vaillant VRC 700-6 Weather Compensated System Control Instruction Manual
- June 10, 2024
- Vaillant
Table of Contents
- Product Information
- Product Design
- Main Function
- Product Usage Instructions
- Installation
- Operation
- Care and Maintenance
- Troubleshooting
- Decommissioning
- Safety
- General safety information
- Product Description
- Operation
- Care
- Decommissioning
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
vaillant VRC 700-6 Weather Compensated System Control
Weather-compensated system control VRC 700/6
Product Information
The VRC 700/6 is a weather-compensated system control designed to regulate the temperature in a heating system. It consists of amain unit and an external temperature sensor that measures the outdoor temperature.
Product Design
The VRC 700/6 has a compact and modern design with a clear and easy-to-use display. It has several operating modes and advanced functions to provide precise temperature control and energy efficiency.
Main Function
The main function of the VRC 700/6 is to regulate the temperature in a heating system based on the outdoor temperature. It adjusts the heating output based on the current weather conditions to maintain a comfortable indoor temperature while saving energy.
Product Usage Instructions
Before using the VRC 700/6, please read the user manual carefully and follow the safety instructions provided. The product is intended for indoor use only and should be installed by a qualified technician.
Installation
- Mount the main unit in a suitable location near the heating system.
- Install the external temperature sensor in a shaded area outside the building.
- Connect the main unit and external sensor using the provided cable.
- Follow the wiring diagram provided in the user manual to connect the VRC 700/6 to the heating system.
Operation
- Press the ON/OFF button on the VRC 700/6 to turn it on.
- Use the arrow buttons to navigate through the menu and select the desired operating mode.
- The VRC 700/6 will adjust the heating output based on the out door temperature and maintain a comfortable indoor temperature.
Care and Maintenance
- Clean the VRC 700/6 with a soft, dry cloth as needed.
- Do not use water or cleaning agents on the product.
- Check the external temperature sensor regularly and clean it if necessary.
Troubleshooting
If the VRC 700/6 fails to operate properly, refer to the troubleshooting section in the user manual. If the issue persists, contact customer service for assistance.
Decommissioning
If the VRC 700/6 is no longer needed, it should be decommissioned and disposed of according to local regulations. Contact a qualified technician for assistance.
For more information on the VRC 700/6, refer to the user manual provided.
Weather-compensated system control
VRC 700/6
en Operating instructions
0020262548_01 – 28.11.2022
Operating instructions
Contents
Index ……………………………………………………………………….. 23
1
Safety ………………………………………………………….. 3
1.1 Action-related warnings ………………………………….. 3
1.2 Intended use …………………………………………………. 3
1.3 General safety information ……………………………… 3
2
Notes on the documentation ………………………… 4
2.1 Observing other applicable documents …………….. 4
2.2 Storing documents…………………………………………. 4
2.3 Validity of the instructions ……………………………….. 4
2.4 Nomenclature ……………………………………………….. 4
2.5 Function availability ……………………………………….. 4
3
Product description……………………………………… 4
3.1 Product design………………………………………………. 4
3.2 Main function ………………………………………………… 4
3.3 Zones…………………………………………………………… 4
3.4 Hybrid manager …………………………………………….. 5
3.5 Frost protection function …………………………………. 5
3.6 Preventing malfunctions …………………………………. 5
3.7 Data plate …………………………………………………….. 5
3.8 Serial number ……………………………………………….. 5
3.9 CE marking …………………………………………………… 5
4
Operation…………………………………………………….. 5
4.1 Operating structure ………………………………………… 5
4.2 Basic display…………………………………………………. 6
4.3 Operating concept …………………………………………. 6
5
Operating and display functions…………………… 8
5.1 Information……………………………………………………. 8
5.2 Settings………………………………………………………. 10
5.3 Operating modes …………………………………………. 14
5.4 Advanced functions ……………………………………… 15
5.5 Messages …………………………………………………… 16
6
Troubleshooting ………………………………………… 16
6.1 Implementing the setting if the heat pump fails ……………………………………………………………. 17
7
Care…………………………………………………………… 17
7.1 Caring for the product …………………………………… 17
8
Decommissioning………………………………………. 17
8.1 Decommissioning the product ……………………….. 17
8.2 Recycling and disposal …………………………………. 17
9
Guarantee and customer service………………… 17
9.1 Guarantee…………………………………………………… 17
9.2 Customer service…………………………………………. 17
10
Technical data……………………………………………. 17
10.1 Product data in accordance with EU Ordinance no. 811/2013, 812/2013 ………………… 17
Appendix …………………………………………………………………. 18
A
Overview of the operating and display
functions……………………………………………………. 18
A.1 Operating modes …………………………………………. 18
A.2 End user level ……………………………………………… 18
B
Troubleshooting ………………………………………… 22
C
Maintenance messages ……………………………… 22
2
Operating instructions 0020262548_01
Safety
Action-related warnings
Classification of action-related warnings The action-related warnings are
classified in accordance with the severity of the possible danger using the
following warning signs and signal words:
Warning symbols and signal words Danger! Imminent danger to life or risk of
severe personal injury
Danger! Risk of death from electric shock
Warning. Risk of minor personal injury
Caution. Risk of material or environmental damage
1.2 Intended use
In the event of inappropriate or improper use, damage to the product and other
property may arise.
The product is intended for using an eBUS interface to control a heating
installation with heat generators from the same manufacturer.
Intended use includes the following:
observance of the operating instructions included for the product and any
other installation components
compliance with all inspection and maintenance conditions listed in the
instructions.
This product can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the product in a safe way and understand the hazards involved. Children
must not play with the product. Cleaning and user maintenance work must not be
carried out by children unless they are supervised.
Any other use that is not specified in these instructions, or use beyond that
specified in this document, shall be considered improper
use. Any direct commercial or industrial use is also deemed to be improper.
Caution.
Improper use of any kind is prohibited.
General safety information
Risk of material damage caused by frost
Ensure that the heating installation always remains in operation during
freezing conditions and that all rooms are sufficiently heated.
If you cannot ensure the operation, have a competent person drain the heating
installation.
1.3.2 Danger caused by improper operation
Improper operation may present a danger to you and others, and cause material
damage.
Carefully read the enclosed instructions and all other applicable documents,
particularly the “Safety” section and the warnings.
Only carry out the activities for which instructions are provided in these
operating instructions.
0020262548_01 Operating instructions
3
2 Notes on the documentation
2.1 Observing other applicable documents
Always observe all operating instructions enclosed with
the installation components.
2.2 Storing documents
Store these instructions and all other applicable docu-
ments for further use.
2.3 Validity of the instructions
These instructions apply only to:
VRC 700/6 article number
Great Britain
0020184838
2.4 Nomenclature
The following terms are used for simplification:
System control: This refers to the VRC 700 system control.
Remote control: If this refers to the VR 91 remote control.
2.5 Function availability
The functions described in these operating instructions are not available for
all system configurations. The system control only shows the functions that
are available in the system configuration you have installed.
Product Description
Product design
1
3.2 Main function
The system control is a weather-compensated system control with an outdoor
temperature sensor installed in the open air.
The system control is connected to the outdoor temperature sensor and the heat
generator. The system control controls the heating installation and other
connected components, e.g. the domestic hot water generation for a connected
domestic hot water cylinder or the ventilation of a connected ventilation
unit.
3.2.1 Heating
The outdoor temperature sensor measures the outdoor temperature and forwards
the values to the system control. When the outdoor temperature is low, the
system control increases the flow temperature of the heating installation. If
the outdoor temperature increases, the system control reduces the flow
temperature. The system control responds to the fluctuations in the outdoor
temperature and uses the flow temperature to ensure that the room temperature
remains at the desired temperature.
3.2.2 Cooling
The room temperature sensor measures the room temperature and sends the data
to the system control. If the room temperature is higher than the desired
temperature that is set, the system control switches cooling on.
3.2.3 Ventilation
Using a controlled exchange of air, the ventilation unit ensures that the
living rooms are ventilated and aerated. The system control controls the air
volume flow via the ventilation levels that are set.
