Vaillant VWS 36/4.1 230V geoTHERM Brine/Water Heat Pump Instruction Manual
- June 9, 2024
- Vaillant
Table of Contents
- Vaillant VWS 36/4.1 230V geoTHERM Brine/Water Heat Pump
- Product Description
- Set-up
- Hydraulics Installation
- Electrical Installation
- Maintenance Instructions
- Safety
- Notes on the Documentation
- Safety
- Notes on the documentation
- Product description
- Set-up
- Hydraulics installation
- Electrical installation
- Start-up
- Adapting the unit to the heating installation
- Troubleshooting
- Decommissioning
- Customer service
- Appendix
- Freeze protection
- Maintenance messages
- Remedy
- High-efficiency pump
- Outdoor temperature sensor
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Vaillant VWS 36/4.1 230V geoTHERM Brine/Water Heat Pump
Product Description
The geoTHERM VWS 36/4.1 230V is a heat pump product manufactured by Vaillant GmbH. The product has safety devices to ensure safeoperation, and it is designed to function efficiently. The product comes with a data plate and CE label for easy identification. There are product stickers that provide additional information about the product.
Set-up
Before installing the heat pump, ensure that the packaging is removed, and the scope of delivery is checked. Select an appropriate installation site with minimum clearances specified in the manual. Use the mounting template to wall- mount the product with proper dimensions. Remove the front and side casing, and transport locks as required.
Hydraulics Installation
The hydraulics installation should be carried out as specified in the manual. Ensure that the heating circuit meets the requirements, and connect the heat pump to the heating circuit and brine circuit. Route the drain pipework of the expansion relief valve and fill and purge both heating and brine circuits.
Electrical Installation
The electrical installation should be carried out as specified in the manual. Route eBUS lines, open the electronics box, and follow the wiring diagrams provided.
Maintenance Instructions
Maintenance of the heat pump should be carried out regularly as specified in the manual. This includes checking safety devices, cleaning filters, and inspecting electrical connections. Any repairs or replacements should only be carried out by authorized personnel.
Safety
It is essential to follow all safety instructions provided in the manual. This includes action-related warnings and general safety information. The product should only be used for its intended use and in compliance with regulations, directives, laws, and standards.
Notes on the Documentation
It is important to observe all other applicable documents and store them safely. The instructions provided are valid at the time of publication.
Installation and maintenance instructions
geoTHERM
VWS 36/4.1 230V
Publisher/manufacturer Vaillant GmbH Berghauser Str. 40 D-42859 Remscheid Tel.
+492191180 Fax +492191182810 info@vaillant.de
www.vaillant.de
3
Safety
1 Safety
1.1 Action-related warnings
Classification of action-related warnings The action-related warnings are
classified in accordance with the severity of the possible danger using the
following warning signs and signal words:
Warning symbols and signal words Danger! Imminent danger to life or risk of
severe personal injury
Danger! Risk of death from electric shock
Warning. Risk of minor personal injury
Caution. Risk of material or environmental damage
1.2 General safety information
1.2.1 Danger caused by improper operation
Improper operation may present a danger to you and others, and cause material
damage.
Carefully read the enclosed instructions and all other applicable documents,
particularly the “Safety” section and the warnings.
Only carry out the activities for which instructions are provided in these
operating instructions.
1.2.2 Risk caused by inadequate qualifications
Applicability: Not for Russia and Kazakhstan
OR Not for Russia
OR Not for Kazakhstan
The following work must only be carried out by competent persons who are
sufficiently qualified to do so:
Set-up Dismantling Installation Start-up Inspection and maintenance
Repair Decommissioning
Observe all instructions that are included with the product.
Proceed in accordance with current technology.
Observe all applicable directives, standards, laws and other regulations.
1.2.3 Risk of death due to lack of safety devices
The schematic drawings included in this document do not show all safety
devices required for correct installation.
Install the necessary safety devices in the system.
Observe the applicable national and international laws, standards and
guidelines.
1.2.4 Risk of death from electric shock
There is a risk of death from electric shock if you touch live components.
Before commencing work on the product:
Unplug the mains plug. Or disconnect the product from the power
supply by switching off all power supplies (electrical partition with a
contact gap of at least 3 mm, e.g. fuse or circuit breaker). Secure against
being switched back on again. Wait for at least 3 minutes until the capacitors
have discharged. Check that there is no voltage.
1.2.5 Danger due to malfunctions
Ensure that the heating installation is in a technically perfect condition.
Ensure that no safety or monitoring devices have been removed, bridged or
disabled.
Immediately eliminate any faults and damage that may affect safety.
Install the control in a location where it is not covered by furniture,
curtains, or other objects.
If room temperature modulation is activated, be aware that, in the room where
the control is mounted, all the radiator valves must be fully open.
4
Installation and maintenance instructions geoTHERM 0020250181_00
Safety 1
Do not use the products’ free terminals as supporting terminals for other
wiring.
At lengths of over 10 m, 230 V connection cables must be laid separately from
sensor or bus lines.
1.2.6 Preventing the risk of injury from corrosive brine fluid
The brine fluid ethylene glycol is harmful to health.
Avoid contact with the skin and eyes. Always wear gloves and protective
goggles. Do not inhale or swallow. Observe the safety data sheet that accom-
panies the brine fluid.
1.2.7 Preventing the risk of injury due to scalding from hot and cold
components
Particularly in the refrigeration circuit, the components of the heat pump can
reach high temperatures or extremely low temperatures.
Do not touch any uninsulated pipelines in any part of the heating
installation.
Do not remove any casing sections. Do not touch the compressor, as it can
become extremely hot during operation. If the components have reached the
envir-
onmental temperature, you can start work.
1.2.8 Risk of injury due to the heavy weight of the product
Make sure that the product is transported by at least two people.
1.2.9 Preventing the risk of injury from freezing as a result of touching
refrigerant
The product is delivered with an operational filling of R410A refrigerant.
This is a chlorine-free refrigerant which does not affect the Earth’s ozone
layer. R410A is neither a fire hazard nor an explosion risk. Escaping
refrigerant may cause freezing if the exit point is touched.
If refrigerant escapes, do not touch any components of the product.
Do not inhale any steam or gases that escape from the refrigerant circuit as a
result of leaks.
Avoid skin or eye contact with the refrigerant.
In the event of skin or eye contact with the refrigerant, seek medical advice.
1.2.10 Risk of material damage caused by condensate inside the house
In heating mode, the lines between the heat pump and the heat source
(environment circuit) are cold, which means that condensate may form on the
lines in the house. In cooling mode, the building circuit lines are cold,
which means that condensate may also form if the temperature falls below the
dew point. Condensate may lead to material damage, for example due to
corrosion.
Ensure that you do not damage the heat insulation on the lines.
1.2.11 Material damage due to additives in the heating water
Unsuitable frost or corrosion protection agents may damage seals and other
components of the heating circuit, and may therefore also cause water leaks.
Only add approved frost and corrosion protection agents to the heating water.
1.2.12 Damage to the building caused by missing isolator devices
Missing isolator devices may lead to damage to the building.
Install the isolator devices that are required in accordance with the
installation standards.
1.2.13 Frost damage due to an unsuitable installation site
Frost poses a risk of damage to the product and the whole heating
installation.
Even if rooms, or the whole flat, are not in use for certain periods, the
heating must remain in operation.
Frost protection and monitoring devices are only active while the product is
connected to the power supply. The product must be connected to the power
supply.
0020250181_00 geoTHERM Installation and maintenance instructions
5
1 Safety
The heat pump itself does not have a frost protection function. For smooth
operation of the refrigeration circuit, a minimum room temperature of 7 °C
must be maintained. If the room temperature falls below 7 °C, this may lead to
frost damage on the heat pump.
1.2.14 Frost damage caused by insufficient room temperature
If the room temperature is set too low in individual rooms, it cannot be ruled
out that sections of the heating installation might be damaged by frost.
If you are going to be away during a cold period, ensure that the heating
installation remains in operation and that the rooms are sufficiently heated.
You must observe the frost protection instructions.
1.2.15 Frost damage as a result of a power cut
If the power supply is cut, it is possible that parts of the heating
installation may become damaged by frost.
If you want to use an emergency power generator to maintain the operational
readiness of the product during a power cut, note the following:
Make sure that the technical values of this emergency power generator
(frequency, voltage, earthing) match those of the power grid.
1.2.16 Material damage due to unsuitable installation surface
The installation surface must be even and have sufficient load-bearing
capacity to support the operating weight of the product. An uneven
installation surface may cause leaks in the product. If the installation
surface does not have sufficient load-bearing capacity, the product may become
detached and fall off. There is a risk of death if the connections are subject
to leaks.
Make sure that the product is positioned flush against the installation
surface.
Ensure that the installation surface has sufficient load-bearing capacity to
bear the operating weight of the product.
1.2.17 Risk of material damage caused by using an unsuitable tool
Use the correct tool to tighten or loosen threaded connections.
1.2.18 Product fault as a result of incorrect system pressure
To avoid operating the system with too little water and thus prevent resulting
damage, note the following:
Check the system pressure of the heating installation at regular intervals.
The system pressure instructions must be observed.
1.2.19 Avoid environmental damage caused by escaping refrigerant
The product contains R 410 A refrigerant. The refrigerant must not be allowed
to escape into the atmosphere. R410A is a fluorinated greenhouse gas covered
by the Kyoto Protocol, with a GWP of 2088 (GWP = global warming potential). If
this gas escapes into the atmosphere, its impact is 2088 times greater than
the natural greenhouse gas CO2.
Before the product is disposed of, the refrigerant that is contained in it
must be completely drained into a suitable vessel so that it can then be
recycled or disposed of in accordance with regulations.
Ensure that only officially certified competent persons with appropriate
protective equipment carry out maintenance work on the refrigerant circuit or
access it.
Arrange for the refrigerant that is contained in the product to be recycled or
disposed of by a certified competent person in accordance with the
regulations.
1.3 Intended use
There is a risk of injury or death to the user or others, or of damage to the
product and other property in the event of improper use or use for which it is
not intended.
The brine-to-water heat pump is designed for use as a heat generator for
closed heating installations. The product is intended exclusively for domestic
use as a heat generator for closed central heating installations. Operating
the product outside the operating limits res-
6
Installation and maintenance instructions geoTHERM 0020250181_00
ults in the product being switched off by the internal control and safety
devices.
Intended use includes the following:
observance of accompanying operating, installation and maintenance
instructions for the product and any other system components
installing and fitting the product in accordance with the product and system
approval
compliance with all inspection and maintenance conditions listed in the
instructions.
Intended use also covers installation in accordance with the IP class.
Any other use that is not specified in these instructions, or use beyond that
specified in this document, shall be considered improper use. Any direct
commercial or industrial use is also deemed to be improper.
Caution.
Improper use of any kind is prohibited.
1.4 Regulations (directives, laws, standards)
Observe the national regulations, standards, guidelines and laws.
Safety 1
0020250181_00 geoTHERM Installation and maintenance instructions
7
Notes on the documentation
2 Notes on the documentation
2.1 Observing other applicable documents
You must observe all the operating and installation in-
structions included with the system components.
The outlet temperature of the heat source is constantly measured. If the outlet temperature of the heat source falls below a certain value, the compressor temporarily switches off and displays a status message. If this fault occurs three times in succession, the unit is permanently shut down and displays a fault message.
2.2 Storing documents
Pass these instructions and all other applicable docu-
ments on to the system operator.
2.3 Validity of the instructions
These instructions apply to products with the following type designations and
article numbers only:
Type designation VWS 36/4.1 230 V
Art. no. 0010022462
You can find the 10-digit article number for the heat
pump on the plate that is located behind the front flap. The seventh to
sixteenth digits of the serial number on the data plate form the article
number.
Product description
3.1 Safety devices
3.1.1 Frost protection function
The frost protection function for the system is controlled via the system
control. If the system control fails, the heat pump guarantees limited frost
protection for the heating circuit.
3.1.2 Protection against low heating water pressure
This function continuously monitors the pressure of the heating water in order
to prevent a possible loss of heating water.
An analogue pressure sensor switches off the heat pump if the water pressure
drops below the minimum pressure. It switches the heat pump on again if the
water pressure reaches the operating pressure.
Minimum heating water pressure: 0.05 MPa ( 0.50 bar)
Heating water operating pressure: 0.07 MPa ( 0.70 bar)
3.1.3 Brine pressure detector
The brine loss protection system continuously monitors the fluid pressure in
the environment circuit in order to prevent a possible shortage of fluid.
An analogue pressure sensor switches off the heat pump if the fluid pressure
drops below the minimum pressure. It switches the heat pump on again if the
fluid pressure reaches the operating pressure.
Minimum brine fluid pressure: 0.05 MPa ( 0.50 bar) Brine fluid operating
pressure: 0.07 MPa ( 0.70 bar)
3.1.5 Pump- and valve-blocking protection system
This function prevents the pumps for heating water and brine and all diverter
valves from sticking. The pumps and the valves, which were out of operation
for 23 hours, are switched on for 10 – 20 seconds, one after the other.
