SmartGen AIN16-PT Marine Engine Controller User Manual

June 3, 2024
SmartGen

SmartGen AIN16-PT Marine Engine Controller User Manual
SmartGen AIN16-PT Marine Engine Controller

Introduction

All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder.
Smartgen Technology reserves the right to change the contents of this document without prior notice.
If the colors of actual products are different from the manual, please take the actual product as the standard

Software Version.

Date Version Content
2014-06-16 1.0 Original release.
   
   

This manual is suitable for AIN16-PT Analog Input Module only.

Clarification of notation used within this publication.

SIGN INSTRUCTION
NOTE Highlights an essential element of a procedure to ensure

correctness.
CAUTION| Indicates a procedure or practice, which, if not strictly observed, could result in damage or destruction of equipment.
WARNING| Indicates error operation may cause death, serious injury and significant property damage.

OVERVIEW

AIN16-PT analog input module is an expansion module which has 16 analog input channels and each channel is resistance PT100 input. The data are transmitted to the HMC9000 controller for processing via CANBUS port. Different alarm threshold values can be set for each sensor via HMC9000 controller, enabling module to basically meet all kinds of customer demands.

PERFORMANCE AND CHARACTERISTICS

  • With ARM-based 32-bit SCM, high integration of hardware and more reliable;
  • Must be used with HMC9000 together;
  • CANBUS communication baud rate can be set as 250kbps or 125kbps via dial switch;
  • Module address can be set as 1 or 2.
  • Widely power supply range DC(18~35)V, suitable to different starting battery voltage environment;
  • 35mm rail mounting type;
  • Modular design, pluggable terminal, compact structure with easy installation.
TECHNICAL PARAMETERS
Item Content
Working Voltage DC18.0V~35.0V    continuous power supply
Power Consumption <0.5W
Sensor type PT100
Measurement accuracy 0.5°C
Case Dimension 161.6mm x 89.7mm x 60.7mm
Rail Dimension 35mm
Working Conditions Temp.:(-25~+70)°C        Humidity:(20~93)%RH
Storage Conditions Temp.:(-25~+70)°C
Weight 0.33kg
CONNECTION

Connection

No. Function Cable Size Description
1 B- 1.0mm2 DC power supply negative input.
2 B+ 1.0mm2 DC power supply positive input.
3 CAN(H) 0.5mm2 A CANBUS port which communicate with HMC9000 controller.

120Ω shielding wire with its one end grounded is recommended.
4| CAN(L)
5| CH16| C| 0.5mm2| PT100 Sensor 16 COM
6| B| PT100 Sensor 16 terminal
7| A
8| CH15| C| 0.5mm2| PT100 Sensor 15 COM
9| B| PT100 Sensor 15 terminal
10| A
11| ****

CH 14

| C| 0.5mm2| PT100 Sensor 14 COM
12| B| PT100 Sensor 14 terminal
13| A
14| ****

CH 13

| C| 0.5mm2| PT100 Sensor 13 COM
15| B| PT100 Sensor 13 terminal
16| A
17| ****

CH 12

| C| 0.5mm2| PT100 Sensor 12 COM
18| B| PT100 Sensor 12 terminal
19| A
20| CH 11| C| 0.5mm2| PT100 Sensor 11 COM
21| B| PT100 Sensor 11 terminal
22| A
23| CH 10| C| 0.5mm2| PT100 Sensor 10 COM
24| B| PT100 Sensor 10 terminal

AIN16-PT Analog Input Module

No. Function Cable Size Description
25   A  
26 CH 1 A 0.5mm2
27 B
28 C PT100 Sensor 1 COM
29 CH 2 A 0.5mm2
30 B
31 C PT100 Sensor 2 COM
32 CH 3 A 0.5mm2
33 B
34 C PT100 Sensor 3 COM
35 CH 4 A 0.5mm2
36 B
37 C PT100 Sensor 4 COM
38 CH 5 A 0.5mm2
39 B
40 C PT100 Sensor 5 COM
41 CH 6 A 0.5mm2
42 B
43 C PT100 Sensor 6 COM
44 CH 7 A 0.5mm2
45 B
46 C PT100 Sensor 7 COM
47 CH 8 A 0.5mm2
48 B
49 C PT100 Sensor 8 COM
50 CH 9 A 0.5mm2
51 B
52 C PT100 Sensor 9 COM
  SWITCH   HMC9000 can connect to two AIN16-PT modules at the same time.