3.2.4 Domestic hot water generation
A temperature sensor measures the temperature of the water in the domestic hot
water cylinder and forwards the values to the system control. If the
temperature lies below the set value, the system control increases the
temperature in the domestic hot water circuit and therefore heats up the water
to the set domestic hot water temperature.
5 6 5
1 Display 2 Wall base 3 Diagnostics socket
3.2.5 Circulation
The secondary return pipe is connected to the domestic hot water pipe and forms a circuit with the domestic hot water 2 cylinder. The circulation pump pumps the domestic hot water through the domestic hot water pipe, either continuously or on a time-controlled basis. This means that domestic hot water is available at the draw-off points.
3 3.3 Zones
4
4 Wall base cover 5 Selection button 6 Rotary knob
A building is divided into several zones if the heat demand differs between
different sections of the building.
If underfloor heating and radiator heating are installed in a house.
If a house contains more than one independent residential unit.
If more than one zone is available, the system control controls the available
zones.
4
Operating instructions 0020262548_01
3.4 Hybrid manager
If a heat pump and an additional boiler are connected, you can use the hybrid
manager. If there is a heat demand, the hybrid manager picks the heat
generator that is more costefficient. The hybrid manager decides which heat
generator to operate based on the tariffs that are set in relation to the heat
demand.
To ensure that the heat pump and the boiler can work effectively and in synch
with one another, the tariffs ( Page 13) must be set correctly. If the tariffs
are set incorrectly, this results in increased costs.
3.5 Frost protection function
The frost protection function protects the heating installation and flat from
frost damage. The frost protection function monitors the outdoor temperature.
If the outdoor temperature
falls below 4 °C, the system control switches the heat generator on after a
frost protection delay time, and brings the target room temperature to 5 °C.
rises above 5 °C, the system control does not switch the heat generator on
but monitors the outdoor temperature.
Operation
4.1 Operating structure
4.1.1 Adjustment and display levels
The product has two adjustment and display levels. The end user level contains
information and setting options that you require as the end user. End user
level ( Page 18) The installer level is reserved for the competent person. It
is protected by a code. Only competent persons may change any settings in the
installer level.
4.1.2 Menu structure design
The menu structure consists of several selection levels and a setting level.
You can always use the selection button Menu to access selection level 1 from
the basic display. You can use the selection button Op. mode to directly
access the setting level Operating mode. The lowest level is always the
setting level.
Note The competent person can set the frost protection delay time.
3.6 Preventing malfunctions
Ensure that room air can circulate freely around the sys-
tem control, and that the system control is not covered by furniture, curtains
or other objects.
Ensure that all thermostatic radiator valves in the room
where the system control is fitted are fully open.
3.7 Data plate The data plate is located inside the product and is not
accessible from the outside.
3.8 Serial number You can call up the serial number to the display under Menu
Information Serial number. The 10-digit article number is located in the
second line.
3.9 CE marking
4.1.3 Selection level
4 Menu
Information
1
3 Desired temperatures
Time programmes
2
Back
Select
2
1 Scroll bar
2 Current function of the selection button
3 List entries on the selection level
4 Current selection level
The scroll bar (1) only appears if there are more list entries than can be shown at once on the display.
4.1.4 Setting level
4 ZONE1 Day temp. heating
3 Day temp. cooling Set-back temp. heat.
2
Back
20,0°C 26,0°C 1
15,0°C
Change
2
The CE marking shows that the products comply with the basic requirements of
the applicable directives as stated on the declaration of conformity.
The declaration of conformity can be viewed at the manufacturer’s site.
1 Set values
2 Current function of the selection button
3 Functions on the setting level
4 Current selection level
You can read or change the set values in the setting level.
4.1.5 Soft key function for the selection buttons
Both selection buttons have a soft key function, i.e. different functions may
be assigned to the selection buttons. If, for example, you press the left-hand
selection button, the current function switches from Menu to Back.
0020262548_01 Operating instructions
5
4.2 Basic display
8
12
Auto
7
5,0°C
19,5 °C
15:34 3
4
6
Desired heating temp. 20,0°C
5
Menu
Op. mode
5
4.2.3.2 Basic display for the Cooling operating mode
Mode Auto
Day off
Time periods On
Off
Symbol
Information field
Desired cooling temp. Empty line Desired cooling temp. Empty line
1 Symbol for outdoor temperature
2 Outdoor temperature
3 Time
4 Room temperature (for wall-mounting only)
5 Current function of the selection button
6 Information field
7 Symbol for Auto operating mode
8 Mode for the current operating mode
The basic display appears:
If you press the selection button several times. If the system control is
in a selection level or setting level
and you do not operate the system control for more than 5 minutes.
4.2.3.3 Basic display for the Ventilation operating mode
Mode Auto
Day Set-back
Time periods On
Off
Symbol
Information field
Max. vent. stage Max. vent. stage Ventilation stage Ventilation stage
4.2.3.4 Basic display for the Manual cooling advanced function
4.2.1 Preferred zone in the basic display
If your heating installation has several zones, the competent person sets the
zone whose values are to appear in the basic display.
4.2.2 Preferred operating mode in the basic display
If your heating installation is designed for two of the three operating modes
(heating, cooling or ventilating), you can switch the basic display to the
required operating mode.
Setting the preferred display ( Page 13)
4.2.3 Information in the basic display
The basic display shows the most important current settings and values for the
heating installation.
Various information may appear in the basic display. This depends on which
operating mode you give preference to in the basic display and the mode that
this operating mode is in.
4.2.3.1 Basic display for the Heating operating mode
Mode Auto
Time periods
On
Off Day Set-back off
Symbol
Information field
Desired heating temp. appears: The system control
maintains the temperature at the desired level.
Empty line appears: The system control
does not request any heating energy.
Empty line
Mode Activated
Time periods On Off
Information field Desired cooling temp. Empty line
4.3 Operating concept
The system control is operated using two selection buttons and a rotary knob.
You can use the selection buttons to do the following:
Navigate through the selection levels and the setting level in the menu
structure.
Select a set value. Confirm a set value. Navigate to the operating
modes. Cancel changing a set value.
You can use the rotary knob to do the following:
Navigate through the list entries for a selection level. Select a
selection level or setting level. Change a selected set value.
The display shows an element that is highlighted by white writing on a black
background. A flashing, highlighted value means that you can change the value.
If you do not operate the system control for more than 10 seconds, the
background lighting switches off.
If you do not operate the system control during a period of more than 5
minutes, the basic display appears again.
4.3.1 Using the rotary knob to make settings in the basic display
If the display shows the basic display, you can use the rotary knob to change
the setting for the desired temperature or ventilation level.
The setting that you change depends on selecting the preferred display in the
basic display, the selected operating mode and the set mode for the operating
mode.
6
Operating instructions 0020262548_01
4.3.1.1 Desired temperature in the Heating operating mode
4.3.1.4 Desired temperature in the Manual cooling advanced function
Change desired day temperature 18°C
For 6 hrs: wait 12 s Permanent: Press OK
OK
Mode Auto
Time periods
On
Off Day
Set-back off
Effect
Switch to another display view with the request:
Permanent change to the Day temp. heating
Change to the Day temp. heating for six hours
Direct change to the Set-back temp. heat. for six hours
Switch to another display view with the request:
Permanent change to the Day temp. heating
Change to the Day temp. heating for six hours
Direct change to the Set-back temp. heat. for six hours
None
4.3.1.2 Desired temperature in the Cooling operating mode
Mode Activated
Time periods
On
Off
Effect
Direct permanent change to the Day temp. cooling None
4.3.1.5 Using the rotary knob to make settings with no effect
You cannot influence the following advanced functions by turning the rotary
knob:
System OFF active Cylinder boost Party function 1 day at home Days
at home scheduling 1 day away from home Days away from home scheduling
Ventilation boost Screed-drying function
4.3.2 Example, changing the display contrast
Auto
5.0 °C
15:34
19.5 °C
Desired heating temp. 20.0 °C
Menu
Operating mode
Mode Auto
Day off
Time periods On
Off
Effect
Direct permanent change to the Day temp. cooling None Direct permanent change
to the Day temp. cooling None
4.3.1.3 Ventilation level in the Ventilation operating mode
1. Press the left-hand selection button Back until the basic display appears
in the display.