3.1.6 High-pressure pressure switch in the refrigeration circuit
The high-pressure pressure switch shuts down the heat pump if the pressure in
the refrigeration circuit is too high.
If the pressure in the heat pump’s refrigeration circuit exceeds the maximum
pressure, the high-pressure pressure switch temporarily shuts down the heat
pump. Following a waiting period, another attempt is made to start the heat
pump. After eleven failed start attempts in succession, a fault message is
displayed.
Max. refrigeration circuit pressure: 4.15 MPa (g) (41.50 bar (g))
Waiting period: 5 minutes (after the first occurrence) Waiting period: 30
minutes
(after the second and every further occurrence)
The fault counter is reset if both of the following conditions are met:
Heat requirement without switching off prematurely 60 minutes of
uninterrupted operation
3.1.7 Pressure sensor in the heating circuit and brine circuit
The heating circuit and brine circuit each have a pressure sensor which
measures the actual pressure.
The pressure can be read in the heat pump’s display. If the pressure in either
of the circuits falls below the minimum operating pressure, a fault message is
shown in the heat pump’s display.
Heating water operating pressure: 0.07 MPa ( 0.70 bar)
Brine fluid operating pressure: 0.07 MPa ( 0.70 bar)
3.1.4 Freeze protection
This function prevents the evaporator from freezing when the heat source
temperature drops below a certain value.
8
Installation and maintenance instructions geoTHERM 0020250181_00
3.2 Design and functionality of the product
3.2.1 Design
19
1
2
18
17 16 15 14
13 3
12 4
5
11
Product description 3
1 2 3 4
5 6 7 8
9
1 Removable hood 2 Front casing 3 Operating panel
7
10
1 Condenser
2 Compressor outlet
temperature sensor
4 Plate with serial number 3 Rotary piston com-
on the rear
pressor
5 Front flap
4 High-pressure pressure switch
5 High-pressure sensor
6 Relay PCB
7 Heating pump
8 Flow rate sensor
9 Switch box
10 Heating circuit expansion relief valve
11 Brine circuit pressure sensor
12 Brine mixer
13 Brine pump
14 Refrigerant collector
15 Low-pressure sensor
16 Electronic expansion valve
17 Compressor inlet temperature sensor
18 Evaporator
19 Purging valves
6
5
43
1 Cable feedthrough for electrical connections
2 Heating return
3 Heating flow
4 Expansion relief valve drain hose
2
1
5 From the heat pump to the heat source (cold brine)
6 From the heat source to the heat pump (hot brine)
7 Data plate
0020250181_00 geoTHERM Installation and maintenance instructions
9
3 Product description
3.2.2 Functionality 3.2.2.1 Heat pump
8
9
10
7
6
3 21
4 5
Information on the data plate
B0/W35
B0/W55
Volt Hz W IP
Meaning
Heating output at a brine temperature of 0 °C and heating flow temperature of
35 °C Heating output at a brine temperature of °C and heating flow temperature
of 55 °C Mains voltage
Mains frequency
Power consumption
Protection class
Information on disposal
Reading the operating and installation instructions
1 Heating pump
2 Condenser
3 Filter element
4 Electronic expansion valve
5 Printed circuit board
6 Evaporator 7 Brine pump 8 Brine mixer 9 Rotary compressor 10 Intermediate
heat ex-
changer
The product is a brine-to-water heat pump and uses geothermal energy as a heat
source.
The heat pump consists of the following separate circuits which are coupled
with one another by means of heat exchangers. These circuits are:
The brine circuit, which extracts the thermal energy from the ground or the
ground water and transfers this to the refrigeration circuit
The refrigerant circuit, which is used to bring the thermal energy from the
ground to a usable, higher temperature level and deliver it to the heating
circuit
The heating circuit, which is used to heat up the living rooms
3.4 Explanation of product stickers
Symbol on the sticker
Meaning Heating flow connection
Heating return connection
Connection from the heat source to the heat pump (hot brine)
Connection from the heat pump to the heat source (cold brine)
Brine heat source
3.3 Information on the data plate The data plate is mounted on the underside of the product.
Information on the data plate Serial no.
P max I max
Meaning
Unique unit identification number Measuring voltage of the compressor, pumps
and controls
Maximum rated power Maximum in-rush current Refrigerant type, fill quantity,
permissible rated overpressure
3.5 CE label
The CE label shows that the products comply with the basic requirements of the
applicable directives as stated on the identification plate. The declaration
of conformity can be viewed at the manufacturer’s site.
COP B0/W35 COP B0/W55
Output figure (coefficient of performance) at a brine temperature of 0 °C and
heating flow temperature of 35 °C
Coefficient of performance at a brine temperature of 0 °C and heating flow
temperature of 55 °C
10
Installation and maintenance instructions geoTHERM 0020250181_00
Set-up
3.6 Benchmark
Applicability: Great Britain
Vaillant is a licensed member of the Benchmark Scheme.
Benchmark places responsibilities on both manufacturers and installers. The
purpose is to ensure that customers are provided with the correct equipment
for their needs, that it is installed, commissioned and serviced in accordance
with the manufacturer’s instructions by a competent person approved at the
time by the Health and Safety Executive and that it meets the requirements of
the appropriate Building Regulations. The Benchmark Checklist can be used to
demonstrate compliance with Building Regulations and should be provided to the
customer for future reference.
Installers are required to carry out installation, commissioning and servicing
work in accordance with the Benchmark Code of Practice which is available from
the Heating and Hotwater Industry Council who manage and promote the Scheme.
Benchmark is managed and promoted by the Heating and Hotwater Industry
Council.
4.3 Selecting the installation site
Select a dry room that is frost-proof throughout and
where the environmental temperature does not fall below 7 °C and does not
exceed a maximum of 40 °C.
The installation room must have a minimum volume of
1.60 m³ at a refrigerant volume of 0.70 kg (R410A).
Ensure that the required minimum clearances can be
maintained.
Choose the installation site so that, where possible, vi-
brations that occur during operation are not transferred.
Ensure that the fastening is adapted to the circumstances
so that it can bear the weight of the heat pump.
Weight without packaging: 59 kg
In the case of walls with a mass per unit area of less than
200 kg/m2, lightweight construction walls and, in particular, dry-lined walls,
use a mounting frame for the prewall installation of the heat pump in order to
prevent vibrations and resulting noise emissions.
Secure the mounting frame to the wall only at floor and
ceiling level in order to minimise vibrations.
Ensure that cables can be easily routed (for brine, do-
mestic hot water and heating).
Use an open hopper for the drain hose on the expansion
relief valve in the heating circuit.
Ensure that there is an option to divert any condensate
that forms.
For more information visit www.centralheating.co.uk
4 Set-up
4.1 Removing the packaging
Carefully remove the packaging and padding without
damaging the parts of the product.
Note Remove the transport locks from the product only after it has been
mounted on the wall or on the mounting frame.
4.2 Checking the scope of delivery
Check that the scope of delivery is complete.
Quantity Designation
1
Unit mounting bracket
1
Bag of small parts with fixing material
1
Heat insulation for the brine line
1
Heat pump
1
Installation set:
4 x compression fitting 2 x connection pipe (22 mm Cu) 2 x seal with
metal support ring for brine
circuit, 2 x flat seal for heating circuit
1
Enclosed documentation
4.4 Transporting the heat pump
Warning. Risk of injury from lifting a heavy weight. The heat pump weighs 59
kg.
To prevent injuries, have several people
lift the heat pump.
Caution. Risk of damage due to improper transportation. Regardless of the mode
of transport, the heat pump must never be tilted by more than 45°. Otherwise,
this may lead to faults in the refrigerant circuit during subsequent
operation. In the worst case scenario, this may lead to a fault in the whole
system.
During transport, do not tilt the heat pump
by any more than the maximum angle of 45°.
1. Have two people lift the product on the frame. 2. Transport the product to
the installation site.
0020250181_00 geoTHERM Installation and maintenance instructions
11
4 Set-up
3. Always transport the product as illustrated above. 4. Never transport the
product as illustrated above.
12
Installation and maintenance instructions geoTHERM 0020250181_00
4.5 Dimensions
440
426
Set-up 4
720 113
198
77 100
55 100
40
0020250181_00 geoTHERM Installation and maintenance instructions
13
4 Set-up
4.6 Minimum clearances
A
4.8 Wall-mounting the product
1
B 2
B
3
D C
The product is securely mounted on a wall.
Minimum clearance to the uniTOWER and domestic hot water cylinder
Minimum clearance to the MEH 60, MEH
61 and gas-fired wall-hung boiler
A
200 mm
B
300 mm
100 mm
C
500 mm
D
600 mm
Comply with the minimum clearances specified in order
to facilitate maintenance work.
If the product is mounted next to the uniTOWER accessory module, a clearance
of 300 mm must be maintained.
If the product is mounted next to the MEH61/60 accessory module, a clearance
of 100 mm must be maintained.
4.7 Using the mounting template
Note A mounting template is supplied with the product to aid wall mounting.
Danger! Risk of accidents as a result of insufficient load-bearing capacity of
the fixing means.
If the fixing elements or wall do not have sufficient load-bearing capacity,
the product may come loose and fall down. Brine fluid may leak from damaged
lines.
When installing the product, ensure that
the fixing elements and the wall have sufficient load-bearing capacity.
Check the quality of the wall.
1. Use the minimum wall clearances ( Page 14) and the supplied mounting
template to align the product.
2. Observe the requirements for the installation site ( Page 11).
3. Install the unit mounting bracket (1) on the wall or mounting frame using
the rawl plugs and screws (2) provided.
4. Hang the product (3) on the unit mounting bracket from above using the
hanging bracket.
1. Position the mounting template vertically over the installation site.
2. Attach the template to the wall, using tacks for example.
3. Mark the drill holes for the unit mounting bracket on the wall.
14
Installation and maintenance instructions geoTHERM 0020250181_00
4.9 Removing the front casing
2
Hydraulics installation
4.11 Removing the transport locks
1. Remove the front casing as shown in the illustration. ( Page 15)
2. Remove the side casing. ( Page 15) 3. Remove the left- and right-hand
transport locks (foam
pieces): To the side below the refrigeration circuit platform. 4. Remove the
transport lock (foam piece) from the front casing.
1
1. Undo the screw (1) on the underside of the product. 2. Push in the two
retaining clips (2) on the underside of
the product so that the front casing is released. 3. Pull the front casing
forwards at the bottom edge. 4. Lift the front casing up and out of the
retainer. 4.10 Removing the side casing
3.
5 Hydraulics installation
Observe the relevant information about hydraulic installa-
tion in the appendix and in the system instructions.
5.1 Carrying out the hydraulics installation
Caution. Risk of damage caused by residue in the heating flow and return.
Residue from the pipelines, such as welding beads, scale, hemp, putty, rust
and coarse dirt, may be deposited in the heat pump and cause faults.
Flush the heating installation thoroughly
before connecting the heat pump in order to remove any possible residue.
Caution. Risk of damage caused by leaks. Mechanical stress on connection
cables may cause leaks and damage to the product.
Avoid mechanical stress on connection
cables.
- 1. 1. Remove both screws (1). 2. Pull the lower section of the side casing forwards. 3. Lift the side casing up to remove it.
1. Install the connection cables in accordance with the dimension and
connection drawings.
2. Position the pipe brackets for securing the heating circuit and solar
circuit piping so that they are not too close to the heat pump in order to
prevent noise transmission.
Note The heat pump’s compressor has two-fold vibration insulation. This
eliminates vibrations in the refrigeration circuit that are inherent in the
system. However, under certain circumstances, residual vibrations may occur.
3. If required, instead of pipe brackets, use cold insulation brackets with
additional rubber insulation and, in some cases, reinforced hoses (armoured
rubber hoses).
4. To prevent excessive pressure losses on the heating water side, do not use
stainless steel corrugated pipes.
5. Attach purging valves to the heating installation.
0020250181_00 geoTHERM Installation and maintenance instructions
15
5 Hydraulics installation
5.2 Requirements for the heating circuit
In heating installations that are equipped primarily with thermostatic or
electrically controlled valves, a constant and sufficient flow through the
heat pump must be ensured. Irrespective of which heating installation is
selected, the minimum volume of circulating heating water (40% of the nominal
volume flow, see the technical data table) must be guaranteed as the product
does not have a bypass valve.
5.3 Connecting the heat pump to the heating circuit
Caution. Risk of damage from magnetite deposition.
In heating installations with steel pipes, static heating surfaces and/or
buffer cylinder systems, magnetite may form where large volumes of water are
involved.
Insert a magnetite filter to protect the
pump inside the product.
You must position the filter in direct prox-
imity to the return line to the heat pump.
1. Install the expansion relief valve hose in a frost-free environment and
ensure that its routing ends in an open hopper where it is then visible.
2. Connect the heating flow to the heating flow connection of the heat pump.
3. Connect the heating return to the heating return connection of the heat
pump.
4. Insulate all of the pipes in the heating circuit and the connections for
the heat pump so that they are vapour diffusion-tight in order to prevent them
from falling below the dew point in cooling mode.
5.4 Connecting the heat pump to the brine circuit
Caution. Risk of damage due to unsuitable frost and corrosion protection
agents.
Unsuitable frost or corrosion protection agents may damage seals and other
components and may therefore also cause leaks in the water outlet.
Only add permitted frost or corrosion pro-
tection agents to the heating water.
Observe the filling regulations.
A
1
B
1. Remove the blind caps (1) from the unit’s connections. These are no longer
required and can be properly disposed of.
2. Connect the brine lines to the heat pump.
3. Connect the brine lines to connection “A” (hot brine) and “B” (cold brine)
of the heat pump.
4. Install an automatic air separator in the brine circuit on the
installation side.
5. Insulate all of the brine lines and the connections of the heat pump so
that they are vapour diffusion-tight.
Caution.
5.5
In cooling mode, there is a risk of damage
caused by the temperature falling below
the dew point and by a build-up of con-
densation.
Radiator heating is not suitable for cooling mode with this product.
Ensure that the radiator heating is not
used for the cooling mode.
Routing the drain pipework of the expansion relief valve
Note The expansion relief valve for the heating installation is integrated
into the product.
Warning. Risk of scalding caused by steam or hot water!
If there is overpressure, then steam and/or hot water is guided out via the
drain hose of the expansion relief valve.
Have the hose end in such a way that
nobody is at risk when steam and/or hot water is drained.
1 1. Install a tundish for the expansion relief valve.
16
Installation and maintenance instructions geoTHERM 0020250181_00
Hydraulics installation 5
Diameter of the tundish/discharge pipe: 32 mm ( 1.26 in)
2. Install the tundish in such a way that no cables or other electrical
components can be damaged if there is a water leak.
The end of the line must be visible.
5.6 5.6.1
Filling and purging the heating circuit
Checking and treating the heating water/filling and supplementary water
Caution. Risk of material damage due to poor-quality heating water
Ensure that the heating water is of suffi-
cient quality.
Applicability: Great Britain
Total heating output
Water hardness at specific system volume1)
20 l/kW
20 l/kW 50 l/kW
50 l/kW
kW
ppm mol/ ppm mol/ ppm mol/ CaCO m³ CaCO m³ CaCO m³
< 50
< 300 < 3
200 2
2
0.02
50
200 2
to 200
150 1.5
2
0.02
200
150 1.5
2
0.02 2
0.02
to 600
600
2
0.02 2
0.02 2
0.02
- Nominal capacity in litres/heating output; in the case of multiboiler systems, the smallest single heating output is to be used.
Applicability: Great Britain
Before filling or topping up the installation, check the
quality of the heating water.
Checking the quality of the heating water
Remove a little water from the heating circuit. Check the appearance of the
heating water. If you ascertain that it contains sedimentary materials,
you must desludge the installation.
Use a magnetic rod to check whether it contains mag-
netite (iron oxide).
If you ascertain that it contains magnetite, clean the in-
stallation and apply suitable corrosion-protection measures, or fit a magnet
filter.
Check the pH value of the removed water at 25 °C. If the value is below 8.2 or
above 10.0, clean the installa-
tion and treat the heating water.
Ensure that oxygen cannot get into the heating water.
Checking the filling and supplementary water
Before filling the installation, measure the hardness of the
filling and supplementary water.
Treating the filling and supplementary water
Observe all applicable national regulations and technical
standards when treating the filling and supplementary water.
Provided the national regulations and technical standards do not stipulate
more stringent requirements, the following applies:
You must treat the heating water in the following cases:
If the entire filling and supplementary water quantity during the operating
life of the system exceeds three times the nominal volume of the heating
installation, or
If the guideline values listed in the following table are not met, or
If the pH value of the heating water is less than 8.2 or more than 10.0.
Caution. Risk of material damage if the heating water is treated with
unsuitable additives.
Unsuitable additives may cause changes in the components, noises in heating
mode and possibly subsequent damage.
Do not use any unsuitable frost and cor-
rosion protection agents, biocides or sealants.
No incompatibility with our products has been detected to date with proper use
of the following additives.
When using additives, follow the manufacturer’s instruc-
tions without exception.
We accept no liability for the compatibility of any additive or its
effectiveness in the rest of the heating system.
Additives for cleaning measures (subsequent flushing required) Adey MC3+
Adey MC5 Fernox F3 Sentinel X 300 Sentinel X 400
Additives intended to remain permanently in the installation Adey MC1+
Fernox F1 Fernox F2 Sentinel X 100 Sentinel X 200
Additives for frost protection intended to remain permanently in the
installation Adey MC ZERO Fernox Antifreeze Alphi 11 Sentinel X 500
If you have used the above-mentioned additives, inform
the end user about the measures that are required.
Inform the end user about the measures required for frost
protection.
0020250181_00 geoTHERM Installation and maintenance instructions
17
5 Hydraulics installation
5.6.2 Filling/refilling the heating installation
1. Open all of the thermostatic valves on the heating installation and, if
required, all other isolation valves.
2. Check all of the connections and the entire heating installation for
leaks.
3. To remove air pockets from the heating installation, use a filling pump to
rinse the heating installation. To do this, fill the heat pump via the return
line and allow the water to flow out via the flow line.
5.7 Filling and purging the brine circuit
5.7.1 Mixing the brine fluid
The brine fluid consists of water mixed with a concentrated antifreeze. The
brine fluids that may be used differ greatly from region to region. For more
information, contact the responsible authorities.
Only ethylene glycol in the specified ratio is authorised by Vaillant as a
brine fluid for operating the heat pump.
Alternatively, suitable ready-mixed fluids for heat pumps can be ordered from
Vaillant.
Carefully mix ethylene glycol with water.
Ratio of ethylene glycol to water: 3:7
This results in an aqueous solution with 30% vol.
ethylene glycol.
The brine fluid is protected against frost.
Frost protection for the brine fluid: -16 … -14
Check the mixture ratio of the brine fluid.
Working materials: Refractometer
5.7.2 Filling the brine circuit
71
42a
69
65
33
67 61
37
62
48
63
66
29
A B
71 Expansion vessel
A From the heat source to the heat pump (hot brine)
B From the heat pump to the heat source (cold brine)
1. Install a dirt filter (33) in the pressure line. 2. Connect the filling
pump’s pressure line to the isolation
valve (61). 3. Close the isolation valve (63). 4. Open the isolation valve
(61). 5. Connect a hose, which leads to the brine fluid, to the
isolation valve (62). 6. Open the isolation valve (62).
Caution. Risk of material damage caused by an incorrect filling direction.
If you fill the brine pump against the direction of flow, this may lead to a
turbine effect which can damage the pump’s electronics.
Ensure that the brine pump is filled in the
direction of flow.
7. Use the filling pump (67) to pour the brine fluid from the brine container
(66) into the brine circuit. Brine fluid: Ethylene glycol/water ratio: 3/7
8. If you choke the filling pump, you can reduce the air ingress into the
brine circuit.
5.7.3 Purge the brine circuit
1. Start up the filling pump (67) in order to fill and rinse the brine
circuit.
2. Allow the filling pump (67) to run for at least 10 minutes in order to
fill and rinse the circuit sufficiently.
3. Then close the isolation valves (61) and (62) and switch off the filling
pump (67).
4. Open and close the purging valves (69) on the heat pump and check whether
air is still escaping.
5. Purge the heat pump completely in order to prevent its functioning from
being impaired by air in the brine circuit.
6. Place a silicone hose (5 mm diameter) on the purging valves and catch the
brine fluid in a bucket.
7. If required, repeat this rinsing process. 8. Open the isolation valve
(63).
5.7.4 Building up pressure in the brine circuit
1. Use the filling pump (67) to pressurise the brine circuit.
29 Brine pump
33 Dirt filter
37 Automatic air separator
42a Expansion relief valve
48 Pressure gauge (optional)
61 Stop valve
62 Stop valve
63 Stop valve
65 Brine collecting container
66 Brine container
67 Filling pump
69 Purging screws
Note To operate the brine circuit without any problems, a filling pressure of
0.15 MPa (1.5 bar) is required. The expansion relief valve opens at 0.3 MPa (3
bar).
2. Read off the pressure on the manometer.
18
Installation and maintenance instructions geoTHERM 0020250181_00
Electrical installation
Brine circuit operating pressure: 0.15 MPa (1.50 bar)
3. Build up the pressure in the brine circuit by using the filling pump to
top up the brine fluid by opening the isolation valve (61).
4. Open the isolation valve (62) to allow any excess pressure to escape if it
is above the required filling pressure of 0.15 MPa (1.5 bar) and below the
expansion relief valve’s operating pressure of 0.3 MPa (3 bar).
5. Check the brine circuit’s filling pressure in the heat pump’s DIA system.
6. If required, repeat the process. 7. Remove the two hoses from the valves
(61) and (62). 8. Purge the system once more after starting up the heat
pump. 9. Pass the vessel with the remaining brine fluid on to the
end user to be stored.
6 Electrical installation
6.1 Carrying out the electrical installation
1. Observe the relevant information about electrical installation in the
appendix and in the system instructions.
Danger! Risk of electric shock!
Touching live connections may cause serious personal injury.
Before carrying out electrical installation
work, always pull the product’s mains plug out of the earthed plug socket.
Secure the power supply against being
switched back on.
Danger! Risk of death from electric shock as a result of an improper
electrical connection!
An improper electrical connection may negatively affect the operational safety
of the product and result in material damage or personal injury.
The electrical installation must be carried
out by a suitably qualified competent person who is responsible for complying
with the existing standards and directives.
Strip the cable ends to a maximum of
10 mm.
Take care to wire up correctly.
2. When electrically connecting the product, observe the technical connection
conditions for connecting to the power supply network operator’s low-voltage
network.
3. Route low-voltage wires, such as sensor lines, on-site in the building so
that there is sufficient clearance to 230 V lines. Minimum clearance for the
low-voltage wire and power supply cable at a line length of > 10 m: 25 cm.
4. To establish the power supply, plug the heat pump’s mains plug into a
suitable earthed plug socket. You must observe the notes ( Page 24)on this.
Make sure that the earthed plug socket for the heat pump is individually
fused. The earthed plug socket must be freely accessible at all times
following installation.
Note If one of the product’s power supply cables is damaged, you must replace
it with a special connection cable that is available from the manufacturer or
customer service.
5. Observe the maximum line length of the sensor lines. Max. length of the
sensor line: 50 m (164 ft 1 in)
6.2 Routing eBUS lines 1. Route the eBUS lines in a star formation from a
junction
box to the individual products. 2. If several conductors are connected, use
connection
terminals. 3. Ensure that you do not route the eBUS lines parallel to
the power supply cables. Piping diameter: 0.75 mm²
6.3 Opening the electronics box
3
Caution. Material damage caused by short circuit.
A maximum of 10 mm of the insulation may be removed from the ends of lines
that carry mains voltage (230 V) for the connection to the 230 V terminal. If
more insulation is removed, there is a risk of short circuits on the PCB if
the cable has not been correctly secured to the 230 V terminal.
2. 1
2
1. Hinge the electronics box (1) forwards. 2. Undo the four clips on the rear
cover (2) of the electron-
ics box from the brackets (3) on the electronics box at the rear and at the
sides.
0020250181_00 geoTHERM Installation and maintenance instructions
19
6 Electrical installation
3. Hinge up the cover. 4. Note the components and accessories in the relevant
system instructions ( Page 51) that you have to connect in the electronics
box.
20
Installation and maintenance instructions geoTHERM 0020250181_00
6.4 Wiring diagrams
230V~ NL
Electrical installation 6
34 1 2 5 6 78
1
X20
Relay PCB
Compressor
SRC
Operating
capacitor
X2
52
M
X18
X17 X19 X1A
X1B
X1C
X70
X700
230V~ 230V~ 230V~ 230V~ 230V~ 230V~
230V~
230V~
LBLA N L N L LO L N L N L N C R N
L LS
X100
6 5
-+
4
24= 24=
3
S20 S21 BUS
2
1
1 2 3 45 67 8 9 1 0 11 12 13 14 15 16
X24
7 8
1 12 34 5 67 8
X20
12 34
X25
X51
X30
Yellow Blue
SSM 2 GND & SSM 1 PWM2 PWM1
Brown Red
PWM1 SSM1
SSM2
GND PWM2
GND
Building
circuit pump
LN
Environ- L N mental
circuit pump
LN
LN
L L C ON L N L N L N
230V~ X1
230V~ 230V~
230V~ 230V~ 230V~ 230V~
X14 X700 X15
X13
X16
X1 1
X12
F1
Main PCB
3-way mixer
M
X40
10 9 8 7 6 543 21
X23
18 17 16 15 14 13 12 11 10 20 19 18 17 16 15 14 13 12 11 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1
X21
X22
p
High-pressure switch
Red Black Grey Yellow Orange
M Electronic expansion valve
Relay PCB
X700
Compressor safety relay
X70
Compressor
X1A
—
X1B
Power supply
X1C
Main PCB mains connection transfer
X17
Cooling active signal, thermostatic radiator valve
switch
X18
—
X19
—
X20
Main PCB control line
0020250181_00 geoTHERM Installation and maintenance instructions
21
6 Electrical installation
Main PCB F1 S20 S21 X1 X11 X12
X13 X14 X15
F2 T 4A/250 V fuse Contact thermostat connection (24 V=) — 230 V~ mains connection (main PCB) — Mains supply edge connector for the 2 in 7 additional module Environment circuit pump — —
X16 X20 – X25 X30 X40 X41
X51 X100 X700
Building circuit pump Internal electrical connections Diagnostics interface Control connection for 2 in 7 additional module DCF/AF edge connector (outdoor temperature sensor + DCF signal) AI display edge connector eBUS (e.g. VRC 700 control) Compressor safety relay
22
Installation and maintenance instructions geoTHERM 0020250181_00
Electrical installation 6
6.5 Connecting controls and accessories to the 13. Lay the lines correctly.
electronics
14. Use the strain reliefs to secure the cable in the elec-
Danger!
tronics box. 15. Close the electronics box. ( Page 23)
Risk of death from live connections!
