KSR LIGHTING KSRSF403 LED Surface Luminaire Installation Guide
- June 9, 2024
- KSR LIGHTING
Table of Contents
KSRSF403 LED Surface Luminaire
Installation Guide
Read these instructions before commencing installation. Please give these
instructions to the owner/occupier after installation to retain for future
reference/maintainence.
IP65 IK10 240V~50Hz 10W/14W/20W
These fittings are Class II and do not need an Earth, but Earth provision is
provided.
Important Information
It is recommended that these luminaires are installed and fitted by a
qualified electrician ensuring the installation complies with current IEE
wiring regulations & local building control. These products are designed for
connection to a 240V~50Hz supply.
Any faulty, broken or damaged luminaires should be replaced immediately.
KSR will not accept responsibility for any claims arising from a poor
installation.
Please Note: The limited warranty shall be deemed null and void in the
following circumstances: Failure by the installer, end user or any third party
to exercise caution to protect any covered product or part from outside
damage, adverse temperature (normal operating ambient temperature 0°C –
+30°C), humidity conditions, fluctuations in the electrical system or physical
abuse as well as failure related to workmanship in the installation of the
products or parts.
Important User Advice
Always switch off mains supply before servicing.
Do not use Megger or similar high voltage instruments. Due to the fact this
luminaire contains electronic components that maybe damaged by high test
voltages, they must be disconnected from the circuit before testing.
To prevent damage to the driver, do not mix with conventional magnetic
ballasts on the same electrical circuit. At the end of life the luminaire is
classed as WEEE under directive 2014/30/EU and should be disposed of in
accordance with local legislation.
Installation Procedure
Isolate mains supply before installation.
Remove rim, diffuser and gear tray by turning the rim anti-clockwise.
Remove the rim, diffuser and gear tray from the body by unclipping the support
strap.
If you are using the optional chrome rim unclip the white rim from the
retaining lugs as per Fig. 1 and install the KSRSF406 rim on to the
diffuser/geartray (Do not unscrew LED tray from the diffuser).
Pass supply wires through grommet into the base section, taking care to ensure
they are not trapped between the fitting and mounting surface.
Fix base to the wall, ceiling or besa box using adequate fixings with regard
to the type of surface.
Ensure incoming cables are protected, re-attach the support strap.
Terminate wiring as per Fig. 2, please note an Earth terminal is only supplied
to aid the continuation of the Earth circuit.
Select LED colour and wattage required using the switches on the LED driver
Note: Never change the LED colour or wattage with the luminaire powered
on as this can damage the luminaire. Fig. 3.
Set Microwave to desired settings, for set up please refer to page overleaf.
Remove the battery cover and connect the emergency battery, replace battery
cover (see overleaf).
Install rim, diffuser and gear tray by lining up lugs and twisting clockwise
to lock in place.
Turn on the mains supply and test luminaire.
This fitting requires a 24 Hour initial charge period prior to any emergency
testing, please see overleaf for testing routine, write on the battery label
in permanent ink the date of commissioning.
All results must be recorded and left with the end user.
The battery has a design life of at least 4 years but should be replaced if
the duration of operation is less than 3 hours after a 24hr charge time with
no interrupted supply.
*Please note: Depending on the amount of fittings on a circuit you may have to upgrade the breaker to a ‘C’ or ‘D’ type to avoid nuisance tripping.
Roma Select LED Surface Luminaire
Lamp Details
Lamp: LED
Wattage: 10W, 14W, 20W
Colour: 3000K, 4000K and 6000K CCT
CRI: Ra>84
CCT | Lumen output |
---|---|
3000K | 4000K |
10W | 1067lm |
14W | 1341lm |
20W | 1719lm |
This product contains a light source of energy efficiency class F
KSR Lighting Aftersales: 023 92 674343
E-mail: aftersales@ksrlighting.com
Read these instructions before commencing installation. Please give these
instructions to the owner/occupier after installation to retain for future
reference/maintainence.
This Microwave sensor is a motion activated switch, it will turn the light on
when movement is detected, then hold the light on for the determined amount of
time, after which the light will turn off.
Using the Dip Switches on the sensor, set it up to your preferred Detection
area, Hold Time & Daylight level.
Microwave sensors will detect movement through certain materials, if this
occurs reduce the detection area until any nuisance triggering stops.
Max Load – 400W (Inductive)(LEDs)
Max Load – 800W (Resistive)
The Sensor is designed for installation heights of 3-6m
Recommended Installation heights
For Wall mounting the height is 1.5m
For Ceiling mounting the height is 3m
1 – Detection Area
Detection area can be reduced by selecting the combination on the Dip
Switches, following the guide as shown here.|
---|---
2 – Hold Time
Hold time means the time period you would like the light to remiain ‘on’ once
no movement is detected.
2 – Hold Time
Hold time means the time period you would like the light to remiain ‘on’ once
no movement is detected.
Roma Select KSR Microwave On/Off Sensor Set Up Guide
Issue | Cause | Solution |
---|---|---|
The load will not illuminate | Incorrect daylight threshold setting selected |
Adjust setting and retest
Load has failed (driver or LED array)| Replace load
No mains power detected| Switch on power
The load is permanently illuminated| Continuous movement in the detection
area| Check detection area setting
The lamp (containing sensor) is installed in an area too close to reflective
surface, i.e Metal, Glass or Concrete walls.| 1. Make sure installation area
suitable with at least 30cm space between lamp and surrounding reflective
surfaces
2. Reduce Sensitivity (detection area)
The load will not illuminate despite movement| Speed of moving object is not
in the range of 0.5-3m/s or the detection radius is too small| Check Detection
area setting
Emergency Range Routine Inspection/Test
All tests must be undertaken at times of least risk and in accordance with EN
50172:2004 as indicated below:
Daily:
LED charge indicators shall be visually inspected for correct operation.
Monthly:
(in addition to the daily check) If automatic testing devices are used, the
results of the short duration tests shall be recorded.
Test shall be carried out as follows:
- Switch the luminaire over to emergency mode to operate from the batteries by simulating a failure of supply to the emergency circuit for a period sufficient to ensure correct luminaire operation.
Note: The period of simulation failure should be sufficient for the
purpose of this clause whilst minimising damage to the system components e.g
lamps. During this period, all luminaires shall be checked to ensure that they
are present, clean and functioning correctly. At the end of this test period,
the unswitched supply should be restored and any indicator lamp or device
should be checked to ensure that is showing that the supply has been restored.
Annually:
If automatic testing devices are used, the results of the short duration tests
shall be recorded. For all other systems the monthly inspection shall be
carried out and the following additional tests made:
- Each luminaire shall be tested monthly as above but for its full duration in accordance with the manufacturer’s information.
- The unswitched supply for the luminaire should be restored and any charge indicator lamp or device should be checked to ensure that it shows the unswitched supply has been restored. The charging arrangements should be checked for proper functioning.
- The date of the test and its results shall be recorded in the system logbook.
A copy of this report must accompany any emergency luminaire returned to KSR Lighting for any reason.
Battery Maintenance (Removal and Replacement Procedure)
For battery servicing please refer to Fig 1. showing how to access the battery
compartment, please ensure when changing the battery that the circuit is
isolated and that the battery replacement is compatible with the product
description.
To access the battery compartment simply remove the locking screw with a
screwdriver and proceed to remove cover by releasing the holding tab located
to the the left side of the compartment.
When cover is removed disconnect old battery and recycle in accordance with
WEEE under directive 2014/30/EU, this should be disposed of in accordance with
local legislation.
Proceed to connect the new battery by clicking connectors back together and
replace battery back into battery housing With battery in place replace cover
onto compartment and fasten in place with locking screw removed earlier Turn
on the mains supply and test luminaire
Any deviation from the battery specification may result in damage to the
emergency circuit or failure to perform under emergency conditions.
Roma Select Emergency Bulkhead
Emergency Lighting Periodic Test Schedule
All emergency lighting should be installed and tested in accordance to
EN5266-1:2011. This test schedule should remain onsite and be accessible to
the relevant authorities on request.
Em No.| Luminaire Location| Luminaire Type| Start Time|
Duration (Mins)| *Pass/Fail| Comments/Actions
---|---|---|---|---|---|---
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
x √=Pass, X=Fail, N/T=Not Tested, N/A=No Access, U/T=Uncomplete Test
Site Address: ————
Test Conducted By: ———-
Date of Test Completion: ——-
Comments/Actions: ———-
KSR Lighting Ltd, Unit E Hazleton Interchange,
Lakesmere Road, Horndean,
Hampshire, PO8 9JU
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>