2. Press the left-hand selection button Menu.
The system control switches to selection level 1.
Menu
Information Desired temperatures Timer programmes
Mode Auto
Time periods
On
Off
Day
Set-back
Effect
Direct permanent change to the Max. vent. stage: Day Direct permanent change
to the Max. vent. stge: Night Direct permanent change to the Max. vent. stage:
Day Direct permanent change to the Max. vent. stge: Night
Back
Select
3. Turn the rotary knob until the list entry Basic settings is highlighted.
Menu
Planning days away from home Days at home scheduling Basic settings
Back
Select
4. Press the right-hand selection button Select.
The system control switches to selection level 2.
0020262548_01 Operating instructions
7
Basic settings
Language Date/time Display
Back
Select
5. Turn the rotary knob until the list entry Display is highlighted.
Basic settings
Language Date/time Display
Back
Select
6. Press the right-hand selection button Select.
The system control switches to setting level
Display. The adjustable value for the Display contrast is highlighted.
Display
Display contrast
9
Button lock
Back
Change
7. Press the right-hand selection button Change.
The highlighted value flashes.
Display
Display contrast
9
Button lock
Cancel
OK
8. Turn the rotary knob to change the value.
Display
Display contrast
12
Button lock
Cancel
OK
9. Press the right-hand selection button OK to confirm the change.
The system control has saved the changed value.
10. Press the left-hand selection button Back repeatedly to go back to the
basic display.
5 Operating and display functions
Note The functions described in this section are not available for all system
configurations.
Overview of operating modes and the end user level Operating modes ( Page 18)
End user level ( Page 18)
The path details given at the start of each function description indicate how
you reach this function in the menu structure.
The description of the functions for ZONE1 also applies for all available
zones.
5.1 Information
5.1.1 Reading the system status
Menu Information System status
Under System status, there is a list containing information that provides an
overview of the current system status, and current settings that you can
change there.
5.1.1.1 System
Menu Information System status Fault status
If no maintenance is required and no faults have occurred, the value No
fault appears for Fault status. If maintenance is required or a fault has
occurred, the value Fault list is shown for Fault status. In this case, the
right-hand selection button is for the Display function. If you press the
right-hand selection button Display, the list of fault messages appears on the
display.
Menu Information System status Green IQ
You can use the function if the connected heat generator Green IQ is capable
of this.
On: The operating mode controls the heat generator in the heating and cylinder
charging mode so that a maximum gross calorific value utilisation is achieved.
Off: The operating mode is switched off.
Menu Information System status Water pressure
You can use this function to read the water pressure of the heating
installation.
Menu Information System status System status
You can use this function to read the heating installation’s operating mode.
Standby: The heating installation has no heat demand and is in standby.
Heat. mode: The heating installation heats the living rooms to the Desired
heating temp..
Cooling: The heating installation cools the living rooms to the Desired
cooling temp..
DHW: The heating installation heats the domestic hot water in the cylinder
to the desired temperature Domestic hot water.
Menu Information System status Collector temp.
You can use this function to read the current temperature on the collector
temperature sensor.
8
Operating instructions 0020262548_01
Menu Information System status Solar yield
You can use this function to read the total solar yield.
Note the contents of the section Display for energy consumption and energy
yield ( Page 9).
Menu Information System status Reset solar yield
If you select the Yes setting in the Reset solar yield function and press
the right-hand selection button OK, you reset the previously totalled solar
yield to 0 kWh.
Menu Information System status Environmental yield
You can use this function to read the total environment yield.
Note the contents of the section Display for energy consumption and energy
yield ( Page 9).
Menu Information System status Reset env.yield
If you select the Yes setting in the Reset env.yield function and press the
right-hand selection button OK, you reset the previously totalled
environmental yield to 0 kWh.
Menu Information System status Curr. room air hum.
You can use this function to read the current room air humidity. The room
air humidity sensor is installed in the system control.
Menu Information System status Current dew point
You can use this function to read the current dew point. The dew point
indicates the temperature at which the water vapour in the air condenses and
settles on objects.
Menu Information System status triVAI
You can use this function to read whether the heat pump or the back-up
boiler (gas, oil or electricity) is currently covering the heat demand. The
energy manager uses the triVAI and the comfort criteria to decide which heat
generator to use.
If the value that is read is greater than 1, the heat pump is better at
covering the heat demand than the back-up boiler.
5.1.1.2 ZONE1
Menu Information System status Day temp. heating
You can use this function to set the desired day temperature for the zone.
Day temp. heating is the temperature that you want to have in the rooms during
the day or when you are at home.
Menu Information System status Day temp. cooling
You can use this function to set the desired day temperature for the zone.
Day temp. cooling is the temperature that you want to have in the rooms during
the day or when you are at home.
Menu Information System status Set-back temp. heat.
You can use this function to set the desired set-back temperature for the
zone.
Set-back temp. heat. is the temperature that you want to have in the rooms
during the night or when you are away from home (night mode).
Menu Information System status Room temperature
If the system control is installed outside of the heat generator, you can
read the current room temperature.
The system control has an integrated temperature sensor, which determines the
room temperature.
5.1.1.3 Ventilation
Menu Information System status Air quality sensor 1/2
You can use this function to read the measured values from the air quality
sensor.
Menu Information System status Exhaust air humidity
You can use this function to read the extract air moisture in the
ventilation unit’s ventilation duct.
5.1.2 Display of energy consumption and energy yield
In the display and in the app that can also be used, the control displays
values for the energy consumption and/or the energy yield.
The control displays an estimation of the values for the installation. Among
other things, the values are influenced by the following:
The installation/design of the heating installation User behaviour
Seasonal environmental conditions Tolerances and components
External components, such as external heating pumps or valves, and other
consumers and appliances in the household are still not taken into
consideration.
The deviations between the energy consumption or energy yield that is
displayed and the actual energy consumption or energy yield may be
significant.
The specifications for the energy consumption or energy yield are not suitable
to be used to create or compare energy billing.
5.1.2.1 Consumption
Some components do not support the calculation of consumption, the total of
which is shown on the display. In the instructions for the components, you can
find out if and how the individual components determine the consumption.
Menu Information Consumption Current month Heating Electricity
You can use this function to read the total power consumption for heating in
the current month.
Menu Information Consumption Current month Heating Fuel
You can use this function to read the total fuel consumption in kWh for
heating in the current month.
Menu Information Consumption Current month Hot water Electricity
You can use this function to read the total power consumption for domestic
hot water in the current month.
Menu Information Consumption Current month Hot water Fuel
0020262548_01 Operating instructions
9
You can use this function to read the total fuel consumption in kWh for
domestic hot water in the current month.
Menu Information Consumption Last month Heating Electricity
You can use this function to read the total power consumption for heating in
the last month.
Menu Information Consumption Last month Heating Fuel
You can use this function to read the total fuel consumption in kWh for
heating in the last month.
Menu Information Consumption Last month Hot water Electricity
You can use this function to read the total power consumption for domestic
hot water in the last month.
Menu Information Consumption Last month Hot water Fuel
You can use this function to read the total fuel consumption in kWh for
domestic hot water in the last month.
Menu Information Consumption History Heating Electricity
You can use this function to read the total power consumption for heating
since start-up.
Menu Information Consumption History Heating Fuel
You can use this function to read the total fuel consumption in kWh for
heating since start-up.
Menu Information Consumption History Hot water Electricity
You can use this function to read the total power consumption for domestic
hot water since start-up.
Menu Information Consumption History Hot water Fuel
You can use this function to read the total fuel consumption in kWh for
domestic hot water since start-up.
5.1.2.2 Diagram: Reading the solar yield
Menu Information Solar yield
The diagram under Solar yield shows a comparison of the monthly solar yields
between the previous and the current year.
The total yield is displayed on the bottom right. The highest value achieved
in one month for the last two years is displayed in the top right.
