SmartGen DIN16A-2 Digital Input Module User Manual

June 3, 2024
SmartGen

SmartGen DIN16A-2 Digital Input Module User Manual

OVERVIEW

DINT16A-2 Digital Input Module is an expansion module which has 16 auxiliary digital input channels. Expansion module status is transmitted to DIN16A-2 by main control board via RS485.

TECHNICAL PARAMETERS

Items Contents
Working Voltage DC8.0V~ DC35.0V continuous power supply
Power Consumption <2W
Aux. Relay Input Ports 16
Case Dimension 107.6mm x 89.7mm x 60.7mm
Installation Way 35mm guide-rail installation or screw installation
Working Conditions Temperature: (-25~+70) °C       Humidity: (20~93)%RH
Storage Conditions Temperature: (-30~+80) °C
Weight 0.25kg

MODULE ADDRESS

This is a 4-bit in-line DIP switch with 16 coding status, namely 16 module addresses (from 100 to 115). When it is turned to ON, the status is 1. The module address formula is Module Address=1A+2B+4C+8D+100. For example, when ABCD is 0000, the module address is 100. When ABCD is 1000, the module address is 101. When ABCD is 0100, the moduleaddress is 102. Similarly, when ABCD is 1111, the module address is 115. The corresponding module addresses of DIP switch

A B C D Module Addresses
0 0 0 0 100
1 0 0 0 101
0 1 0 0 102
1 1 0 0 103
0 0 1 0 104
1 0 1 0 105
0 1 1 0 106
1 1 1 0 107
0 0 0 1 108
1 0 0 1 109
0 1 0 1 110
1 1 0 1 111
0 0 1 1 112
1 0 1 1 113
0 1 1 1 114
1 1 1 1 115

TERMINAL DIAGRAM

TERMINAL DIAGRAM

Description of Rear Panel Terminal Connection

No. Name Cable Size Description
1. B- 1.5mm2 DC power supply negative input
2. B+ 1.5mm2 DC power supply positive input
3. 120Ω RS485

Communication Port

| ****

0.5 mm2

| Twisted shielded line is used. If the terminal needs to match 120Ω resistance, terminal 3

and 4 need to be short circuited.

4.| RS485B (-)
5.| RS485A (+)
6.| Aux. Input Port 1| 1.0 mm2| Digital input
7.| Aux. Input Port 2| 1.0 mm2| Digital input
8.| Aux. Input Port 3| 1.0 mm2| Digital input
9.| Aux. Input Port 4| 1.0 mm2| Digital input
10.| Aux. Input Port 5| 1.0 mm2| Digital input
11.| Aux. Input Port 6| 1.0 mm2| Digital input
12.| Aux. Input Port 7| 1.0 mm2| Digital input
13.| Aux. Input Port 8| 1.0 mm2| Digital input
14.| Aux. Input Common Port| 1.0 mm2| B-port connected
15.| Aux. Input Port 9| 1.0 mm2| Digital input
16.| Aux. Input Port 10| 1.0 mm2| Digital input
17.| Aux. Input Port 11| 1.0mm2| Digital input
18.| Aux. Input Port 12| 1.0mm2| Digital input
19.| Aux. Input Port 13| 1.0mm2| Digital input
No.| Name| Cable Size| Description
---|---|---|---
20.| Aux. Input Port 14| 1.0mm2| Digital input
21.| Aux. Input Port 15| 1.0mm2| Digital input
22.| Aux. Input Port 16| 1.0mm2| Digital input
23.| Aux. Input Common Port| 1.0mm2| B-port connected
Module

Address

| Module Address|  | Select module address by DIP switch.
Input

Status

| Input Status Indicator|  | Light     when    1~16     indicators    of the

corresponding input ports are active.

Power| Power Indicator|  | Light when power supply is normal.
RS485| RS485             Communication

Indicator

|  | Light when communication is normal, flash

when abnormal.

COMMUNICATION CONFIGURATION AND MODBUS COMMUNICATION PROTOCOL

RS485 COMMUNICATION PORT

DIN16A-2 is an expansion input module with RS485 communication port, which follows Modbus-RTU communication protocol.
Communication Parameters
Module Address 100(range 100-115)
Baud Rate 9600bps
Data Bit 8-bit
Parity Bit None
Stop Bit 2-bit

INFORMATION FRAME FORMAT EXAMPLE

FUNCTION CODE 01H

Slave address is 64H (decimal 100), read 10H (decimal 100) status of starting address64H (decimal 16).

Function Code 01H Master Request Example

Request Bytes Example (Hex)
Slave Address 1 64    Send to slave 100
Function Code 1 01    Read status
Starting Address 2 00    Starting address is 100

64

Count Number| 2| 00    Read 16 status

10


CRC Code

| ****

2

| 75    CRC code which calculated by master

EC

Function Code 01H Slave Response Example

Response Bytes Example (Hex)
Slave Address 1 64    Respond slave address 100
Function Code 1 01    Read status
Read Count 1 02    16 status (total 2 bytes)
Data 1 1 01    The content of address 07-00
Data 2 1 00    The content of address 0F-08

CRC Code

| 2| F4    CRC code which calculated by slave.

64

The value of status 07-00 is indicated as 01H in Hex, and 00000001 in binary. Status 07 is the
high-order byte, 00 is the low-order byte. The state of status 07-00 is
OFF-OFF-OFF-OFF-OFF-OFF-OFF-ON.

FUNCTION CODE 03H

Slave address is 64H (decimal 100), starting address is 1 data of 64H (decimal 100) (2 bytes per data).

Function Code 03H Master Request Example

Request Bytes Example (Hex)
Slave Address 1 64    Send to the slave 64H
Function Code 1 03    Read point register
Starting Address 2 00    Starting address is 64H

64

Count Number| 2| 00    Read 1 data (total 2 bytes)

01


CRC Code

| ****

2

| CC    CRC code which calculated by master.

20

Function Code 03H Slave Response Example

Response Bytes Example (Hex)
Slave Address 1 64    Respond to the slave 64H
Function Code 1 03    Read point register
Read Count 1 02    1 data (total 2 bytes)

Data 1

| 2| 00    The content of address 0064H

01


CRC Code

| 2| 35    CRC code which calculated by slave.

8C

CORRESPONDING ADDRESS TO FUNCTION CODE

Address Item Description
100 Input Port 1 Status 1 for active
101 Input Port 2 Status 1 for active
102 Input Port 3 Status 1 for active
103 Input Port 4 Status 1 for active
104 Input Port 5 Status 1 for active
105 Input Port 6 Status 1 for active
106 Input Port 7 Status 1 for active
107 Input Port 8 Status 1 for active
108 Input Port 9 Status 1 for active
109 Input Port 10 Status 1 for active
110 Input Port 11 Status 1 for active
111 Input Port 12 Status 1 for active
112 Input Port 13 Status 1 for active
113 Input Port 14 Status 1 for active
114 Input Port 15 Status 1 for active
115 Input ort 16 Status 1 for active
Address Item Description
--- --- ---
100 Input Port 1-16 Status Unsigned

DIN16A-2 TYPICAL APPLICATION DIAGRAM

DIN16A-2 TYPICAL APPLICATION DIAGRAM

INSTALLATION

Overall dimensions are shown as follows:

INSTALLATION

Case Dimensions

support

SmartGen — make your generator smart
SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Zhengzhou
P. R. China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952