There is a risk of death from electric shock
6.6 Closing the electronics box
when working in the heat generator’s elec-
tronics box.
3
Before working on the heat generator’s
electronics box, pull out the mains plug from the earthed plug socket.
Secure the power supply against being
switched back on.
Open the electronics box only when the
heat generator is disconnected from the power supply.
Caution. Risk of damage caused by incorrect installation.
Mains voltage at the incorrect plug terminals on the ProE system may destroy
the electronics.
Do not connect a mains voltage to the
eBUS terminals (+/-).
1. Open the electronics box. ( Page 19) 2. Guide the connection cables of the
components to be
connected (e.g. external components, outdoor temperature sensor) through the
grommet on the underside of the product. 3. Use strain reliefs. 4. Shorten the
connection cables as necessary. 5. Only strip a maximum of 3 cm from the outer
sheathing of the flexible lines. 6. Ensure the inner conductor insulation is
not damaged when stripping the outer sheathing. 7. Only strip inner conductors
just enough to establish good, sound connections. 8. Fit the stripped ends of
the conductors with crimp pin terminals to ensure a secure connection that is
free from loose strands and to thus prevent short circuits. 9. Use a
screwdriver to connect the ProE plug to the control’s connection cables.
Note Ensure that the conductors are securely fastened to the plug terminals of
the ProE plug.
10. Connect the controls and accessories in accordance with the wiring
diagrams in the appendix.
11. If you install the control in the product (depending on the basic system
diagram, see appendix), remove the panel from the product and insert the
control into the slot.
12. Plug the ProE plug into the relevant PCB slot of the heat pump’s main
PCB.
1
2
1. Close the back wall (2) by pressing downwards on the electronics box (1).
2. Ensure that all four clips (3) audibly click into the brackets.
3. Fold the electronics box upwards. 4. Attach the casing. ( Page 23) 5.
Attach the front casing. ( Page 24)
6.7 Checking the electrical installation
After the installation is complete, check the electrical
installation by checking that the established connections are secured
correctly and are sufficiently insulated.
6.8 Completing installation 6.8.1 Checking the system pressure and leak-
tightness 1. After completing the installation, carry out a check of
the system. 2. Start up the heat pump in accordance with the relevant
operating instructions.
Checking the water pressure and checking for water leaks 3. Check the heating
installation for leaks.
6.8.2 Attaching the casing to the heat pump 1. Hang the casing on the upper
hooks for the heat pump. 2. Use two screws to secure the casing to the front
side of
the heat pump.
0020250181_00 geoTHERM Installation and maintenance instructions
23
Start-up
6.8.3 Attaching the front casing to the heat pump
1. Place the front casing on the upper brackets. 2. Push the front casing
onto the heat pump until the re-
taining clips snap into place on the front casing. To help you, you can also
push the retaining clips upwards at the same time. 3. Secure the front casing
by screwing in the screw on the underside of the heat pump.
6.8.4 Connecting the heat pump to the power supply
Danger! Risk of death from electric shock!
The product is fitted with a CEE 7/7 mains plug at the factory. There is a
risk of death from electric shock if the mains plug is connected to an
incompatible earthed plug socket.
If no suitable country-specific earthed plug
socket is available, use a country-specific adapter plug with a protection
contact.
7.2 Starting up the heat pump
Plug the mains plug into an earthed plug socket. The display shows the basic
display.
7.3 Running through the installation assistant The installation assistant is
launched when the heat pump is switched on for the first time. You must
confirm the launching of the installation assistant. Once confirmed, all
heating demands from the heat pump are blocked. This status remains until the
installation assistant is completed or cancelled.
7.3.1 Setting the language
Set the required language.
7.3.2 Setting the freeze protection
Applicability: Ground/brine environment circuit type
If required, change the temperature. It is set to -7 °C at
the factory. Freeze protection: -13 … 4
Danger! Risk of fire caused by an incompatible earthed plug socket. The
product is fitted with a CEE 7/7 mains plug at the factory. There is a risk of
fire if the mains plug is connected to an incompatible earthed plug socket.
If no suitable country-specific earthed plug
socket is available, use a country-specific adapter plug with a protection
contact.
After completing all of the other installation steps, plug
the mains plug into a suitable earthed plug socket.
7 Start-up
Observe the relevant information about starting up the
unit in the system instructions.
7.1 Heat pump operating concept The operating concept and operation of the
heat pump is described in the operating instructions for the heat pump.
7.3.3 Purging the building circuit
Start the check programme P.05 in order to purge
( Page 29) the building circuit.
7.3.4 Purging the environment circuit
Start the check programme P.06 in order to purge
( Page 29) the environment circuit.
7.3.5 Telephone number for the competent person
You can store your telephone number in the appliance menu.
The operator can display it in the information menu. The tele-
phone number can be up to 16 digits long and must not con-
tain any spaces. If the telephone number is shorter, end the
entry after the last digit by pressing the right-hand selection
button
.
All of the digits to the right will be deleted.
7.3.6 Ending the installation assistant
Once you have run through the installation assistant suc-
cessfully, confirm by pressing .
The installation assistant will close and will not launch
again when the product is next switched on.
7.1.1 Overview of the installer level menu structure
Installer level overview ( Page 32)
24
Installation and maintenance instructions geoTHERM 0020250181_00
Adapting the unit to the heating installation
7.4 Calling up Live Monitor (checking status codes)
Menu Live Monitor
You can use this function to call up the status code of the heat pump, which
provides you with information about the current operating condition of the
heat pump (Status display ( Page 28)).
7.5 Calling up the installer level
1. Press and at the same time. Menu Installer level
2. Set the value 17 (code) and confirm by pressing .
7.7 Calling up statistics
Menu Installer level Test menu Statistics
You can use this function to call up the statistics for the heat pump.
7.8 Checking that the product works correctly
1. Start up the product in accordance with the relevant operating
instructions.
2. Navigate to Menu Installer level Test programmes Check programmes.
3. Check the heating mode using P.01. 4. Check the cooling mode using P.02.
7.6 Heating mode flow temperature control
For economical and fault-free operation of a heat pump, it is important to
regulate the start of the compressor. The startup of the compressor is the
point at which the highest loading occurs. Using the energy balance control,
it is possible to minimise the number of heat pump start-ups without having to
forgo the convenience of a comfortable room environment. As with other
weather-compensated heating controls, the control determines a target flow
temperature by recording the outdoor temperature using a heating curve. The
energy balance calculation is made on the basis of this target flow
temperature and the actual flow temperature the difference per minute is
measured and added up:
1 degree minute [°min] = 1 K temperature difference in the course of 1 minute
The heat pump starts up at a defined heat deficit (under the menu item
Configuration Compressor starts at) and only switches off again when the
supplied heat is equal to the heat deficit. The larger the preset negative
numerical value, the longer the periods for which the compressor operates or
does not operate.
As an additional condition, if there is a deviation of more than 7 K between
the actual flow temperature and the target flow temperature, the compressor is
directly switched on and switched off. The compressor always starts
immediately if a heating demand only just arises from the control (e.g. due to
a time period or switching from gas-fired product operation to heat pump
mode).
Time conditions for compressor operation
When operating the compressor, the following shall always apply:
Minimum running time: 2 minutes Minimum rest period: 5 minutes Minimum
time from start to start: 20 minutes
8 Adapting the unit to the heating installation
8.1 Adapting the unit to the heating installation
The installation assistant is launched when the heat pump is switched on for
the first time.
If you have already filled the heating installation and terminated the
installation assistant, but want to set the most important system parameters
again, you can also call up the Configuration menu item.
Menu Installer level Configuration
8.2 Heat pump setting parameters
To individually adjust the heat pump, you can adjust certain parameters in the
Configuration menu.
Menu Installer level Configuration
Parameter Explanation
Language
Select the required language here.
Contact data
As a competent person, you can enter your telephone number here. The end customer can read this number in the menu Information.
Compressor starts at
Heat deficit at which the compressor is started in heating mode. See section “Heating mode flow temperature control”.
Comp. hysteresis
Additional condition for switching the compressor on and off. See section “Heating mode flow temperature control”
Max. rem. feed head
Limiting the product’s remaining feed head in the building circuit. If the value is reduced, the pump speed is limited as far as necessary in order to prevent the remaining feed head from being exceeded.
Conf. build cir. pump
Switching between automatic mode (flow rate regulation with operation- dependent target values) and fixed value mode (1-100%). The fixed value mode should only be selected if the installation does not permit automatic mode.
Boiler supp. set p.
Flow rate target value for controlling the internal building circuit pump in the event that the gasfired boiler is used for the mixing circuit and the pump also runs in the heat pump. Only in conjunction with the VWZ ZK accessory.
Enviro. pump set p.
Target fixed value for the environment circuit pump. This setting is used to adapt to the installed environment circuit (e.g. ground probe or ground collector).
0020250181_00 geoTHERM Installation and maintenance instructions
25
8 Adapting the unit to the heating installation
Parameter Freeze protection
Enable emergency mode
Software version
Explanation
Minimum outlet temperature from the heat pump into the environment circuit at
which operation is stopped in order to prevent the brine from freezing.
If “On” is selected here and no control is connected (e.g. due to a defect),
it is possible to adjust a target flow value and select an operating mode in
the basic menu in order to operate the heat pump in limp home mode.
The version number for the main PCB (HMU xxxx) and the display (AI xxxx) are
shown here alternately.
Additional setting data is listed in the appendix.
8.3 Setting the high-efficiency pumps
8.3.1 Setting the building circuit pump
Automatic mode At the factory, the nominal volume flow is automatically
achieved by volume flow regulation. This volume flow regulation allows for
efficient operation of the heating pump because the pump speed is adjusted to
the hydraulic resistance of the system. Vaillant recommends that you retain
this setting.
Manual operation
[ mbar ] 700
600
500
400 300
5 K /460 l/h (VWS)
200 100
0
30
40
50
60
70
80
90
100 [ % ]
Menu Installer level Configuration Building circuit pump conf.
If you do not want to operate the pump in automatic mode, you can set the
manual mode in the Configuration menu. The diagram shows how setting the pump
actuation affects the remaining feed head at nominal volume flow for a
temperature spread of 5 K on the heating side.
Setting the maximum differential pressure in the building circuit If the
differential pressure in the building circuit is not permitted to exceed a
maximum value, this limit can be set in the Configuration menu within the
range of 0.02 to 0.07 MPa (0.2 to 0.7 bar).
Menu Installer level Configuration Max. remaining feed head
8.3.2 Setting the environment circuit pump
If the heat source temperature spread lies below 2 K due to low pressure
losses (large pipe cross-sections, low drilling depth) in continuous
operation, you can adjust the pump output. The following diagram shows how
setting the pump ac-
tuation affects the remaining feed heads at nominal volume flows for a heat source temperature spread of 3 K.
[ mbar ] 700
600
500
400 300
3K / 620 l/h (VWS)
200
100
0
30
40
50
60
70
80
90
100 [ % ]
The default setting for the environment circuit pump is 75%.
8.4 Setting the flow temperature in heating mode (with no control connected)
1. Activate manual operation.
Menu Installer level Configuration Enable
limp home mode
2. Press the right-hand selection button
(” “).
The display shows the flow temperature in heating
mode.
3. Use the minus button
or plus button
to change the flow temperature in heating
mode.
Max. heating mode flow temperature: 55 (131.0 )
4. Confirm the change by pressing the right-hand selection
button
(“OK”).
8.5 Setting the flow temperature in cooling mode (with no controller connected)
1. Activate manual operation.
Menu Installer level Configuration Enable limp home mode
2. Press the right-hand selection button twice.
(” “)
The display shows the value of the flow temperature
in cooling mode.
3. Use the minus button
or plus button
mode.
to change the flow temperature in cooling
4. Confirm the change by pressing the right-hand selection
button
(“OK”).
Note
At the factory, the target flow temperature can be set between 20 °C and 16 °C
in cooling mode.
26
Installation and maintenance instructions geoTHERM 0020250181_00
Inspection and maintenance 9
8.6 Handing the product over to the end user
Explain to the end user how the safety devices work and
where they are located.
Inform the end user how to handle the product. In particular, draw attention
to the safety information
which the end user must follow.
Inform the end user of the necessity to have the product
maintained according to the specified intervals.
Pass all of the instructions and documentation for the
product to the end user for safe-keeping.
9 Inspection and maintenance
9.1 Inspection and maintenance check-list
The following table shows the inspection and maintenance work that must be
carried out at specific intervals.
No. Work
1 Check the general condition and leak-tightness of the heat pump.
2 Check the pressure in the heating circuit and, if required, top up the
heating water.
3 Check the volume and concentration of the brine fluid and the pressure in
the brine circuit.
4 Check the condensate discharge of the heat pump for blockages and remove any
dirt or blockages.
5 Check that the expansion vessel in the heating circuit operates correctly.
6 Check the heat pump for leaks in the brine and heating circuit and eliminate
these leaks, if required.
Inspection (every year, within 24 months at the latest) x
x
x
x
x
x
Maintenance (every two years)
x x
x
x
x
x
9.2 Observing inspection and maintenance intervals
Danger! Risk of damage and personal injury as a result of neglected and
improper inspection and maintenance.
Inspection and maintenance work must only be carried out by a competent
person.
Carry out the inspection and maintenance
work described on a regular basis and to a professional standard.
Danger! Risk of electric shock!
Touching live connections may cause serious personal injury.
Always switch off all power supply lines
for the heat pump and all components involved before carrying out any
electrical installation or maintenance work.
Check that there is no voltage. Secure the power supply against being
switched back on.
9.3 Preparing for inspection and maintenance
9.3.1 Procuring spare parts
The original components of the product were also certified by the manufacturer
as part of the declaration of conformity. If you use other, non-certified or
unauthorised parts during maintenance or repair work, this may void the
conformity of the product and it will therefore no longer comply with the
applicable standards.
We strongly recommend that you use original spare parts from the manufacturer
as this guarantees fault-free and safe operation of the product. To receive
information about the available original spare parts, contact the contact
address provided on the reverse of these instructions.
If you require spare parts for maintenance or repair
work, use only the spare parts that are permitted for the product.
9.3.2 General inspection and maintenance information
Inspection
The inspection is intended to determine the actual condition of the respective
product and compare it with the target condition. This is done by measuring,
checking and observing.
Maintenance
Maintenance is required in order to eliminate any deviations between the
actual condition and the target condition. This is normally done by cleaning,
setting and, if necessary, replacing individual components that are subject to
wear.
9.3.3 Checking maintenance messages
If the symbol is shown in the display, the product requires maintenance work
or the product is in comfort protection mode.
To obtain further information, call up the Live Monitor.
( Page 28)
Carry out the maintenance work that is listed in the table.
Maintenance messages ( Page 35)
Conditions: Lhm. 37 is displayed
The product is in Comfort protection mode. The product has detected a
permanent fault and continues to run with restricted comfort.
If the temperature sensor for the building circuit outlet, environment circuit
inlet or environment circuit outlet fails, the product continues to run with
replacement values.
To determine which component is defective, read the
fault memory. ( Page 28)
0020250181_00 geoTHERM Installation and maintenance instructions
27
Troubleshooting
Note If a fault message is present, the product remains in comfort protection
mode after it is reset. After the product is reset, the fault message is
displayed first before the message Limp home mode (comfort protection) appears
again.
Check the component that is displayed and replace it.
9.4 Cleaning the product
Caution. Risk of material damage caused by unsuitable cleaning agents.
Do not use sprays, scouring agents, de-
tergents, solvents or cleaning agents that contain chlorine.
Clean the casing and operator control elements with a
damp cloth and a little solvent-free soap.
9.5 Checking and correcting the filling pressure of the heating installation
If the filling pressure falls below the minimum pressure, a fault message is
shown in the display.
Minimum heating water pressure: 0.05 MPa ( 0.50 bar)
Top up the water to start up the heat pump again. (See
section: Filling the system ( Page 18)).
If you notice frequent drops in pressure, determine and
eliminate the cause.
9.6 Checking and correcting the filling pressure in the brine circuit
If the filling pressure falls below the minimum pressure, the heat pump is
automatically shut down and a fault message is shown in the display.
Minimum brine fluid pressure: 0.05 MPa ( 0.50 bar)
Top up the brine fluid to start up the heat pump again.
(See section: Filling the brine circuit ( Page 18)). Brine fluid operating
pressure: 0.1 … 0.2 MPa (1.0
… 2.0 bar)
If you notice frequent drops in pressure, determine and
eliminate the cause.
9.7 Carrying out a restart and test operation
Warning. Risk of injury due to hot and cold components. The heat pump must
only be started up after all the casing sections have been installed.
Before starting up the unit, fit all of the
casing sections for the heat pump.
1. Start up the heat pump system.
2. Check that the heat pump system is working without any problems.
10 Troubleshooting
10.1 Troubleshooting 10.1.1 Checking the status codes 10.1.1.1 Calling the
Live Monitor Menu Live Monitor You can call up status codes in the heat
pump’s display
and these codes provide you with information about the current operating
status of the heat pump. Status codes ( Page 35)
10.1.1.2 Status code meanings The status codes provide you with information
about the current operating status of your product. If several operating
statuses occur at the same time, the applicable status codes are displayed
alternately, one after the other.
10.1.2 Querying the fault memory Menu Installer level Fault list The heat pump
has a fault memory. You can use this to query the last ten faults that
occurred in chronological order. If a DCF sensor is connected, the date on
which the fault occurred is also displayed. You can only call up fault lists
if faults have previously occurred.
Display views Number of faults that occurred The fault currently selected
with fault number F.xxx You can find a list of the sensor characteristic
values in the appendix. Sensor characteristics for the VR 10 external
temperature sensor ( Page 39) Sensor characteristics for the internal
temperature sensors ( Page 40) Sensor characteristic value for the VRC DCF
outdoor temperature sensor ( Page 41)
10.1.3 Resetting the fault memory 1. Press (Delete). 2. Confirm that you wish
to clear the fault memory by
pressing (OK).
10.1.4 Overview of fault codes You can find an overview of the fault codes in
the appendix. You can find a list of the surface-mounted sensor resistances in
the appendix.
10.1.5 Restarting the installation assistant You can restart the installation
assistant any time by calling it up manually in the menu.
28
Installation and maintenance instructions geoTHERM 0020250181_00
Replacing components 11
Menu Installer level Start inst. assistant
10.1.6 Using check programmes Menu Installer level Test menu Check programmes
You can use this function to start check programmes.
Note If the heat pump is in a fault state, you cannot start the check
programmes.
You can press the left-hand selection button (Cancel) at any time to end the
check programmes.
11 Replacing components
7. Ensure that water does not drip on live components (e.g. the electronics
box).
8. Use only new seals and O-rings.
11.1.2 Completing the replacement work 1. Attach the casing. ( Page 23) 2.
Attach the front casing. ( Page 24)
11.1.3 Replacing the PCB and/or the display
Danger! Risk of death from electric shock! Power supply terminals L and N
remain live even if the heat pump is switched off.
Isolate the heat pump from the power grid
by pulling out the mains plug.
11.1 Procuring spare parts
The original components of the product were also certified by the manufacturer
as part of the declaration of conformity. If you use other, non-certified or
unauthorised parts during maintenance or repair work, this may void the
conformity of the product and it will therefore no longer comply with the
applicable standards.
We strongly recommend that you use original spare parts from the manufacturer
as this guarantees fault-free and safe operation of the product. To receive
information about the available original spare parts, contact the contact
address provided on the reverse of these instructions.
If you require spare parts for maintenance or repair
work, use only the spare parts that are permitted for the product.
11.1.1 Preparing for replacement work
Danger! Risk of death from electric shock!
Power supply terminals L and N remain live even if the heat pump is switched
off.
Isolate the heat pump from the power grid
by pulling out the mains plug.
Caution. Risk of damage caused by incorrect repair work.
Using an incorrect replacement display may cause damage to the electronics.
Before replacing, check that the correct
replacement display is available.
Never use another replacement display.
Comply with the assembly and installation instructions
provided with the spare parts.
11.1.3.1 Replacing either the PCB or the display
1. Replace the PCB or display according to the assembly and installation
instructions supplied.
If you are replacing only one of the two compon-
ents (PCB or display), the parameterization functions automatically. When the
product is switched on, the new component adopts the previously set parameters
from the unreplaced component.
2. Plug the plug into the new PCB. When replacing the PCB
1. Decommission the heat pump.
Note When carrying out any repair work on the heat pump, make sure that you
observe the following instructions for your own safety and to avoid material
damage to the heat pump.
Note
Coding resistors are integrated into the plugs and these enable the unit type
to be detected.
2. Disconnect the heat pump from the power grid.
3. Remove the front casing as shown in the illustration. ( Page 15)
4. Remove the side casing. ( Page 15)
5. Close the service valves in the heating flow and in the heating return.
6. Drain the heat pump if you want to replace water-carrying components in
the heat pump.
0020250181_00 geoTHERM Installation and maintenance instructions
29
Decommissioning
11.1.3.2 Replacing the PCB and the display at the same time
Language 01 English
12 Decommissioning
12.1 Temporary decommissioning 12.1.1 Protecting the heat pump against frost
Observe the requirements for the installation site of the
heat pump ( Page 11).
Cancel
OK
1. Use the minus button
and the plus button
to select the required language, and con-
firm this by pressing the right-hand selection button
“OK”.
You then automatically access the installation as-
sistant.
2. Set the required values for the initial installation.
12.2 Permanently decommissioning
12.2.1 Recycling and disposal
Caution. Environmental hazard resulting from improper disposal.
Improper disposal of refrigerant can be harmful to the environment.
Ensure that refrigerant and brine fluid is
only disposed of by qualified competent persons.
11.1.4 Replacing the secondary PCB
1. Undo the fixing screw for the secondary PCB box. 2. Fold the secondary PCB
box downwards. 3. Undo the connection cable. 4. Release the secondary PCB from
the clips. 5. Insert the new secondary PCB and use the clips to se-
cure it in place. 6. Reconnect the connection cable to the secondary PCB.
11.1.5 Replacing pumps
Product Do not dispose of the product or any accessories in household waste.
Ensure that your old unit and any accessories are dis-
posed of properly.
Disposing of the product
If the product is identified with this symbol, it does not belong with the
household waste at the end of its useful life.
Instead, take the product to a collection point for recyc-
ling electrical and electronic devices.
For more information on where to take used electrical and electronic devices,
contact your town or district authorities, or a waste disposal company.
12.2.2 Disposing of the brine fluid
Danger! Risk of injury due to chemical burns!
1
The brine fluid ethylene glycol is harmful to health.
Avoid contact with the skin and eyes. Do not inhale or swallow. Always wear
gloves and protective
goggles.
Observe the safety data sheet that ac-
companies the brine fluid.
1. Remove the insulating material from the pipelines in the Ensure that the brine fluid is disposed of in compliance
area of the pump.
with local regulations, for example, at an appropriate
2. Undo the cap nuts (1) from the pump connections.
waste site or waste incineration plant.
3. Install the new pump with new seals.
For smaller volumes, contact your local disposal com-
4. Install new vapour-diffusion-tight insulating material
pany.
around the pipelines.
12.2.3 Arranging disposal of refrigerant
The product is filled with R410A refrigerant.
30
Installation and maintenance instructions geoTHERM 0020250181_00
Refrigerant must only be disposed of by a qualified com-
petent person.
13 Customer service
Customer service
0020250181_00 geoTHERM Installation and maintenance instructions
31
Appendix
Appendix A Heat pump schematic
S22
S8
P
T
A1 S1
T
S2 T
S14 T
P S18
HE2
A12 (230 V) & A13 (PWM) S10
T
Sensors & Switches: – 8 x T – 4 x P sensor – 1 x P switch – 1 x V flow rate
sensor
S11 T
Mesh filter
A1 A7 A10/ A11 A12/ A13 HE1 HE2 S1 S2 S3 S4
Compressor Electronic expansion valve Heating pump (relay and pulse-width modulation) Source pump (relay and pulse-width modulation) Condenser Evaporator Compressor inlet temperature sensor Compressor outlet temperature sensor High-pressure sensor High-pressure switch
P SW
S15
S4
S3
P
A7
S16
T
HE1
A10 (230 V) & A11 (PWM)
S13
P
T
Mesh filter
S17
S8
Source inlet temperature sensor
S10
Source outlet temperature sensor
S11
Temperature sensor of the electronic expansion
valve with HEX heat source
S13
Heating return temperature sensor
S14
Heating flow temperature sensor
S15
Heating circuit flow rate sensor
S16
Temperature sensor of the electronic expansion
valve with HEX heating
S17
Heating circuit pressure sensor
S18
Heat source pressure sensor
S22
Low-pressure sensor
B Installer level overview
Setting level
Installer level Enter code
Values
Unit
Min.
Max.
00
99
Increment, select
Default setting Setting
1 (competent person
00
code 17)
Installer level List of faults F.514 F.7432)
Deleting
Installer level Test menu Statistics
Compressor hours
Current value
h
Compressor starts
Current value
Build. pump hours
Current value
h
Build. pump starts
Current value
Environm. pump hours
Current value
h
- Can only work in conjunction with the VWZ ZK accessory. 2) Fault lists (section 9.1) are only available, and can only be deleted, if faults have occurred.
32
Installation and maintenance instructions geoTHERM 0020250181_00
Setting level
Environm. pump starts Cooling mixer steps EEV steps VUV DHW switchings
Values
Unit
Min.
Max.
Current value
Current value
Current value
Current value
Increment, select
Installer level Test menu Check programmes P.01 Heating mode P.02 Cooling mode P.03 Hot water handling P.05 Purge building circuit P.06 Purge environment circuit P.07 Purge building and environment circuit
Select Select Select Select Select Select
Installer level Test menu Sensor/actuator test
T.01 Building circuit pump power 0
100
%
5, off
T.14 Env. circuit pump power
0
100
%
5, off
T.15 Cooling mixer position
0
100
%
5
T.33 Position of the electronic
0
100
%
5
expansion valve
T.45 Fault outlet
On, Off
T.48 Circulation pump
On, Off
T.49 Cooling relay active
On, Off
T.79 Flow temperature
-40.0
150.0
0.1
T.81 Return temperature
-40.0
150.0
0.1
T.82 Building circuit: Pressure
0
4.5
bar
0.1
T.83 Building circuit: Flow rate 0
1400
l/h
1
T.97 Environment circuit: Inlet
-40.0
150.0
0.1
temperature
T.98 Environment circuit: Outlet -40.0
150.0
0.1
temperature
T.121 Compressor outlet temper- -25.0
150.0
0.1
ature
T.122 Compressor inlet temper- -40.0
150.0
0.1
ature
T.125 EEV environment circuit
-40.0
150.0
0.1
temperature
T.126 EEV building circuit tem- -40.0
150.0
0.1
perature
T.127 High pressure
0.0
51.0
bar (abs)
0.1
T.128 Condensation temperature -52.0
70.0
0.1
T.129 Low pressure
0.0
22.0
bar (abs)
0.1
T.130 Evaporation temperature -52.0
70.0
0.1
T.131 Superheating target value 0.0
16.0
0.1
T.132 Superheating actual value 0.0
16.0
0.1
T.133 Subcooling actual value
0.0
99.0
0.1
T.134 High-pressure switch
Open, closed
T.146 Outside temperature
-60.0
45.0
0.1
- Can only work in conjunction with the VWZ ZK accessory. 2) Fault lists (section 9.1) are only available, and can only be deleted, if faults have occurred.
Appendix
Default setting Setting
Closed
0020250181_00 geoTHERM Installation and maintenance instructions
33
Appendix
Setting level T.147 DCF status
Values
Unit
Min.
Max.
Increment, select
No DCF signal Validate DCF signal Valid DCF signal
Default setting Setting
Installer level Configuration Language
Current language
Contact data Compressor starts at Comp. hysteresis Max. rem. feed head Conf. heat. build. pump Conf. cool. build. pump Conf. DHW build. pump Reset anti- cycl. time Boiler supp. set p.1) Enviro. pump set p. Freeze protection Enable emergency mode Software version
Phone number
-999
0
3
15
200
700
1
100
1
100
1
100
0
120
300
1300
29
100
-14
5
°min mbar % % % min l/h %
Current value for the main PCB (HMU xxxx) and the display (AI xxxx)
01 Deutsch 02 English 03 Français 06 Nederlands 16 Norsk 18 Cestina 20
Slovenscina 27 Suomi 0-9 1 1 1 1, auto 1, auto 1, auto 1 20
1 1 On, Off
02 English
-60 7 700 Auto Auto Auto 0 1000 75 -7 Off
Installer level Resets Switch-on delay Statistics Factory settings
Yes, No
No
Yes, No
No
Yes, No
No
Installer level Start inst. assistant
Language
01 Deutsch 02 English 03 Français 06 Nederlands 16 Norsk 18 Cestina 20 Slovenscina 27 Suomi
Freeze protection
-13
4
1
Check programme
P.05 Purge building circuit
P.06 Purge environment circuit
P.07 Purge environment and building circuit
Contact data
Phone number
0-9
- Can only work in conjunction with the VWZ ZK accessory. 2) Fault lists (section 9.1) are only available, and can only be deleted, if faults have occurred.
02 English -7
34
Installation and maintenance instructions geoTHERM 0020250181_00
Appendix
Setting level
Values
Unit
Increment, select
Min.
Max.
End the installation assistant?
Yes, back
- Can only work in conjunction with the VWZ ZK accessory. 2) Fault lists (section 9.1) are only available, and can only be deleted, if faults have occurred.
Default setting Setting
Maintenance messages
Code M.32
M.34
Meaning Building circuit: Pressure low
Cause
Pressure loss in the building circuit due to leaks or air pockets
Building circuit pressure sensor is defective
Environment circuit: Pressure low
Pressure loss in the environment circuit due to leaks or air pockets
Environment circuit pressure sensor defective
Remedy
Check the building circuit for leaks, top up with heating water and purge
Check the plug contact on the PCB and on the cable harness; check that the
pressure sensor is working correctly and, if required, replace the pressure
sensor
Check the environment circuit for leaks, top up with medium (brine/water),
and purge
Check the plug contact on the PCB and on the cable harness; check that the
pressure sensor is working correctly and, if required, replace the pressure
sensor
D Status codes
Code Meaning Heat pump system S.34 Heating mode: Frost protection S.91 Service
message: Demo mode S.100 Standby S.101 Heating: Compressor switched off S.102
Heating: Compressor blocked S.103 Heating: Flow S.104 Heating: Compressor
active S.107 Heating: Overrun S.118 Cooling: Flow S.119 Cooling: Mixer active
S.131 Hot water: Compressor shutdown S.132 Hot water: Compressor blocked S.133
Hot water: Flow S.134 Hot water: Compressor active S.137 Hot water: Overrun
General S.201 Check program: Purging of env. circuit active S.202 Check
program: Purging of building circuit active S.203 Actuator test active
Communication S.211 Connection error: Display not detected S.212 Connection
error: Control not detected
0020250181_00 geoTHERM Installation and maintenance instructions
35
Appendix
Code Meaning Environment circuit
S.242 Environment circuit: Outlet temperature too low S.246 Environment
circuit: Pressure too low S.247 Env. circuit: Fault contact: Pump open
Building circuit
S.272 Building circuit: Remaining feed heads limit active S.273 Building
circuit: Flow temperature too low S.274 Building circuit: Pressure too low
S.275 Building circuit: Flow rate too low S.276 Building cir.: Lockout contact
S20 opened Refrigeration circuit
S.302 High pressure switch opened S.303 Compressor outlet temperature too high
S.304 Evaporation temperature too low S.305 Condensation temperature too low
S.306 Evaporation temperature too high S.308 Condensation temperature too high
S.311 Environment cir. inlet temperature too low S.312 Building circuit inlet
Return temperature too low S.313 Environment cir. inlet temperature too high
S.314 Building circuit inlet Return temperature too high S.315 Compressor
circuit breaker open S.316 WHB support active S.240 Oil temperature too low
E Fault codes
Code Meaning F.042 Sensor fault: Coding resistor 1 F.042 Sensor fault: Coding
resistor 2 F.042 Sensor fault: Coding resistor 3 F.070 Invalid Device Specific
Number
F.514 Temp. sensor fault: Compressor inlet F.517 Temp. sensor fault:
Compressor outlet F.519 Sensor fault: Building circuit return temp. F.520
Temp. sensor fault: Building circuit flow F.532 Building circuit: Flow rate
too low
Cause Sensor not connected or sensor in-
put has short-circuited
Replacing the control PCB and display PCB
Sensor not connected or sensor input has short-circuited
Remedy
Check and, if required, replace the sensor (see sensor characteristic values
in the appendix)
Replace the cable harness
Checking coding resistors 1 and 2
Disconnecting the product from the power supply and switching it back on
again
Check and, if required, replace the sensor (see sensor characteristic values
in the appendix)
Replace the cable harness
Stopcock was not opened
Building circuit pump defective
All consumers in the heating system are closed
Flow rate is too low for recording with the volume flow sensor (< 120 l/h)
Check the stopcocks and thermostatic valves
Ensure that there is a minimum flow rate of 150 l/h
Check that the building circuit pump functions correctly
36
Installation and maintenance instructions geoTHERM 0020250181_00
Appendix
Code Meaning F.546 Sensor fault: High pressure F.583 Building circuit: Flow
temperature too low
F.585 Sensor fault: Building EEV temp F.685 Connection error: Control not
detected F.700 Temp. sensor fault: EEV environment cir. F.701 Temp. sensor
fault: Environ. circuit inlet F.702 Temp. sensor fault: Environment cir. out
F.703 Sensor fault: Low pressure F.704 Sensor fault: Building cir. pressure
F.705 Sensor fault: Enviro. cir. pressure F.706 Sensor fault: Building flow
rate F.710 Environment circuit: Outlet temperature too
low
F.714 Environment circuit: Pressure too low
F.715 Environment circuit: Fault contact, pump open
Cause
Remedy
Sensor not connected or sensor input has short-circuited
Check and, if required, replace the sensor (see sensor characteristic values
in the appendix)
Replace the cable harness
The temperature sensor in the flow is Checking the building circuit’s
defective
flow rate
Air in the building circuit
Check the quality of the plug contact on the PCB and on the cable harness
Check that the sensor is working correctly (measure the resistance using the sensor characteristic values, see appendix)
Replace the sensor
Purging the building circuit
Sensor not connected or sensor input has short-circuited
Check and, if required, replace the sensor (see sensor characteristic values
in the appendix)
Replace the cable harness
The VRC 700 control was previously detected but the connection is broken
Check the eBUS connection to the VRC 700 control
Sensor not connected or sensor input has short-circuited
Check and, if required, replace the sensor (see sensor characteristic values
in the appendix)
Replace the cable harness
Environment circuit pump defective
Temperature sensor for environment circuit outlet defective
Volume flow too low in the environment circuit
Air in the environment circuit
Check the environment circuit flow rate
Check the quality of the plug contact on the PCB and on the cable harness
Check that the sensor is working correctly (measure the resistance using the
sensor characteristic values in the appendix)
Replace the sensor
Check the volume flow of the environment circuit pump (optimum spread of 3
K)
Purging the environment circuit
Pressure drop in the environment
Check the environment circuit for
circuit due to leakages or air pockets
leaks
Environment circuit pressure sensor Top up the medium
defective
(brine/water), purge
Check the quality of the plug contact on the PCB and on the cable harness
Check that the pressure sensor works correctly
Replace the pressure sensor
The electronics of the high-efficiency Switch the heat pump off for at
pump has detected a fault (e. g. dry
least 30 seconds (no current)
running, blockage, overvoltage, undervoltage) and switched the pump off as a securing measure.
Check the quality of the plug contact on the PCB
Check that the pump functions
correctly
Purging the environment circuit
0020250181_00 geoTHERM Installation and maintenance instructions
37
Appendix
Code Meaning F.723 Building circuit: Pressure too low
F.726 Compressor protector switch opened
F.730 Low pressure switch opened F.731 High pressure switch opened
F.732 Compressor outlet temperature too high
F.733 Evaporation temperature too low
F.734 Condensation temperature too low
Cause
Remedy
Pressure drop in the building circuit due to leakages or air pockets
Building circuit pressure sensor defective
Check the building circuit for leaks
Top up with water, purge
Check the quality of the plug contact on the PCB and on the cable harness
Check that the pressure sensor works correctly
Replace the pressure sensor
Compressor overheated, e.g. as
Environmental temperatures fall
a result of operating outside of its
below 40 °C
application limits
Check the pressure difference
Maximum environmental temperature
during the start-up attempt
of 40 °C exceeded for the heat pump
Compressor blocked due to mechanical defect
Compressor blocked because the pressure difference is too high when switched on (> 3 bar)
Low-pressure switch input not bridged (X22-8 to X22-11)
Replace the cable harness
Refrigerant pressure too high. The integrated high-pressure switch tripped
at 41.5 bar (g)
Insufficient energy output via the relevant capacitors
Purging the building circuit
Insufficient volume flow as a result of closing individual room controls in
an underfloor heating system
Check the existing dirt filter for penetrability
Refrigerant flow rate too low (e.g. electronic expansion valve defective,
filter blocked)
The compressor outlet temperature is
Check the low-pressure sensor,
above 115 °C:
compressor inlet sensor and
Application limits exceeded
compressor outlet sensor Check the EEV (does the EEV
EEV does not work or does not open
move to the limit stop? Use the
correctly
sensor/actuator test)
Refrigerant volume too low
Check the refrigerant volume
(700 g)
Carry out a leak-tightness test
No flow rate in the environment circuit (heating mode)
Energy input too low in the environment circuit (heating mode) or building
circuit (cooling mode)
Check the flow rate in the environment circuit
Check the dimensioning of the environment circuit (heating mode)
If the building circuit contains thermostatic valves, check that they are
suitable for cooling mode (cooling mode)
Check the low-pressure sensor and compressor inlet sensor
Temperature in the building circuit (heating mode) or environment circuit
(cooling mode) too low for compressor operation
Refrigerant volume too low
Check the EEV (does the EEV move to the limit stop? Use the sensor/actuator
test)
Check the compressor inlet sensor, high-pressure sensor and low-pressure
sensor
Check the refrigerant volume (700 g)
Leak-tightness test
38
Installation and maintenance instructions geoTHERM 0020250181_00
Appendix
Code Meaning F.735 Evaporation temperature too high
F.740 Environment cir. inlet temperature too low F.741 Building circuit inlet
Return temperature too
low F.742 Environment cir. inlet temperature too high F.743 Building circuit
inlet Return temperature too
high
Cause Temperature in the environment cir-
cuit (heating mode) or building circuit (cooling mode) too high for compressor
operation Feed-in of external heat into the environment circuit
Inlet temperature in the environment circuit too low for the compressor to
start
Heating: VWS environment circuit inlet tem-
perature < -10 °C Return temperature in the building
circuit too low for the compressor to start Heating: Return temperature < 5
°C Cooling: Return temperature < 7 °C Inlet temperature in the environment
circuit too high for the compressor to start Heating: Environment circuit
inlet temp. > 25 °C
Return temperature in the building circuit too high for the compressor to
start
Heating: Return temperature > 55 °C Cooling: Return temperature > 35 °C
Remedy Reduce or stop the external heat
that is entering Check the de-icer (does it heat
up even though it is “Off” in the sensor/actuator test?) Check the EEV (does
the EEV move to the limit stop? Use the sensor/actuator test) Check the
compressor inlet sensor and low-pressure sensor Check the dimensioning of
the environment circuit for VWS Check the sensors
Check the sensors Checking the cooling mixer
Check the environment circuit Check the sensors Checking the environment
circuit
pump Checking the cooling mixer Checking the isolation valve
in the environment circuit (if present) Check the sensors Checking the
heating pump Checking the non-return flap (if present) Checking the 2-zone
set (if present)
F Sensor characteristics for the VR 10 external temperature sensor
Temperature (°C) -40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20
Resistance (ohms) 87879 63774 46747 34599 25848 19484 14814 11358 8778 6836 5363 4238 3372
0020250181_00 geoTHERM Installation and maintenance instructions
39
Appendix
Temperature (°C) 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155
Resistance (ohms) 2700 2176 1764 1439 1180 973 807 672 562 473 400 339 289 247 212 183 158 137 120 104 92 81 71 63 56 50 44
G Sensor characteristics for the internal temperature sensors
Temperature (°C) -40 -35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
Resistance (ohms) 332094 239900 175200 129287 96358 72500 55046 42157 32554 25339 19872 15698 12488 10000 8059,1 6534,7 5329,9 4371,7
40
Installation and maintenance instructions geoTHERM 0020250181_00
Appendix
Temperature (°C) 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150
Resistance (ohms) 3605,3 2988,7 2489,9 2084,4 1753,0 1480,9 1256,4 1070,3 915,5 786,4 678,1 586,8 509,5 443,9 388,1 340,3 299,3 264,0 233,6 207,2 184,3
H Sensor characteristic value for the VRC DCF outdoor temperature sensor
Temperature (°C) -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40
Resistance (ohms) 2167 2067 1976 1862 1745 1619 1494 1387 1246 1128 1020 920 831 740
0020250181_00 geoTHERM Installation and maintenance instructions
41
Appendix
I Technical data
Technical data General
Flow/return heating connections, boiler side Boiler-side flow/return heat
source connections Product dimensions, width Product dimensions, height
Product dimensions, depth Weight without packaging Weight with packaging
Weight when ready for operation Heating circuit/compressor rated voltage
Control circuit rated voltage Fuse type B, slow-blow Optional on-site
residual-current circuit breaker In-rush current without in-rush current
limiter Min. electrical power consumption for B-10/W20 Max. electrical power
consumption for B20/W55 Max. electrical power consumption in continuous
operation IP rating in accordance with EN 60529 Inner sound power level (LWi)
in accordance with EN 12102; heating mode at B0/W35 Inner sound power level
(LWi) in accordance with EN 12102; heating mode at B0/W45 Inner sound power
level (LWi) in accordance with EN 12102; heating mode at B0/W55 Permissible
ambient temperature Installation room at a refrigerant volume of 0.70 kg
Installation site
VWS 36/4.1 230V 22 mm diameter 22 mm diameter
440 mm 720 mm 435 mm
59 kg 67 kg 66 kg 1/N/PE 230 V / 50 Hz 1/N/PE 230 V / 50 Hz 16 A RCB type A or
RCB type B 23 A 0.6 kW 1 kW 4.7 A IP 20 41.1 dB(A) 43.6 dB(A) 44.7 dB(A) 7 …
40 1.6 m³ Interior/dry
Technical data Source circuit
Min. brine fluid operating pressure
Max. brine fluid operating pressure
Nominal volume flow T 3 K for B0/W35 Min. source inlet temperature (hot brine)
in heating mode Max. source inlet temperature (hot brine) in heating mode
Brine content of the brine circuit in the heat pump Remaining feed head at
max. T 3 K B0/W35 Electrical power consumption of the brine pump at B0/W35 T 3
K with an external pressure loss of 250 mbar in the source circuit Electrical
power consumption of the brine pump Pump type Materials
Brine fluid type
VWS 36/4.1 230V 0.05 MPa (0.50 bar) 0.3 MPa (3.0 bar) 600 l/h -10 20 3.5 l 590 mbar 21 W
3 … 70 W
High-efficiency pump
Cu
CuZn alloy
Stainless steel
EPDM
Brass
Fe
Ethylene glycol 30% vol.
42
Installation and maintenance instructions geoTHERM 0020250181_00
Appendix
Technical data Heating circuit
Minimum operating pressure
Maximum operating pressure
Min. heating mode flow temperature Max. heating mode flow temperature Min.
cooling mode flow temperature Heating circuit water contents in the heat pump
Nominal volume flow at B0 T 3 K / W35 T 5 K Nominal volume flow at B0 T 3 K /
W55 T 8 K Max. remaining feed head B0 T 3 K / W35 T 5 K Max. remaining feed
head at B0 T 3 K / W55 T 8 K Electrical power consumption of the heating pump
Electrical power consumption of the heating pump at B0/W35 T 5 K for a 250
mbar external pressure loss in the heating circuit Permissible heating water
condition
Pump type Materials
VWS 36/4.1 230V 0.05 MPa (0.50 bar) 0.3 MPa (3.0 bar) 20 60 16 3.5 l 470 l 250 l 400 mbar 680 mbar 4 … 63 W 21 W
Only add permitted frost or corrosion protection agents to the heating water
if these are approved in the
installation instructions. Soften the heating water at water hardnesses from
3.0 mmol/l (16.8° dH) according
to Directive VDI 2035 sheet 1.
High-efficiency pump
Cu
CuZn alloy
Stainless steel
EPDM
Brass
Fe
Technical data Refrigeration circuit
Refrigerant type Refrigerant content of the refrigerant circuit in the heat
pump Global warming potential (GWP) in accordance with regulation (EU) no.
517/2014 CO equivalent Expansion valve design Permissible operating pressure
(relative)
Compressor type Oil type Oil level
VWS 36/4.1 230V R410A 0.7 kg 2088 1.46 t
Electronic 4.15 MPa (41.50 bar) Rotary piston
FV50S 0.3 l
Technical data Heat pump system performance data The following performance data is applicable to new products with clean heat exchangers.
Heating output B0/W35 T 5 K Power consumption B0/W35 T 5 K Effective power consumption B0/W35 T 5 K Coefficient of performance EN 14511 B0/W35 T 5 K Heating output B0/W45 Power consumption B0/W45 Effective power consumption B0/W45 T 8 K
VWS 36/4.1 230V 2.50 kW 0.70 kW 0.63 kW 4.00 2.30 kW 0.8 kW 0.74 kW
0020250181_00 geoTHERM Installation and maintenance instructions
43
Appendix
Coefficient of performance EN 14511 B0/W45 Heating output B0/W55 T 8 K Power consumption B0/W55 T 8 K Effective power consumption B0/W55 T 8 K Coefficient of performance EN 14511 B0/W55 T 8 K Cooling output B10/W18(22), passive
VWS 36/4.1 230V 3.10
2.20 kW 0.90 kW 0.88 kW
2.50 5 kW
Application limits for the heat pump: Heating (heat source = brine) At the
same volume flow rates in the heating circuit (T 5 K or T 8 K) and the brine
circuit (T 3 K) as for the nominal
heat output test under standard nominal conditions. Operation of the pump
outside the application limits results in the heat pump being switched off by
the internal control and safety devices. Application limits for the heat
pump: Heating: B-10/W20 B-10/W55 B-3/W60 B20/W60 B20/W20 To be
able to achieve the B-10/W20 and B-10/W55 operating limits, you must change
the freeze protection in the
configuration from the factory setting to -13 °C.
J Basic hydraulic diagram
J.1 Basic hydraulic diagram 0020232108
2
Heat pump
3e
Circulation pump
44
5e
Hydraulic tower
8b
Potable water expansion relief valve
Installation and maintenance instructions geoTHERM 0020250181_00
8c
Safety group drinking water connection
8e
Heating diaphragm expansion vessel
8f
Diaphragm expansion vessel potable water
9a
Single-room temperature control valve (thermo-
static/motorised)
9d
Bypass valve
J.2 Basic hydraulic diagram 0020235577
Appendix
9h
Filling/draining cock
9j
Tamper-proof capped valve
12
System control
12k
Limit thermostat
12m
Outdoor temperature sensor
1c
Heating/domestic hot water back-up boiler
9d
Bypass valve
2
Heat pump
9h
Filling/draining cock
3e
Circulation pump
9j
Tamper-proof capped valve
5
Monovalent domestic hot water cylinder
10c
Non-return valve
8b
Potable water expansion relief valve
12
System control
8c
Safety group drinking water connection
12k
Limit thermostat
8e
Heating diaphragm expansion vessel
12m
Outdoor temperature sensor
8f
Diaphragm expansion vessel potable water
DHW
Cylinder temperature sensor
9a
Single-room temperature control valve (thermo-
static/motorised)
0020250181_00 geoTHERM Installation and maintenance instructions
45
Appendix
J.3 Basic hydraulic diagram 0020235580
1c
Heating/domestic hot water back-up boiler
2
Heat pump
3e
Circulation pump
5
Monovalent domestic hot water cylinder
8b
Potable water expansion relief valve
8c
Safety group drinking water connection
8e
Heating diaphragm expansion vessel
8f
Diaphragm expansion vessel potable water
9d
Bypass valve
9e
9h 9j 10c 12 12b 12m DHW MA
Domestic hot water generation prioritising diverter valve Filling/draining cock Tamper-proof capped valve Non-return valve System control Remote heat pump expansion module Outdoor temperature sensor Cylinder temperature sensor Multi-function output
46
Installation and maintenance instructions geoTHERM 0020250181_00
J.4 Basic hydraulic diagram 0020249867
Appendix
2
Heat pump
9h
Filling/draining cock
3e
Circulation pump
9j
Tamper-proof capped valve
5
Monovalent domestic hot water cylinder
10c
Non-return valve
8b
Potable water expansion relief valve
12
System control
8c
Safety group drinking water connection
12b
Remote heat pump expansion module
8e
Heating diaphragm expansion vessel
12m
Outdoor temperature sensor
8f
Diaphragm expansion vessel potable water
DHW
Cylinder temperature sensor
9d
Bypass valve
MA
Multi-function output
9e
Domestic hot water generation prioritising diverter
valve
0020250181_00 geoTHERM Installation and maintenance instructions
47
Appendix
J.5 Basic hydraulic diagram 0020185684
1
Heat generator
9c
Flow regulator valve
2
Heat pump
9h
Filling/draining cock
3e
Circulation pump
9j
Tamper-proof capped valve
5
Monovalent domestic hot water cylinder
10c
Non-return valve
8a
Expansion relief valve
10e
Line strainer with magnetite separator
8b
Potable water expansion relief valve
12
System control
8c
Safety group drinking water connection
12g
eBUS bus coupler
8e
Heating diaphragm expansion vessel
12k
Limit thermostat
8f
Diaphragm expansion vessel potable water
12m
Outdoor temperature sensor
9a
Single-room temperature control valve (thermo-
DHW
Cylinder temperature sensor
static/motorised)
Either the heat pump or the gas-fired boiler are active in heating mode. It is not possible to operate the units in parallel. The domestic hot water is only generated by the gas-fired boiler.
