KSR LIGHTING KS98105 LED Emergency Downlight Installation Guide
- October 30, 2023
- KSR LIGHTING
Table of Contents
Navara LED Emergency Downlight
Available Rim Finishes: White, Silver and Black
Fig 1.
ØRim Size | ØCut out | Void Depth Req’d |
---|---|---|
60mm | 48mm | 220mm |
Lamp Details
Wattage: 2W
Colour: 6000K
Lumen Output: 130 Lumens
The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced.
Installation Sheet KS98105
Read these instructions before commencing installation. Please give these instructions to the owner/occupier after installation to retain for future reference/maintenance.
IP20 240V~50Hz 2W LED
This Emergency luminaire is Class II and does not require an Earth
Important Information
It is recommended that this Emergency luminaire is installed and fitted by a
qualified electrician ensuring the installation complies with current IEE
wiring regulations & local building control. These products are designed for
connection to a 240V~50Hz supply.
Any faulty, broken or damaged modules should be replaced immediately.
KSR will not accept responsibility for any claims arising from a poor
installation.
Please Note: The limited warranty shall be deemed null and void in the
following circumstances: Failure by the installer, end user or any third party
to exercise caution to protect any covered product or part from outside
damage, adverse temperature (normal operating ambient temperature 0 – 45°C),
humidity conditions, fluctuations in the electrical system or physical abuse
as well as failure related to workmanship in the installation of the products
or parts.
Important User Advice
Always switch off mains supply before installing/servicing.
As the buyer/installer and/or user of this product it is your own
responsibility to ensure that this emergency luminaire is fit for the purpose
for which you have intended and operates to the relevant standards. KSR
Lighting can’t accept any liability for loss, damage or premature failure
resulting from inappropriate use.
Please note: This luminaire is non-dimmable.
Do not use Megger or similar high voltage instruments. Due to the fact this
Emergency pack contains electronic components that maybe damaged by high test
voltages, they must be disconnected from the circuit before testing.
To prevent damage to the Emergency luminaire, do not mix with conventional
magnetic ballasts on the same electrical circuit.
At the end of life the Emergency luminaire is classed as WEEE under directive
2014/30/EU and should be disposed of in accordance with local legislation.
Installation Procedure
Familiarize yourself with the installation procedure and ensure the power is
safely isolated before installing the Emergency luminaire.
If you wish to use the silver or black rims remove the white rim by unscrewing
(anti clockwise) from the body and screw the preferred rim on to the body.
Remove the base using a screwdriver to gently pry off the base and write on
the battery label in permanent ink the date of commissioning, replace the
cover. Connect the battery to the PCB using the plug and play connector.
Taking care not to damage the circuit board.
Locate the area’s suitable to install these luminaires.
Cut a round 48mm hole and ensure there is sufficient ceiling void without
infringing on joists, water pipes or electrical cables. Remove both terminal
covers on the inverter and connect your mains supply, Permanent Live – L and
Neutral – N. These fittings are Class II and do not require an earth
connection. Replace the terminal cover.
Connect the battery lead to the circuit board and replace the terminal cover.
Ensure the inverter and head are connected then place the Inverter Pack into
the ceiling void, push back the two spring clips and offer the luminaire in to
the cut-out, carefully release the springs and allow them to pull the fitting
into place as per Fig 1.
Ensure there is adequate free air ventilation around the inverter and the
luminaire.
Turn on the power and ensure that the module is showing it’s charge indicator.
This fitting requires a minimum 24 Hour initial charge period prior to any
emergency testing, please see overleaf for testing routine, All results must
be recorded and left with the end user.
The battery has a rated duration of at least 4 years but should be replaced if the duration of operation is less than 3 hours after a 24hr charge time with no interrupted supply.
Mains supply to Emergency remote pack
L – Permanant Live
N – Neutral
Warranty
The LED luminaire comes complete with a 24 month warranty from date of purchase unless otherwise stated. Please note that the emergency packs and batteries come with a 12 month fixed warranty. Should any claim be made against battery failure within the warranty period, full and complete maintenance test reports must be provided.
KSR Lighting Aftersales: 023 92 674343
E-mail: aftersales@ksrlighting.com
Drg No. KSR98105-IS-C
Installation Particulars For End User
Commissioning:
Once the luminaire has been installed in line with the manufacturer’s
recommendations, the battery should be allowed to charge for a minimum period
of 24 hours before testing for its rated duration. If it is anticipated that
the un-switched supply may be interrupted, it is imperative that the battery
is left disconnected and commissioning is delayed until the supply is stable.
If the luminaire has been stored for a number of months, it may be necessary
to repeat the charge/discharge process several times to re-condition the
battery. After successful commissioning, the battery should be marked with the
date of commission.
Routine test and inspection should be performed in accordance with EN50172 or
otherwise local legislation. Short discharge periods of around 5 – 10 minutes
each month for the purposes of inspection will not adversely affect the
batteries and should be considered as a maintenance exercise for the battery.
Regular full discharge cycles may adversely affect the design life of the
battery.
Precautions
This product should be installed as per the following guidelines, electric shock or damage to the product may result if incorrectly installed. The luminaire should be installed by a qualified and competent electrician. If the luminaire is to be mounted in cold or hot environments, consider the battery location as temperatures below 5°C will in this case compromise the design life and more frequent battery replacements may be needed. Likewise, if the luminaire is situated in a hot environment where the temperature is maintained at 25°C or above, or sited next to large panes of glass in which case it may be exposed to thermal magnification.
Emergency Range Routine Inspection/Test
Navara X Emergency LED Batten
All tests must be undertaken at times of least risk and in accordance with EN 50172:2004 as indicated below:
Daily:
LED charge indicators shall be visually inspected for correct operation.
Monthly:
(in addition to the daily check) If automatic testing devices are used, the
results of the short duration tests shall be recorded.
Test shall be carried out as follows:
- Switch the luminaire over to emergency mode to operate from the batteries by simulating a failure of supply to the emergency circuit for a period sufficient to ensure correct luminaire operation.
Note: The period of simulation failure should be sufficient for the purpose of this clause whilst minimising damage to the system components e.g lamps. During this period, all luminaires shall be checked to ensure that they are present, clean and functioning correctly. At the end of this test period, the unswitched supply should be restored and any indicator lamp or device should be checked to ensure that is showing that the supply has been restored.
Annually:
If automatic testing devices are used, the results of the short duration tests
shall be recorded. For all other systems the monthly inspection shall be
carried out and the following additional tests made:
- Each luminaire shall be tested monthly as above but for its full duration in accordance with the manufacturer’s information.
- The unswitched supply for the luminaire should be restored and any charge indicator lamp or device should be checked to ensure that it shows the unswitched supply has been restored. The charging arrangements should be checked for proper functioning.
- The date of the test and its results shall be recorded in the system logbook.
A copy of this report must accompany any emergency luminaire returned to KSR Lighting for any reason.
KSR Lighting Ltd, Optimum House, Beeding Close, Southern Cross Trading Estate,
Bognor Regis, West Sussex, PO22 9TS.
Emergency Lighting Periodic Test Schedule
All emergency lighting should be installed and tested in accordance to EN5266-1:2011. This test schedule should remain onsite and be accessible to the relevant authorities on request.
Em No.| Luminaire Location| Luminaire Type| Start Time| Duration
(Minuets)| Pass/Fair| Comments/Actions
---|---|---|---|---|---|---
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
- √=Pass, X=Fail, N/T=Not Tested, N/A=No Access, U/T=Uncomplete Test
Site Address:
Test Conducted By:
Date of Test Completion:
Comments/Actions