAC, N/O, Free Voltage, Each side has 1. | |||
**** Operation time | Mechanical | 6000 times | ||
Electrical | 3000 times | |||
Number of poles | 3P | 4P | 3P | 4P |
Net weight (kg) | 37 | 43.5 | 39 | 46 |
Operation cycle | 15s/time | 20s/time | 25s/time | 25s/time |
WORKING REQUIREMENTS
Table 9 Working Requirements
Item | Requirements |
---|---|
Working temperature | (-40~+70)ºC |
Working Humidity | (20~90)%RH |
Installation elevation | ≤5000m |
Pollution class | III |
Installation type | Ⅳ |
ATS WIRING CONNECTION DIAGRAM
N AND T TYPE WIRING CONNECTION DIAGRAM
- Position control I
- Position control II
- Aux. contact of position I
- Aux. contact of position II
- SB2 is #2 power close button
- SB1 is #1 power close button
M TYPE WIRING CONNECTION DIAGRAM
- Position control I
- Position control II
- Aux. contact of position I
- Aux. contact of position II
INSTALLATION AND DEBUGGING
All operations about ATS installation and debugging shall be conducted by professionals or persons knowing the switch device and protection and precaution measures must be considered during the operation. Wiring connection of main loop must make sure leading wire is not taking any pressure or force. Before installation and debugging please check firstly whether switch is damaged or whether there is harmful environment effect on it. At the same time please check whether there is loose wire resulting from transportation; clear the smudge, especially the smudge on the surface of insulating parts. The smudge probably is caused by the packing materials in the transportation process or in the storage process. Please make sure the phase sequences are in accordance at connecting the first circuit; please observe the wiring connection diagram of user manual strictly at connecting the second circuit and pay attention to control power voltage class at the same time. Ground must be well connected on switch installation. Considering personal safety and switch changeover rapidity, debugging handle can only be used for debugging and users are prohibited to operate on-load with debugging handle. First use the handle to operate switch, and if nothing unusual occurs, then operate button manually. If nothing unusual happens, then normal running can start.
ORDER MODELS
SmartGen make your generator smart
SmartGen Technology Co., Ltd.
No. 28 Jinsuo Road Zhengzhou City Henan Province P. R. China
Tel: 86 371 67988888/67981888 /67992951+86 371 67981000(overseas)
Fax: 86 371 67992952
Web: www.smartgen.com.cn/
www.smartgen.cn/
Email: sales@smartgen.cn
All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of t he copyright holder. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to SmartGen Technology at the address above. Any reference to trademarked product names used within this publication on is owned by their respective companies. SmartGen Technology reserves the right to change the contents of this document without prior notice.
Table 1 Software Version
Date | Version | Note |
---|---|---|
2006-03-18 | 1.0 | Original release. |
2010-10-19 | 2.0 | Revision. |
2011-06-08 | 2.1 | Modify the wiring diagram of N type, T type and M type. |
2011-11-22 | 2.2 | Modify the technical data of N type, T type and M type. |
2012-06-29 | 2.3 | Lines of wiring diagram are bold. |
2012-11-08 | 2.4 | Format Modification. |
2014-05-30 | 2.5 | Add terminal number in wiring connection diagram. |
2015-03-30 | 2.6 | Modify some details. |
2019-06-26 | 2.7 | Modify M type wiring diagram, and add Q type switch. |
2019-09-11 | 2.8 | Modify wiring diagram of M type and Q type. |
2020-01-07 | 2.9 | Delete Q type switch and related parameters. |
2022-01-04 | 3.0 | Modify M type wiring diagram. |