Address selection: It is module 1 when the switch 1 is connected to terminal 123 while module 2 when connect to ON terminal.
Baud rate selection: It is 250kbps when the switch 2 is connected to terminal 123 while 125kbps when connect to ON terminal.
120Ω resistance selection: There is no matched resistance when the switch 3 is connected to terminal 123 while 120Ω matched resistance has been connected when the switch 3 is connected to ON terminal.
 | POWER|  | Power supply indicator and communication status indicator; It
is flashing when the communication is abnormal.

PROTECTION

All data can be protected via HMC9000 controller. HMC9000 can connect to two AIN16-PT modules at the same time and users can select module address via dial switch.
Following parameters can be set via HMC9000:

  1. AIN16-PT module enable: HMC9000 can communicate with the module and collect the AIN16-C data only when the module is enabled;
  2. Alarm threshold and alarm enable of each sensor;

AIN16-PT can collect data only and all alarms are initiated by HMC9000 controller.
HMC9000 will initiate alarm when the sensor value is abnormal. There are two kinds of alarm: warning alarm and shutdown alarm. All alarms are handled by HMC9000 controller only

WARNING

Warning types are as follows:

No. Items Range Description

1

| Sensor 1~16 high| From “Waiting for load”  delay to “Cooling” delay| When the controller detects that the sensor 1-16 warning signals, it will initiate a warning alarm and the corresponding alarm information will be displayed on HMC9000 LCD.
2| Sensor 1~16 Low| From “Waiting for load”  delay to “Cooling” delay
3| Sensor| Always active.
1~16 open|

SHUTDOWN ALARM

Shutdown types are as follows,

NO. Items DET Range Description
1 Sensor 1~16 High From “Waiting for load” delay to “Cooling” delay When

the controller detects that the sensor 1-16 shutdown alarm, it will initiate a shutdown alarm and the corresponding alarm information will be displayed on HMC9000 LCD.
2| Sensor 1~16 Low| From “Waiting for load” delay to Cooling” delay

PARAMETER CONFIGURATION

AIN16-PT parameters can be set via HMC9000 controller or HMC9000 PC software; more details please refer to specific instruction of HMC9000.

Parameter Configuration List

Parameter Contents Default
Module Enable 0:Enable
1:Disable Disable
Sensor 1~16 set Sensor types/ Alarm Speed /Range/ High Shutdown Enable / High

Shutdown Value / High Shutdown Delay / Low Shutdown Enable / Low Shutdown Value / Low Shutdown Delay / High Warn Enable / High Warn Value / High Return Value / High Warn Delay/ Low Warn Enable / Low Warn Value / Low Return Value / Low Warn Delay For more details please refer to chapter 5.4| Sensor type: Temperature Sensor

SENSOR SETTINGS
NO. Items Contents Remarks
1 Sensor types 0:Not Used

1:Oil Pressure Sensor
2:Temperature Sensor|
2| Sensor Curve| PT100|
3| Alarm Speed| (0-200)%|
4| Range (current type)| (0-6000)|
5| High             Shutdown

Enable

| 0:Enable
1:Disable|
6| High Shutdown Value| (0-6000)|
7| High Shutdown Delay| (0-3600)s|
8| Low              Shutdown

Enable

| 0:Enable
1:Disable|
9| Low Shutdown Value| (0-6000)|
10| Low Shutdown Delay| (0-3600)s|
11| High Warn Enable| 0:Enable
1:Disable|
12| High Warn Value| (0-6000)|
13| High Return Value| (0-6000)|
14| High Warn Delay| (0-3600)s|
15| Low Warn Enable| 0:Enable
1:Disable|
16| Low Warn Value| (0-6000)|
17| Low Return Value| (0-6000)|
18| Low Warn Delay| (0-3600)s|
19| **** User-defined string| User can reset the sensors’ names which are displayed on HMC9000 LCD. e.g. rename sensor 1 as Temperature sensor. User- defined string can be edited via HMC9000 PC software only.

ELECTRICAL CONNECTIONS

AIN16-PT ELECTRICAL CONNECTION.
Electric Connections  

HMC9000 controller connect with two AIN16-PT module.
Electric Connections

INSTALLATION

Case dimensions:
Dimensions

TROUBLESHOOTING

PROBLEM POSSIBLE SOLUTION
Controller no response with power. Check batteries;

Check controller connection wirings; Check DC fuse.
CANBUS: Communication
failure| Check if CANBUS wires are connected in the opposite
way.

Customer Support

Smartgen Technology Co., Ltd.
No. 28 Jinsuo Road
Zhengzhou City
P. R. China
Tel: +86-371-67988888
+86-371-67981888
+86-371-67991553
+86-371-67992951
+86-371-67981000 (overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn/
http://www.smartgen.cn/
Email: [email protected]

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals