SmartGen AIN16-PT Marine Engine Controller User Manual
- June 3, 2024
- SmartGen
Table of Contents
SmartGen AIN16-PT Marine Engine Controller User Manual
Introduction
All rights reserved. No part of this publication may be reproduced in any
material form (including photocopying or storing in any medium by electronic
means or other) without the written permission of the copyright holder.
Smartgen Technology reserves the right to change the contents of this document
without prior notice.
If the colors of actual products are different from the manual, please take
the actual product as the standard
Software Version.
Date | Version | Content |
---|---|---|
2014-06-16 | 1.0 | Original release. |
This manual is suitable for AIN16-PT Analog Input Module only.
Clarification of notation used within this publication.
SIGN | INSTRUCTION |
---|---|
NOTE | Highlights an essential element of a procedure to ensure |
correctness.
CAUTION| Indicates a procedure or practice, which, if not strictly
observed, could result in damage or destruction of equipment.
WARNING| Indicates error operation may cause death, serious injury and
significant property damage.
OVERVIEW
AIN16-PT analog input module is an expansion module which has 16 analog input channels and each channel is resistance PT100 input. The data are transmitted to the HMC9000 controller for processing via CANBUS port. Different alarm threshold values can be set for each sensor via HMC9000 controller, enabling module to basically meet all kinds of customer demands.
PERFORMANCE AND CHARACTERISTICS
- With ARM-based 32-bit SCM, high integration of hardware and more reliable;
- Must be used with HMC9000 together;
- CANBUS communication baud rate can be set as 250kbps or 125kbps via dial switch;
- Module address can be set as 1 or 2.
- Widely power supply range DC(18~35)V, suitable to different starting battery voltage environment;
- 35mm rail mounting type;
- Modular design, pluggable terminal, compact structure with easy installation.
TECHNICAL PARAMETERS
Item | Content |
---|---|
Working Voltage | DC18.0V~35.0V continuous power supply |
Power Consumption | <0.5W |
Sensor type | PT100 |
Measurement accuracy | 0.5°C |
Case Dimension | 161.6mm x 89.7mm x 60.7mm |
Rail Dimension | 35mm |
Working Conditions | Temp.:(-25~+70)°C Humidity:(20~93)%RH |
Storage Conditions | Temp.:(-25~+70)°C |
Weight | 0.33kg |
CONNECTION
No. | Function | Cable Size | Description |
---|---|---|---|
1 | B- | 1.0mm2 | DC power supply negative input. |
2 | B+ | 1.0mm2 | DC power supply positive input. |
3 | CAN(H) | 0.5mm2 | A CANBUS port which communicate with HMC9000 controller. |
120Ω shielding wire with its one end grounded is recommended.
4| CAN(L)
5| CH16| C| 0.5mm2| PT100 Sensor 16 COM
6| B| PT100 Sensor 16 terminal
7| A
8| CH15| C| 0.5mm2| PT100 Sensor 15 COM
9| B| PT100 Sensor 15 terminal
10| A
11| ****
CH 14
| C| 0.5mm2| PT100 Sensor 14 COM
12| B| PT100 Sensor 14 terminal
13| A
14| ****
CH 13
| C| 0.5mm2| PT100 Sensor 13 COM
15| B| PT100 Sensor 13 terminal
16| A
17| ****
CH 12
| C| 0.5mm2| PT100 Sensor 12 COM
18| B| PT100 Sensor 12 terminal
19| A
20| CH 11| C| 0.5mm2| PT100 Sensor 11 COM
21| B| PT100 Sensor 11 terminal
22| A
23| CH 10| C| 0.5mm2| PT100 Sensor 10 COM
24| B| PT100 Sensor 10 terminal
AIN16-PT Analog Input Module
No. | Function | Cable Size | Description |
---|---|---|---|
25 | A | ||
26 | CH 1 | A | 0.5mm2 |
27 | B | ||
28 | C | PT100 Sensor 1 COM | |
29 | CH 2 | A | 0.5mm2 |
30 | B | ||
31 | C | PT100 Sensor 2 COM | |
32 | CH 3 | A | 0.5mm2 |
33 | B | ||
34 | C | PT100 Sensor 3 COM | |
35 | CH 4 | A | 0.5mm2 |
36 | B | ||
37 | C | PT100 Sensor 4 COM | |
38 | CH 5 | A | 0.5mm2 |
39 | B | ||
40 | C | PT100 Sensor 5 COM | |
41 | CH 6 | A | 0.5mm2 |
42 | B | ||
43 | C | PT100 Sensor 6 COM | |
44 | CH 7 | A | 0.5mm2 |
45 | B | ||
46 | C | PT100 Sensor 7 COM | |
47 | CH 8 | A | 0.5mm2 |
48 | B | ||
49 | C | PT100 Sensor 8 COM | |
50 | CH 9 | A | 0.5mm2 |
51 | B | ||
52 | C | PT100 Sensor 9 COM | |
SWITCH | HMC9000 can connect to two AIN16-PT modules at the same time. |
Address selection: It is module 1 when the switch 1 is connected to
terminal 123 while module 2 when connect to ON terminal.
Baud rate selection: It is 250kbps when the switch 2 is connected to
terminal 123 while 125kbps when connect to ON terminal.
120Ω resistance selection: There is no matched resistance when the switch
3 is connected to terminal 123 while 120Ω matched resistance has been
connected when the switch 3 is connected to ON terminal.
| POWER| | Power supply indicator and communication status indicator; It
is flashing when the communication is abnormal.
PROTECTION
All data can be protected via HMC9000 controller. HMC9000 can connect to two
AIN16-PT modules at the same time and users can select module address via dial
switch.
Following parameters can be set via HMC9000:
- AIN16-PT module enable: HMC9000 can communicate with the module and collect the AIN16-C data only when the module is enabled;
- Alarm threshold and alarm enable of each sensor;
AIN16-PT can collect data only and all alarms are initiated by HMC9000
controller.
HMC9000 will initiate alarm when the sensor value is abnormal. There are two
kinds of alarm: warning alarm and shutdown alarm. All alarms are handled by
HMC9000 controller only
WARNING
Warning types are as follows:
No. | Items | Range | Description |
---|
1
| Sensor 1~16 high| From “Waiting for load” delay to “Cooling” delay| When
the controller detects that the sensor 1-16 warning signals, it will initiate
a warning alarm and the corresponding alarm information will be displayed on
HMC9000 LCD.
2| Sensor 1~16 Low| From “Waiting for load” delay to “Cooling” delay
3| Sensor| Always active.
1~16 open|
SHUTDOWN ALARM
Shutdown types are as follows,
NO. | Items | DET Range | Description |
---|---|---|---|
1 | Sensor 1~16 High | From “Waiting for load” delay to “Cooling” delay | When |
the controller detects that the sensor 1-16 shutdown alarm, it will initiate a
shutdown alarm and the corresponding alarm information will be displayed on
HMC9000 LCD.
2| Sensor 1~16 Low| From “Waiting for load” delay to Cooling” delay
PARAMETER CONFIGURATION
AIN16-PT parameters can be set via HMC9000 controller or HMC9000 PC software; more details please refer to specific instruction of HMC9000.
Parameter Configuration List
Parameter | Contents | Default |
---|---|---|
Module Enable | 0:Enable | |
1:Disable | Disable | |
Sensor 1~16 set | Sensor types/ Alarm Speed /Range/ High Shutdown Enable / High |
Shutdown Value / High Shutdown Delay / Low Shutdown Enable / Low Shutdown Value / Low Shutdown Delay / High Warn Enable / High Warn Value / High Return Value / High Warn Delay/ Low Warn Enable / Low Warn Value / Low Return Value / Low Warn Delay For more details please refer to chapter 5.4| Sensor type: Temperature Sensor
SENSOR SETTINGS
NO. | Items | Contents | Remarks |
---|---|---|---|
1 | Sensor types | 0:Not Used |
1:Oil Pressure Sensor
2:Temperature Sensor|
2| Sensor Curve| PT100|
3| Alarm Speed| (0-200)%|
4| Range (current type)| (0-6000)|
5| High Shutdown
Enable
| 0:Enable
1:Disable|
6| High Shutdown Value| (0-6000)|
7| High Shutdown Delay| (0-3600)s|
8| Low Shutdown
Enable
| 0:Enable
1:Disable|
9| Low Shutdown Value| (0-6000)|
10| Low Shutdown Delay| (0-3600)s|
11| High Warn Enable| 0:Enable
1:Disable|
12| High Warn Value| (0-6000)|
13| High Return Value| (0-6000)|
14| High Warn Delay| (0-3600)s|
15| Low Warn Enable| 0:Enable
1:Disable|
16| Low Warn Value| (0-6000)|
17| Low Return Value| (0-6000)|
18| Low Warn Delay| (0-3600)s|
19| **** User-defined string| User can reset the sensors’ names which are
displayed on HMC9000 LCD. e.g. rename sensor 1 as Temperature sensor. User-
defined string can be edited via HMC9000 PC software only.
ELECTRICAL CONNECTIONS
AIN16-PT ELECTRICAL CONNECTION.
HMC9000 controller connect with two AIN16-PT module.
INSTALLATION
Case dimensions:
TROUBLESHOOTING
PROBLEM | POSSIBLE SOLUTION |
---|---|
Controller no response with power. | Check batteries; |
Check controller connection wirings; Check DC fuse.
CANBUS: Communication
failure| Check if CANBUS wires are connected in the opposite
way.
Customer Support
Smartgen Technology Co., Ltd.
No. 28 Jinsuo Road
Zhengzhou City
P. R. China
Tel: +86-371-67988888
+86-371-67981888
+86-371-67991553
+86-371-67992951
+86-371-67981000 (overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn/
http://www.smartgen.cn/
Email: sales@smartgen.cn
References