5.1.2.4 Diagram: Reading the electrical consumption
Menu Information Electrical consumption The diagram under Electrical
consumption shows a
comparison between the monthly consumption of electricity for the previous
year and for the current year.
The total yield is displayed on the bottom right. The highest value achieved
in one month for the last two years is displayed in the top right.
5.1.2.5 Diagram: Reading the fuel consumption
Menu Information Fuel consumption The diagram below Fuel consumption shows a
compar-
ison between the monthly fuel consumption for the previous year and for the
current year.
The total yield is displayed on the bottom right. The highest value achieved
in one month for the last two years is displayed in the top right.
5.1.2.6 Diagram: Reading the heat recovery yield
Menu Information Heat recovery The diagram under Heat recovery shows a
comparison
between the monthly heat recovery yield for the previous year and for the
current year.
The total yield is displayed on the bottom right. The highest value achieved
in one month for the last two years is displayed in the top right.
5.1.3 Read competent person contact details
Menu Information Contact details If the competent person entered their
company name and
telephone number when they installed the product, you can read this data under
Contact details.
5.1.4 Reading the serial number and article number
Menu Information Serial number You can use this function to read the
product’s serial
number. The article number is found in the second line.
5.2 Settings
5.2.1 Setting desired temperatures
This function is used to set the desired temperatures for the zone and
domestic hot water generation.
5.1.2.3 Diagram: Reading the environmental yield
Menu Information Environmental yield
The diagram under Environmental yield shows a comparison between the monthly
environmental yields for the previous year and for the current year.
The total yield is displayed on the bottom right. The highest value achieved
in one month for the last two years is displayed in the top right.
5.2.1.1 Zone
Menu Desired temperatures ZONE1
You can set different desired temperatures for the zone:
Heating Day temp. heating: Set a comfortable room temperature
in the living rooms. Set-back temp. heat.: Set a low room temperature at
which the living rooms do not cool down.
Cooling Day temp. cooling: Set a comfortable room temperature
in the living rooms.
10
Operating instructions 0020262548_01
5.2.1.2 Hot water generation
Danger! Risk of death from legionella.
Legionella multiply at temperatures below 60 °C.
Have a competent person inform you
about the measures that should be taken to protect against Legionella in your
installation.
Do not set any water temperatures below
60 °C without consulting the competent person first.
5.2.3.1 Heating operating mode example: Time period for a day
B 21 °C 16 °C
1
1
2
2
3
4
Menu Desired temperatures Domestic hot water
You can set the desired Domestic hot water temperature for the domestic hot
water circuit.
If a heat pump is connected and you have set the desired temperature to above
55 °C, it may be the case that it is the back-up boiler that predominantly
takes on the task of supplying domestic hot water.
5.2.2 Setting the ventilation level
Menu Ventilation stage
You can use this function to set how quickly the used room air is replaced
with fresh outdoor air.
Max. vent. stage: Day: The ventilation guarantees quick exchange of air.
Max. vent. stge: Night: The ventilation guarantees a reduced air change.
5.2.3 Time programme
You can use the time programme to switch the system control between two
implemented settings at specified times. To do this, create the required time
periods in the time programme.
Setting the Heating time programme ( Page 12)
Setting the Cooling time programme ( Page 12)
Setting the domestic hot water circuit time programme ( Page 12)
Setting the Circulation time programme ( Page 12)
Setting the Ventilation time programme ( Page 12)
Setting the High tariff time programme ( Page 12)
You can create up to three time periods for each individual day and for
predefined blocks (Monday – Friday, Saturday Sunday, Monday – Sunday).
When entering time periods for individual days or blocks, the last information
that was entered always applies.
If you have not set any time periods, the system control uses the time periods
set in the factory settings.
A
16:30 18:00 20:00
22:30
A Time B Temperature 1 Day temp. heating
2 Set-back temp. heat. 3 Time period 1 4 Time period 2
You can specify the temperatures (Day temp. heating and Set-back temp. heat.)
in the Setting the Desired temperatures ( Page 10) function.
You can specify the times for the time periods in the Setting time programmes
Heating ( Page 12) function.
Day temp. heating: 21 °C
Set-back temp. heat.: 16 °C
Period 1: 16:3018:00
Period 2: 20:0022:30
Within the time periods, the system control maintains the room temperature at
the set Day temp. heating.
Outside of the time periods, the system control maintains the room temperature
at the set Set-back temp. heat..
5.2.3.2 Setting time programmes quickly
If, for example, you require different time periods for just one working day
in the week, first set the times for the entire block Monday – Friday. Then
set the different time period for the working day.
5.2.3.3 Displaying and changing different times in the block
Monday – Sunday Period 1: Period 2: Period 3:
!! : !! – !! : !! !! : !! – !! : !! !! : !! – !! : !!
Back
Select
Note
Once time programmes are set, they are retained even if there is a loss of
voltage.
If you view a block in the display and have defined a different time period for a day in this block, the display indicates the time periods in the block with !!.
0020262548_01 Operating instructions
11
Individual dates vary from the selected time programme
Mo-Su.
Back
OK
If you press the right-hand selection button Select, a message appears on the
display which informs you about different time periods. You do not need to
adjust the times.
You can use the right-hand selection button OK to display and change the set
times for the block marked with !!.
5.2.3.4 Setting the Heating time programme
Menu Time programmes ZONE1
The time programmes are only effective for the Heating operating mode in
automatic mode. Within the time periods, the system control brings the
temperature of the connected rooms to the set desired temperature Day temp.
heating. Outside of these time periods, the system control switches to the
operating mode that the competent person has set: Eco or Set-back temp. heat..
If the competent person has left the factory setting Eco, the system control
switches off the heating function.
Setting the Heating operating mode. ( Page 14)
5.2.3.5 Setting the Cooling time programme
Menu Time programmes ZONE1: Cooling
The time programmes are only effective in the Cooling mode and the Manual
cooling advanced function. In each set time period, the desired temperature
that you set in the Desired temperatures function applies. Within the time
periods, the zone cools the living areas to the desired Day temp. cooling
temperature. Outside this time period, there is no cooling.
5.2.3.6 Setting the domestic hot water generation time programme
Menu Time programmes DHW circuit
The time programmes are only effective for domestic hot water generation in
automatic mode. In each set time period, the desired Domestic hot water
temperature applies. At the end of a time period, the system control switches
the domestic hot water generation off until the start of the next time period.
5.2.3.7 Setting the time programme Circulation
Menu Time programmes Circulation
The time programmes are only effective for circulation in Automatic mode.
The set time periods determine the operating times for circulation. Within the
time period, the circulation is switched on. Outside the time period, the
circulation is switched off.
5.2.3.8 Setting the Ventilation time programme
Menu Time programmes Ventilation
The time programmes are only effective for ventilation in automatic mode. In
each set time period, the ventilation level that you set in the Ventilation
function applies. Within the time period, the system control regulates the
ventilation unit to Max. vent. stage: Day as a maximum. Outside the time
period, the system control regulates the ventilation unit to Max. vent. stge:
Night as a maximum.
5.2.3.9 Setting the High tariff time programme
Menu Time programmes High tariff
You can use this function to set when the high tariff or the low tariff
should be used to calculate the costs.
Within the time period: For the high tariff
Outside of the time period: For the low tariff
The times of high tariff depend on your energy supply company.
If the energy supply company only offers one tariff, you do not need to set
any time periods. The cost for the electricity is calculated using one tariff.
Setting costs ( Page 13)
5.2.4 Days away from home scheduling
Menu Days away from home scheduling
You can use this function to set a period of time and a temperature for the
days that you are away from home.
Heating installation operation during the set time period The domestic hot
water is not being heated. The previously set temperature applies for all
zones. The ventilation runs at the lowest ventilation level. The cooling
is switched off.
While the Days away from home scheduling function is activated, it has
priority over the set operating mode. At the end of the specified period, or
if you cancel the function, the heating installation returns to the pre-set
mode.
5.2.5 Day at home scheduling
Menu Days at home scheduling
In the specified period, the heating installation works in the Automatic
mode mode and uses the day settings for Sunday, which were set using the Time
programmes function. At the end of the specified period, or if you cancel the
function, the heating installation returns to the preset mode.
5.2.6 Select language
Menu Basic settings Language
You can use this function to change to the language that you want to appear
in the display.
12
Operating instructions 0020262548_01
5.2.6.1 Setting your language
1. Press the left-hand selection button repeatedly until the basic display
appears.
2. Press the left-hand selection button again. 3. Rotate the rotary knob
clockwise until the dotted line
appears. 4. Turn the rotary knob anti-clockwise until the second list
entry above the dotted line is highlighted. 5. Press the right-hand selection
button twice. 6. Turn the rotary knob until you find a language that you
understand. 7. Press the right-hand selection button.
5.2.7 Setting the date and time
Note If you disconnect the entire heating installation from the power supply,
the time continues to run correctly for 30 minutes. You then have to reset the
date and time.
5.2.7.1 Setting the date
Menu Basic settings Date/time Date
Select this function to set the current date. All functions that contain a
date relate to the set date.
5.2.7.2 Setting the time
Menu Basic settings Date/time Time
Select this function to set the current time. All functions that contain a
time relate to the set time.
5.2.8 Activating the automatic or manual changeover to daylight saving time
Menu Basic settings Date/time Daylight saving time
You can use this function to set whether the system control automatically
changes over to daylight saving time, or whether you want to do this manually.
Auto: The system control automatically changes over to daylight saving time.
The system control uses Central European Summer Time: Start = last Sunday in
March, end = last Sunday in October.
Manual: You have to manually change over to daylight saving time.
If the outdoor temperature sensor is equipped with a DCF77 receiver, the time
is changed over automatically. This Daylight saving time function is not used.
5.2.9 Set display contrast
Menu Basic settings Display Display contrast
You can use this function to set the display contrast in relation to the
brightness of the surroundings to ensure that the display is clearly legible.
Each time you actuate the system control, the following message appears in the
display Button lock active To unlock, press OK for 3 seconds. If you press and
hold the OK button for three seconds, the basic display appears and you can
change functions. The button lock becomes active again if you do not press any
button or operate the rotary knob for one minute.
To permanently remove the button lock, you must first release the button lock
and then select the value off in the Button lock function.
5.2.11 Setting the preferred display
Menu Basic settings Display Preferred display
You can use this function to choose whether you see the data for heating,
cooling or ventilation in the basic display.
5.2.12 Setting costs
You must specify all tariffs in the unit of currency per kWh for the
calculation to be correct.
If the tariffs are in the unit of currency per m3 for you, request that your
energy supply company provides the required tariffs in the unit of currency
per kWh.
If your energy supply company only offers one electricity tariff, enter the
same value for the High-tariff elec. rate ( Page 14) and Low-tariff elec. rate
( Page 14) functions.
Round the tariff data up or down to one decimal point. To establish the factor
that is to be set, multiply the value by 10.
Example:
Tariff for aux. heater (Gas, oil, electricity)
Low-tariff elec. rate (heat pump)
High-tariff elec. rate (heat pump)
Costs 11.3 currency units/kWh
14.5 currency units/kWh
18.7 currency units/kWh
Factor to be set 113
145 187
5.2.12.1 Setting the tariff for the back-up boiler
Menu Basic settings Costs Tariff for aux. heater
The hybrid manager can use this function to correctly calculate the costs
for the back-up boiler. To do this, the hybrid manager requires the factor
that is to be set.
In order to enter the correct factor, you must request the tariff from your
energy supply company and calculate the factor in accordance with the example.
5.2.10 Activating Button lock
Menu Basic settings Display Button lock
You can use this function to activate the button lock. After one minute of
not pressing any button or operating the rotary knob, the button lock is
active and you can no longer change any functions unintentionally.
0020262548_01 Operating instructions
13
5.2.12.2 Setting the low-tariff electricity rate
Menu Basic settings Costs Low-tariff elec. rate
The hybrid manager can use this function to correctly calculate the costs
for the back-up boiler. To do this, the hybrid manager requires the factor
that is to be set.
In order to enter the correct factor, you must request the tariff from your
energy supply company and calculate the factor in accordance with the example.
Menu Basic settings Default setting Time programmes
With Time programmes, you reset all the settings you have made in the Time
programmes function to the default setting. All other settings that include
times, such as Date/time, are not affected.
While the system control is resetting the time programme settings to the
default settings, In progress is shown on the display. The basic display is
then shown on the display.
5.2.12.3 Setting the high-tariff electricity rate
Menu Basic settings Costs High-tariff elec. rate The hybrid manager can use
this function to correctly
calculate the costs for the back-up boiler. To do this, the hybrid manager
requires the factor that is to be set.
In order to enter the correct factor, you must request the tariff from your
energy supply company and calculate the factor in accordance with the example.
5.2.13 Set offset room temperature
Caution. Risk of a malfunction.
The Default setting Everything function restores all settings to the default
settings, including those set by the competent person. It may be the case that
it is no longer possible to operate the heating installation after this.
Arrange for the competent person to reset
all settings to factory settings.
Menu Basic settings Offset Room temperature
The system control can display the current room temperature if it is
installed in a living room.
A thermometer is integrated in the system control for measuring the room
temperature. You can use the offset to correct the measured temperature value.
5.2.14 Set offset outdoor temperature
Menu Basic settings Offset Outside temperature
The thermometer in the system control’s outdoor temperature sensor measures
the outdoor temperature. You can use the offset to correct the measured
temperature value.
Menu Basic settings Default setting Everything While the system control is
restoring the factory settings,
Reset to default setting In progress is shown in the display. The installation
assistant is then shown in the display; it must only be operated by a
competent person.
5.2.19 Installer level
The Installer level is reserved for the competent person and is therefore
protected by an access code. At this level, the competent person can implement
the required settings.
5.3 Operating modes
5.2.15 Changing a zone name
Menu Basic settings Enter zone name You can now modify the factory-set zone
names as you
wish. The name is limited to 10 characters.
5.2.16 Activating Heat recovery
Menu Basic settings Ventilation Heat recovery The Heat recovery function is
set to Auto. This means
that an internal control system checks whether heat recovery makes sense, or
whether the outdoor air can be guided directly into the living room. For more
information, see the operating instructions for recoVAIR…/4 and later models.
If you have selected Activate, heat recovery is used constantly.
5.2.17 Setting the room air humidity
Menu Basic settings Max. room air humidity If the room air humidity exceeds
the value set, a connec-
ted dehumidifier is activated. As soon as the value drops below the value that
is set, the dehumidifier switches off again.
5.2.18 Resetting to default setting
You can reset the settings for the Time programmes or for Everything to the
default setting.
The operating modes can be activated directly from any operating mode using
the right-hand selection button Op. mode. If the heating installation is
equipped with more than one zone, the activated operating mode only applies
for the zone that was preset by the competent person.
If more than one zone is activated, you can set a separate operating mode for
each zone using the left-hand selection button Menu Basic settings.
The path details given at the start of each operating mode description
indicate how you reach this operating mode in the menu structure.
5.3.1 Setting the Heating operating mode
Op. mode Heating
Menu Basic settings Operating mode ZONE1 Heating
You can use this function to specify how the heating installation should
operate during heating.
off: The zone is switched off in this operating mode and the frost protection
function is activated.
Auto: The operating mode brings the zone to the desired temperature set for
Day temp. heating in the time periods that you have set in the time programme.
Outside these time periods, the system control regulates the control behaviour
set by the competent person.
Eco The heating function is switched off and the system control monitors the
outdoor temperature. If the outdoor temperature falls below 3 °C, the system
control switches
14
Operating instructions 0020262548_01
the heating function on after the end of the frost protection delay time and
brings the room temperature to the set desired temperature Set-back temp.
heat.. Despite the heating function being activated, the burner is only active
on demand. If the outdoor temperature rises above 4 °C, the system control
switches the heating function off, but continues to monitor the outdoor
temperature. Set-back: The heating function is switched on and the system
control brings the room temperature to the set desired temperature Set-back
temp. heat..
Day: The operating mode brings the zone to the desired temperature Day temp.
heating, regardless of the time periods that you have set in the time
programme.
Set-back: The operating mode brings the zone to the desired temperature Set-
back temp. heat., regardless of the time periods that you have set in the time
programme.
5.3.2 Setting the Cooling operating mode
Op. mode Cooling
Menu Basic settings Operating mode ZONE1 Cooling
You can use this function to specify how the heating installation should
operate during cooling.
off: The zone is switched off in this operating mode.
Auto: The operating mode brings the zone to the desired temperature Day temp.
cooling in the time periods that you have set in the time programme. Outside
these time periods, the Cooling function is switched off.
Day: The operating mode brings the zone to the desired temperature set for Day
temp. cooling, regardless of the time periods that you have set in the time
programme.
5.3.3 Setting the Ventilation operating mode
The operating instructions for the ventilation unit explain how the
ventilation unit works with the ventilation levels.
Op. mode Ventilation
You can use this function to define how the ventilation unit operates during
ventilation.
Auto: The operating mode controls the air exchange via the set ventilation
level Max. vent. stage: Day in the set time periods that you have defined in
the time programme. The set ventilation level Max. vent. stge: Night is
effective outside of the time periods.
If air-quality sensors are connected to the ventilation unit, the ventilation
unit varies the ventilation levels:
If the air quality is good, the ventilation unit works at a lower
ventilation level than the one that is set.
If the air quality is poor, the ventilation unit works at a higher
ventilation level. However, the ventilation unit cannot exceed the Max. vent.
stage: Day and Max. vent. stge: Night ventilation levels that are set.
Day: The operating mode constantly controls the exchange of air using the
value that you set in the Max. vent. stage: Day ventilation level.
Set-back: The operating mode constantly controls the exchange of air using the
value that you set in the Max. vent. stge: Night ventilation level.
5.3.4 Setting the operating mode for domestic hot water generation
Op. mode Domestic hot water
You can use this function to specify how the heating installation should
operate during domestic hot water generation.
off: Domestic hot water generation is switched off and the frost protection
function is activated.
Auto: The operating mode brings the domestic hot water generation to the
desired temperature set for Domestic hot water in the time periods that you
have set in the time programme.
Day: The operating mode brings the domestic hot water generation to the
desired temperature set for Domestic hot water, regardless of the time periods
that you have set in the time programme.
5.3.5 Operating mode for circulation
The operating mode for circulation always corresponds to the operating mode
for hot water. You cannot set a different operating mode.
5.4 Advanced functions
The advanced functions can be activated directly from any operating mode using
the right-hand selection button Op. mode. If the heating installation is
equipped with more than one zone, the activated advanced function only applies
for the zone that was preset by the competent person.
If more than one zone is activated, you can set a separate advanced function
for each zone using the left-hand selection button Menu Basic settings.
The path details given at the start of each advanced function description
indicate how you can access this advanced function in the menu structure.
5.4.1 Activating manual cooling
Op. mode Manual cooling
If the outdoor temperature is high, you can activate the Manual cooling
advanced function. You define for how many days you want to activate the
advanced function. If you activate Manual cooling, you cannot use the heating
function at the same time. The Manual cooling function takes priority over the
heating function.
The setting applies for as long as the advanced function is active. The
advanced function is deactivated if the days that are set have elapsed or if
the outdoor temperature falls below 4 °C.
If you want to set the temperature separately for more than one zone, you can
set these temperatures using the Desired temperatures function.
5.4.2 Activating 1 day at home
Op. mode 1 day at home
Menu Basic settings Operating mode ZONE1 1 day at home
The 1 day at home advanced function activates the automatic mode in the
operating mode Heating with the settings for the Sunday.
The advanced function is automatically deactivated after 00:00 (midnight) or
you can cancel the advanced function
0020262548_01 Operating instructions
15
first. The heating installation then returns to the pre-set operating mode.
5.4.3 Activating 1 day away from home
Op. mode 1 day away from home
Menu Basic settings Operating mode ZONE1 1 day away from home
The 1 day away from home advanced function brings the room temperature to
the desired Set-back temperature.
Domestic hot water generation and circulation are switched off and the frost
protection is activated.
Ventilation is activated and works at the lowest ventilation level.
The advanced function is automatically deactivated after 00:00 (midnight) or
you can cancel the advanced function first. The heating installation then
returns to the pre-set operating mode.
5.4.4 Activating Ventilation boost
Op. mode Ventilation boost
Menu Basic settings Operating mode ZONE1 Ventilation boost
This Ventilation boost advanced function switches the zone off for 30
minutes.
The frost protection function is activated, and domestic hot water generation
and circulation remain active.
Ventilation is activated and works at the highest ventilation level.
The advanced function is automatically deactivated after 30 minutes or you can
cancel the advanced function first. The heating installation will then return
to the pre-set operating mode.
5.4.5 Activating Party function
Op. mode Party function
Menu Basic settings Operating mode ZONE1 Party function
The advanced function regulates the room temperature to the desired Day
temperature, the domestic hot water to the desired Domestic hot water
temperature and the ventilation to ventilation level Max. vent. stage: Day in
accordance with the set time periods. The circulation is activated.
The advanced function is automatically deactivated after six hours or you can
cancel the advanced function first. The heating installation will then return
to the pre-set operating mode.
5.4.7 Activating System OFF active
Op. mode System OFF active
The System OFF active advanced function switches off the heating function,
the domestic hot water circuit, the circulation and the cooling. The frost
protection function is activated.
Ventilation is activated and works at the lowest ventilation level.
The advanced function is deactivated by cancelling the advanced function. The
heating installation will then return to the pre-set mode.
5.5 Messages
5.5.1 Maintenance message
Maintenance messages ( Appendix C)
If maintenance is required, the system control displays a maintenance message
in the display.
To prevent the heating installation from breaking down and to prevent damage,
you must pay attention to the maintenance message:
Observe the operating instructions for the unit shown. Only carry out the
maintenance instructions that are de-
scribed in the operating instructions for the unit shown.
For all other maintenance instructions, inform the com-
petent person.
5.5.2 Fault message
Fault messages ( Appendix B)
A fault message with fault code (e.g. F.33) and the affected heat generator
appear in the system control’s display.
Press the Reset selection button.
Heat generator fault clearance? appears in the display.
Press the OK selection button.
Faults are cleared for the heat generator briefly appears in the display.
If the fault persists, inform the competent person.
If you would like to see the basic display on the display again, press the
left-hand selection button Back.
You can read the current fault messages under Menu Information System status
Fault status. As soon as a fault message occurs for the heating installation,
the setting level displays the value Fault list. The right-hand selection
button has been assigned the Display function.
6 Troubleshooting
5.4.6 Activating Cylinder boost
Op. mode Cylinder boost
The Cylinder boost advanced function heats the water in the domestic hot
water cylinder until it reaches the set desired temperature Domestic hot
water.
The advanced function is active for one hour unless you cancel it sooner. The
heating installation then returns to the preset operating mode.
Troubleshooting faults ( Appendix B)
16
Operating instructions 0020262548_01
6.1 Implementing the setting if the heat pump fails
If the fault message Restricted operation/ comfort protection Inactive appears
on the display, the heat pump has failed and the system control enters limp
home mode. The back-up boiler now supplies the heating installation with
heating energy. During installation, the competent person has restricted the
temperature for limp home mode. You can feel that the domestic hot water and
heating are not becoming very hot.
While you wait for the competent person to come, you can use the rotary knob
to implement the following settings:
Inactive: The system control works in limp home mode; heating and domestic hot
water become moderately hot.
Heating: The back-up boiler takes over the heating mode; the heating becomes
hot, the domestic hot water is cold.
DHW: The back-up boiler takes over the domestic hot water mode; the domestic
hot water becomes hot, the heating is cold.
DHW+heat.: The back-up boiler takes over the heating and domestic hot water
mode; the heating and the domestic hot water become hot.
The back-up boiler is not as efficient as the heat pump, meaning that using
only the back-up boiler to generate heat is expensive.
If you want to implement settings on the system control, click Back and the
basic display appears in the display. After five minutes of no operation, the
fault message appears again in the display.
9 Guarantee and customer service
9.1 Guarantee
We only grant a Vaillant manufacturers warranty if a suitably qualified
engineer has installed the system in accordance with Vaillant instructions.
The system owner will be granted a warranty in accordance with the Vaillant
terms and conditions. All requests for work during the guarantee period must
be made to Vaillant Service Solutions.
9.2 Customer service
For contact details for our customer service department, you can write to the
address that is provided on the back page, or you can visit
www.vaillant.co.uk.
10 Technical data
10.1 Product data in accordance with EU Ordinance no. 811/2013, 812/2013
On units with integrated weather-compensated controls, including a room
thermostat function that can be activated, the seasonal room-heating
efficiency always includes the correction factor for control technology class
VI. The seasonal room-heating efficiency may deviate if this function is
deactivated.
Temperature control class
Contribution to the seasonal room-heating energy efficiency s
VI 4.0 %
Care
7.1 Caring for the product
Clean the casing with a damp cloth and a little solvent-
free soap.
Do not use sprays, scouring agents, detergents, solvents
or cleaning agents that contain chlorine.
Decommissioning
Decommissioning the product If you want to replace or remove the product, you
must decommission the heating installation.
This work should be carried out by a competent person.
8.2 Recycling and disposal
Observe the recycling and disposal information in the
installation instructions.
0020262548_01 Operating instructions
17
Appendix A Overview of the operating and display functions
Note The functions and operating modes listed are not available for all system
configurations.
A.1 Operating modes
Operating mode Operating mode Heating Cooling Ventilation Domestic hot water
Advanced functions Manual cooling 1 day at home 1 day away from home
Ventilation boost Party function Cylinder boost System OFF active
Setting
off, Auto, Day, Set-back off, Auto, Day Auto, Day, Set-back off, Auto, Day
active active active active active active active
Default setting
Auto Auto Auto Auto
A.2 End user level The description of the functions for ZONE1 also applies for all available zones.
Setting level
Information System status System —Fault status Green IQ Water pressure System
status
Burner Collector temp. Solar yield Reset solar yield Environmental yield Reset
env.yield Curr. room air hum. Current dew point triVAI ZONE1 —Day temp.
heating Day temp. cooling Set-back temp. heat. Room temperature Ventilation
—Air quality sensor 1 Air quality sensor 2
Values
Unit
Min.
Max.
Current value
Current value Current value
Current value Current value Current value
Current value
Current value Current value Current value
5
30
15
30
5
30
Current value
Current value Current value
bar
kWh
kWh
%
ppm ppm
Increment, select
No fault, Fault list Off, On Standby, Heat. mode, Cooling, DHW On, off
Yes, No Yes, No
0.5 0.5 0.5
Default setting
On
No No
20 24 15
18
Operating instructions 0020262548_01
Setting level Exhaust air humidity
Values
Min.
Max.
Current value
Unit %rel
Increment, select
Information Consumption Current month
Heating —-
Electricity
Total value for the current month
Fuel
Total value for the current month
Hot water —-
Electricity
Total value for the current month
Fuel
Total value for the current month
kWh kWh
kWh kWh
Information Consumption Last month
Heating —-
Electricity
Total value for the last month
Fuel
Total value for the last month
Hot water —-
Electricity
Total value since startup
Fuel
Total value since startup
kWh kWh
kWh kWh
Information Consumption History
Heating —-
Electricity
Total value since startup
Fuel
Total value since startup
Hot water —-
Electricity
Total value since startup
Fuel
Total value since startup
kWh kWh
kWh kWh
Information Solar yield Bar chart
Previous year to cur- kWh/month rent year comparison
Information Environmental yield
Bar chart
Previous year to current year comparison
kWh/month
Information Electrical consumption
Bar chart
Previous year to current year comparison
kWh/month
Information Fuel consumption Bar chart
Previous year to current year comparison
kWh/month
Information Heat recovery
0020262548_01 Operating instructions
Default setting
19
Setting level Bar chart
Values
Min.
Max.
Previous year to current year comparison
Unit
Increment, select
kWh/month
Default setting
Information Contact details Installer Phone number
Current values
Information Serial number Product number
Permanent value
Desired temperatures ZONE1
Day temp. heating
5
30
0.5
20
Day temp. cooling
15
30
0.5
24
Set-back temp. heat.
5
30
0.5
15
Desired temperatures Domestic hot water
Domestic hot water
35
70
1
60
Ventilation stage
Max. vent. stage: Day
Depending on the
1
ventilation unit
Max. vent. stge: Night
Depending on the
1
ventilation unit
Depending on the ventilation unit
Depending on the ventilation unit
Time programmes ZONE1 (Heating) Time programmes ZONE1: Cooling Time programmes
Circulation Time programmes Ventilation
Individual days and blocks
Period 1: Start End Period 2: Start End Period 3: Start End
00:00
24:00
h:min
Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday and Monday –
Friday, Saturday – Sunday, Monday – Sunday
00:10
Mo – Fr: 06:0022:00
Sa: 07:30-23:30
Su: 07:30-22:00
Time programmes Domestic hot water Individual days and blocks
Period 1: Start End Period 2: Start End Period 3: Start End
00:00
24:00
h:min
Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday and Monday –
Friday, Saturday – Sunday, Monday – Sunday
00:10
Mo to Fr: 05:3022:00
Sa: 07:00-23:30
Su: 07.00-22.00
Time programmes High tariff Individual days and blocks
Period 1: Start End Period 2: Start End Period 3: Start End
00:00
24:00
h:min
Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, Sunday and Monday –
Friday, Saturday – Sunday, Monday – Sunday
00:10
Mo – Su: 11:0013:00
Days away from home scheduling
20
Operating instructions 0020262548_01
Setting level
Start End Temperature
Values Min. 01.01.01 01.01.01 5
Max. 31.12.99 31.12.99 30
Unit
dd.mm.yy dd.mm.yy
Increment, select
Day.Month.Year Day.Month.Year 1
Days at home scheduling Start End
01.01.01 01.01.01
31.12.99 31.12.99
dd.mm.yy dd.mm.yy
Day.Month.Year Day.Month.Year
Basic settings Language
Selectable language
Basic settings Date/time Date Time Daylight saving time
01.01.01 00:00
31.12.99 23:59
dd.mm.yy h:min
Day.Month.Year 00:10 Manual, Auto
Basic settings Display Display contrast Button lock Preferred display
1
15
1 off, On Heating, Cooling, Vent.
Basic settings Costs
Tariff for aux. heater
1
999
1
Low-tariff elec. rate
1
999
1
High-tariff elec. rate
1
999
1
Basic settings Offset Room temperature Outside temperature
-3.0
3.0
0.5
-3.0
3.0
0.5
Basic settings Operating mode ZONE1 Heating Cooling 1 day at home 1 day away from home Ventilation boost Party function
off, Auto, Day, Set-back off, Auto, Day Active, Not active Active, Not active Active, Not active Active, Not active
Basic settings Enter zone name
ZONE1
1
10
Let-
A to Z, 0 to 9, space
ter/number
Basic settings Ventilation Heat recovery
Auto, Activate, off
Basic settings Max. room air humidity
Max. room air hum.
30
70
%rel
1
Basic settings Default setting Time programmes
Yes, No
0020262548_01 Operating instructions
Default setting 01.01.14 01.01.14 15
01.01.14 01.01.14
English
01.01.15 08:00 Manual
9 off Heating
12 16 20
0.0 0.0
Auto Auto Not active Not active Not active Not active
ZONE1
Auto
40
No
21
Setting level Everything
Values
Unit
Min.
Max.
Increment, select Yes, No
Default setting No
Installer level
Enter code
000
999
1
000
B Troubleshooting
Symptom Display remains dark
Possible cause Software error
No changes in the display when Software error the rotary knob is turned
No changes in the display when the selection buttons are pressed
Software error
Display view: Button lock active To unlock, press OK for 3 seconds, it is not possible to change the settings or values
Button lock is active
Display view: Restricted operation/ comfort protection, insufficient heating
up of the heating
and the domestic hot water
Heat pump does not work
Display view: Fault F. Fault: Heat generator 1, the specific fault code (e.g. F.33) and the specific heat generator appear behind F. in the display
Heat generator faults
Measure
1. Switch off the mains switch on all heat generators for approx. 1 minute
and then switch them on again.
2. If the fault persists, inform the competent person.
1. Switch off the mains switch on all heat generators for approx. 1 minute
and then switch them on again.
2. If the fault persists, inform the competent person.
1. Switch off the mains switch on all heat generators for approx. 1 minute
and then switch them on again.
2. If the fault persists, inform the competent person.
1. If you would like to change any of the values, follow the instructions on
the display.
2. Also read through the Button lock Activate ( Page 13) function.
1. Inform the competent person. 2. Select the setting for limp home mode
until the competent
person arrives. 3. To do this, read through the Implementing the setting when
the heat pump fails ( Page 17) function.
1. Carry out a Reset fault message ( Page 16). 2. If the fault persists,
inform the competent person.
C Maintenance messages
The maintenance message Service heat pump 1 is an example of a maintenance
message that may appear for heat pumps 1 to 7.
The maintenance message Service heat generator 1 is an example of a
maintenance message that may appear for heat generators 1 to 7.
Code/meaning
Description
Maintenance work
Interval
1
Service heat
pump 1
The heat pump requires maintenance work.
Refer to the operating instructions of the relevant heat pump for information on the maintenance work required
See the operating instructions for the heat pump
2
Service heat
generator 1
The heat generator requires maintenance work.
Refer to the operating instructions of the relevant heat generator for information on the maintenance work required
See the operating instructions for the heat generator
3
Service ventila- The ventilation unit requires
tion unit
maintenance work.
Refer to the operating instructions of the ventilation unit for information on the maintenance work required
See the operating instructions for the ventilation unit
4
Low water pres- The water pressure is too low in Refer to the operating instruc- See the operating instructions
sure
the heating installation.
tions for the relevant heat gen- for the heat generator
erator for information on filling
with water
5
Service date
The competent person has
Inform the competent person if Date entered in the control
Next service on entered a date on which main- maintenance work is required
tenance is due for the heating
installation.
22
Operating instructions 0020262548_01
Index
1 1 day at home ………………………………………………………….. 15 1 day away from
home……………………………………………… 16 A Activating Button lock ………………………………………………. 13
Activating Heat recovery ……………………………………………. 14 Advanced functions
………………………………………………….. 15
1 day at home……………………………………………………… 15 1 day away from home ………………………………………… 16
Cylinder boost…………………………………………………….. 16 Manual cooling……………………………………………………… 15
Party …………………………………………………………………… 16 System off……………………………………………………………. 16
Ventilation boost…………………………………………………. 16 Article number
…………………………………………………………….. 5 B Basic display ………………………………………………………………. 6 C CE
marking…………………………………………………………………. 5 Changing the display contrast, example
…………………………. 7 Circulation ………………………………………………………………….. 4 Circulation time
programme ………………………………………… 12 Competent person, contact details………………………………..
10 Contact details…………………………………………………………. 10 Contact details, competent
person……………………………….. 10 Cooling ………………………………………………………………………. 4 Cylinder boost
…………………………………………………………. 16 D Days at home scheduling ……………………………………………. 12
Days away from home scheduling ……………………………….. 12 Desired temperature Hot water
generation …………………………………………….. 11 Setting…………………………………………………………………. 10
Zone……………………………………………………………………. 10 Display level ……………………………………………………………….. 5
Display, solar statistics ……………………………………………….. 10 Documents
…………………………………………………………………. 4 Domestic hot water generation………………………………………. 4 E
Electrical consumption…………………………………………….. 10 Energy
consumption…………………………………………………….. 9 Energy yield………………………………………………………………… 9
Enter zone name ……………………………………………………….. 14 Environmental yield
…………………………………………………. 10 Example, changing the display contrast………………………….. 7 F
Fault message…………………………………………………………… 16 Frost ………………………………………………………………………….. 3
Frost protection function……………………………………………….. 5 Fuel consumption
………………………………………………………. 10 H Heat recovery yield…………………………………………………….. 10
Heating ………………………………………………………………………. 4 Hot water generation
………………………………………………….. 11 Hybrid manager…………………………………………………………… 5 Hybrid
manager heating installation ……………………………….. 5 I Information in the basic
display ……………………………………… 6 Installer level …………………………………………………………….. 14
Intended use……………………………………………………………….. 3 L Language selection
……………………………………………………. 12
M Main function ………………………………………………………………. 4 Maintenance message ……………………………………………….. 16 Manual cooling ………………………………………………………….. 15 N Nomenclature ……………………………………………………………… 4 O Operating concept ……………………………………………………….. 6 Operating level ……………………………………………………………. 5 Operating mode…………………………………………………………. 14 Operating mode in the basic display ………………………………. 6 Outdoor temperature, setting the offset…………………………. 14 P Party ………………………………………………………………………… 16 Preventing a malfunction………………………………………………. 5 R Reading the article number ……………………………………… 5, 10 Reading the electrical consumption ……………………………… 10 Reading the environment yield…………………………………….. 10 Reading the fuel consumption……………………………………… 10 Reading the heat recovery yield…………………………………… 10 Reading the serial number ………………………………………. 5, 10 Reading the solar statistics …………………………………………. 10 Reading the system status ……………………………………………. 8 Recycling and disposal……………………………………………….. 17 Restoring the language ………………………………………………. 13 Room temperature, setting the offset ……………………………. 14 S Selection level …………………………………………………………….. 5 Serial number ……………………………………………………………… 5 Setting costs……………………………………………………………… 13 Setting daylight saving time…………………………………………. 13 Setting level………………………………………………………………… 5 Setting the air humidity……………………………………………….. 14 Setting the Cooling operating mode…………………………….. 15 Setting the Cooling time programme……………………………. 12 Setting the date …………………………………………………………. 13 Setting the date, time …………………………………………………. 13 Setting the display ……………………………………………………… 13 Setting the display contrast …………………………………………. 13 Setting the domestic hot water generation time programme ……………………………………………………………………. 12 Setting the Heating operating mode …………………………….. 14 Setting the Heating time programme……………………………. 12 Setting the High tariff time programme ………………………… 12 Setting the high-tariff electricity rate ……………………………… 14 Setting the low-tariff electricity rate ………………………………. 14 Setting the offset outdoor temperature………………………….. 14 Setting the offset room temperature……………………………… 14 Setting the operating mode for domestic hot water generation ………………………………………………………………… 15 Setting the preferred display ……………………………………….. 13 Setting the room air humidity……………………………………….. 14 Setting the standard time ……………………………………………. 13 Setting the tariff for the back-up boiler ………………………….. 13 Setting the time …………………………………………………………. 13 Setting the ventilation level………………………………………….. 11 Setting the Ventilation operating mode………………………… 15 Setting the Ventilation time programme……………………….. 12 Soft key function………………………………………………………….. 5 System OFF ……………………………………………………………… 16 System status……………………………………………………………… 8 T Time period, deviating times in the block ………………………. 11
0020262548_01 Operating instructions
23
Time programme ……………………………………………………… 11 quick setting………………………………………………………….
11 Setting…………………………………………………………………. 11
V Ventilation…………………………………………………………………… 4 Ventilation boost
……………………………………………………… 16 Ventilation level …………………………………………………………. 11 Z Zone
…………………………………………………………………….. 4, 10 Zone in the basic
display………………………………………………. 6
24
Operating instructions 0020262548_01
Supplier Vaillant Ltd. Nottingham Road Belper Derbyshire Telephone 03301003143 info@vaillant.co.uk www.vaillant.co.uk
DE56 1JT
0020262548_01
Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel.
+49 2191180 Fax +49 2191182810 info@vaillant.de www.vaillant.de
© These instructions, or parts thereof, are protected by copyright and may be
reproduced or distributed only with the manufacturer’s written consent.
Subject to technical modifications.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>