Connect the underfloor heating circuits directly to the heat pump.
Connect two limit thermostats to guarantee the underfloor heating protection
function for the heat pump and the gas-fired boiler.
Ensure that a minimum circulation water volume (40% of the nominal volume
flow) is guaranteed.
Install one of the supplied non-return flaps in the flow of both the heat
pump and the gas-fired boiler. The flow direction is from the product towards
the heating installation; the backflow to the product is blocked
If you have installed a low loss header between the heat pump and the
heating installation, the VF2 system sensor in the flow of the low loss header
must be attached to the heating installation.
Install the control in the living room.
48
Installation and maintenance instructions geoTHERM 0020250181_00
J.6 Basic hydraulic diagram 0020180635
Appendix
1
Heat generator
9c
Flow regulator valve
2
Heat pump
9d
Bypass valve
3e
Circulation pump
9h
Filling/draining cock
5
Monovalent domestic hot water cylinder
9j
Tamper-proof capped valve
7i
2-zone module
9k
3-port mixing valve
8a
Expansion relief valve
10c
Non-return valve
8b
Potable water expansion relief valve
12
System control
8c
Safety group drinking water connection
12a
Remote control unit
8e
Heating diaphragm expansion vessel
12d
Expansion/wiring centre
8f
Diaphragm expansion vessel potable water
12g
eBUS bus coupler
9a
Single-room temperature control valve (thermo-
12k
Limit thermostat
static/motorised)
9b
Zone valve
12m
Outdoor temperature sensor
Using a 2-zone set and the appropriate information in the VRC 700 system
control also makes the parallel heating mode possible for parallel operation
of different temperature levels in the heating system with the different heat
generators.
For the parallel heating mode, the 2-zone kit (Vaillant accessory) must be
installed. The heat pump, the gas-fired boiler and the required heating
circuits are connected to the 2-zone kit. When using a 2-zone kit (Vaillant
accessory), the two non-return flaps are not required.
Connect two limit thermostats to guarantee the underfloor heating protection
function for the heat pump and the gas-fired boiler
Ensure that a minimum circulation water volume (40% of the nominal volume
flow) is guaranteed. Install the control in the living room.
0020250181_00 geoTHERM Installation and maintenance instructions
49
Appendix
J.7 Basic hydraulic diagram 0020235626
1
Heat generator
9j
Tamper-proof capped valve
2
Heat pump
9k
3-port mixing valve
3e
Circulation pump
10c
Non-return valve
3f
Heating pump
10e
Line strainer with magnetite separator
5
Monovalent domestic hot water cylinder
12
System control
7f
Decoupler module
12a
Remote control unit
8b
Potable water expansion relief valve
12d
Expansion/wiring centre
8c
Safety group drinking water connection
12g
eBUS bus coupler
8e
Heating diaphragm expansion vessel
12k
Limit thermostat
8f
Diaphragm expansion vessel potable water
12m
Outdoor temperature sensor
9a
Single-room temperature control valve (thermo-
DHW
Cylinder temperature sensor
static/motorised)
9h
Filling/draining cock
FS
Flow temperature sensor
SysFlow Cylinder temperature sensor
50
Installation and maintenance instructions geoTHERM 0020250181_00
K Wiring diagrams
K.1 Wiring diagram 0020232108
Appendix
2
Heat pump
3e
Circulation pump
5c
Combi cylinder (tank in tank)
12
System control
12k
Limit thermostat
12m
Outdoor temperature sensor
0020250181_00 geoTHERM Installation and maintenance instructions
51
Appendix
K.2 Wiring diagram 0020235577
1c
Heating/domestic hot water back-up boiler
2
Heat pump
3e
Circulation pump
12
System control
12k 12m DHW
Limit thermostat Outdoor temperature sensor Cylinder temperature sensor
52
Installation and maintenance instructions geoTHERM 0020250181_00
K.3 Wiring diagram 0020235580
Appendix
1c
Heating/domestic hot water back-up boiler
12
System control
2
Heat pump
12b
Remote heat pump expansion module
3e
Circulation pump
12m
Outdoor temperature sensor
9e
Domestic hot water generation prioritising diverter
DHW
Cylinder temperature sensor
valve
0020250181_00 geoTHERM Installation and maintenance instructions
53
Appendix
K.4 Wiring diagram 0020249867
2
Heat pump
12
System control
3e
Circulation pump
12b
Remote heat pump expansion module
9e
Domestic hot water generation prioritising diverter
12m
Outdoor temperature sensor
valve
DHW
Cylinder temperature sensor
54
Installation and maintenance instructions geoTHERM 0020250181_00
K.5 Wiring diagram 0020185684
Appendix
1
Heat generator
2
Heat pump
3e
Circulation pump
12
System control
12g 12k 12m DHW
eBUS bus coupler Limit thermostat Outdoor temperature sensor Cylinder temperature sensor
0020250181_00 geoTHERM Installation and maintenance instructions
55
Appendix
K.6 Wiring diagram 0020180635
1
Heat generator
2
Heat pump
3e
Circulation pump
5
Monovalent domestic hot water cylinder
7i
2-zone module
9b
Zone valve
9k
3-port mixing valve
12
System control
12d
Expansion/wiring centre
12g
eBUS bus coupler
12k
Limit thermostat
12m
Outdoor temperature sensor
FS
Flow temperature sensor/swimming pool sensor
56
Installation and maintenance instructions geoTHERM 0020250181_00
K.7 Wiring diagram 0020235626
Appendix
1
Heat generator
2
Heat pump
3e
Circulation pump
3f
Heating pump
9k
3-port mixing valve
12
System control
12a
Remote control unit
12d 12g 12m DHW FS SysFlow
Expansion/wiring centre eBUS bus coupler Outdoor temperature sensor Cylinder temperature sensor Flow temperature sensor/swimming pool sensor System temperature sensor
0020250181_00 geoTHERM Installation and maintenance instructions
57
Appendix
L Commissioning Checklist
Applicability: Great Britain
Benchmark Commissioning and Servicing Section
It is a requirement that the boiler is installed and commissioned to the
completed in full.
© Heating and Hotwater Industry Council (HHIC)
58
Installation and maintenance instructions geoTHERM 0020250181_00
Appendix
GROUND SOURCE HEAT PUMP COMMISSIONING CHECKLIST
This Commissioning Checklist is to be completed in full by the competent person who commissioned the heat pump and associated equipment as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission this equipment to the manufacturer’s instructions may invalidate the warranty but does not affect statutory rights.
Customer name: Address: Heat Pump Make and Model Heat Pump Serial Number
Commissioned by (PRINT NAME): Company name: Company address:
%XLOGLQJ5HJXODWLRQV1RWL¿FDWLRQ1XPEHULIDSSOLFDEOH>@
Telephone number:
&HUWL¿HG2SHUDWLYH5HJ1R>@ Telephone number: Commissioning date:
CONTROLS – SYSTEM AND HEAT PUMP (tick the appropriate boxes)
Time and temperature control to heating
Room thermostat and programmer/timer Load/weather compensation
Time and temperature control to hot water
Cylinder thermostat and programmer/timer
+HDWLQJ]RQHYDOYHVLQFOXGLQJXQGHUÀRRUORRSV
Fitted
Hot water zone valves
Fitted
Thermostatic radiator valves
Fitted
+HDW3XPS6DIHW,QWHUORFN>@
Built In
2XWGRRU6HQVRU
Fitted
Automatic bypass to system
Fitted
Buffer Vessel Fitted
Yes
No
If YES
Programmable Roomstat
2SWLPXPVWDUWFRQWURO
Combined with Heat pump main controls
Not required
Not required
Not required
Provided
Not required
Not required
Volume:
Litres
ALL SYSTEMS 7KHKHDWLQJVVWHPKDVEHHQ¿OOHGDQGSUHVVXUHWHVWHG ([SDQVLRQYHVVHOIRUKHDWLQJLVVL]HG¿WWHG FKDUJHGLQDFFRUGDQFHZLWKPDQXIDFWXUHU¶VLQVWUXFWLRQV 7KHKHDWSXPSLV¿WWHGRQDVROLGVWDEOHVXUIDFHFDSDEOHRIWDNLQJLWVZHLJKW 7KHVVWHPKDVEHHQÀXVKHGDQGFOHDQHGLQDFFRUGDQFHZLWK%6DQGKHDWSXPSPDQXIDFWXUHU¶VLQVWUXFWLRQV What system cleaner was used? What inhibitor was used? Are all exposed external pipeworks insulated?
Quantity
Yes Yes Yes Yes
litres Yes
BORE HOLE/GROUND LOOPS
Bore Hole
Ground Loop
Length/Depth
7KHJURXQGORRSVERUHKROHSLSHVKDYHEHHQ¿OOHGDQGSUHVVXUHWHVWHGLQDFFRUGDQFHZLWKUHOHYDQW%ULWLVK6WDQGDUGV
,IPRUHWKDQRQHFROOHFWRUKDVEHHQXVHGKDVWKHVVWHPEHHQKGUDXOLFDOOEDODQFHG)ORZEDODQFLQJUHJXODWLQJYDOYHV¿WWHG DGMXVWHG”
Has the system been vented/de-aired?
$UHVVWHP¿OWHUV¿WWHG FOHDQ”
Is the system topped up to the correct level?
:DVWKHVVWHPFOHDQHG ÀXVKHGSULRUWRXVH”
Are isolating valves in their correct position
What system cleaner was used?
Qty
What antifreeze was used?
Qty
What temperature will the antifreeze protect to?
What inhibitor was used (if not included in Antifreeze)?
Qty
5HFRUGLQFRPLQJFROOHFWRUÀXLGWHPSHUDWXUH
5HFRUGRXWJRLQJFROOHFWRUÀXLGWHPSHUDWXUH
m Yes Yes Yes Yes Yes Yes Yes litres litres °C litres °C °C
CENTRAL HEATING MODE Measure and Record
Heating Flow Temperature
°C
Heating Return Temperature
°C
DOMESTIC HOT WATER MODE Measure and Record: Is the heat pump connected to a hot water cylinder? Hot water has been checked at all outlets
Unvented
Vented
Thermal Store
Yes
+DYH7KHUPRVWDWLF%OHQGLQJ9DOYHVEHHQ¿WWHG”
Yes
Not Connected Not required
ADDITIONAL SYSTEM INFORMATON Additional heat sources connected:
Gas Boiler
2LO%RLOHU
Electric Heater
Solar Thermal
2WKHU
ALL INSTALLATIONS
The heating, hot water and ventilation systems complies with the appropriate Building Regulations
Yes
All electrical work complies with the appropriate Regulations
The heat pump and associated products have been installed and commissioned in accordance with the manufacturer’s instructions
Yes
The operation of the heat pump and system controls have been demonstrated to the customer
Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer
Yes
Commissioning Engineer’s Signature Customer’s Signature 7RFRQ¿UPVDWLVIDFWRUGHPRQVWUDWLRQDQGUHFHLSWRIPDQXIDFWXUHU¶VOLWHUDWXUH
1RWHV>@,QVWDOOHUVVKRXOGEHPHPEHUVRIDQDSSURSULDWH&RPSHWHQW3HUVRQV6FKHPH>@$OOLQVWDOODWLRQVLQ(QJODQGDQG
:DOHVPXVWEHQRWL¿HGWR/RFDO$UHD%XLOGLQJ&RQWURO/$%&HLWKHUGLUHFWORUWKURXJKD&RPSHWHQW3HUVRQV6FKHPH$
%XLOGLQJ5HJXODWLRQV&RPSOLDQFH&HUWL¿FDWHZLOOWKHQEHLVVXHGWRWKHFXVWRPHU>@0DEHUHTXLUHGIRUVVWHPVFRYHUHG
E*5HJXODWLRQV
© Heating and Hotwater Industry Council (HHIC)
0020250181_00 geoTHERM Installation and maintenance instructions
59
Appendix
SERVICE RECORD
It is recommended that your heating system is serviced regularly and that the
appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Interval Record below, please ensure
you have carried out the service as described in the manufacturer’s
LQVWUXFWLRQV$OZDVXVHWKHPDQXIDFWXUHU¶VVSHFL¿HGVSDUHSDUWZKHQUHSODFLQJFRQWUROV
SERVICE 01
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
SERVICE 02
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
SERVICE 03
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
SERVICE 04
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
SERVICE 05
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
SERVICE 06
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
SERVICE 07
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
SERVICE 08
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
SERVICE 09
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
SERVICE 10
Engineer name: Company name: Telephone No: 2SHUDWLYH,’1R Comments:
Date:
Signature
Signature
60
Installation and maintenance instructions geoTHERM 0020250181_00
Index
Index
B Brine circuit
Filling ………………………………………………………………….. 18 Purging ……………………………………………………………….. 18 C
Casing Fitting ………………………………………………………………….. 23 CE label
……………………………………………………………………. 10 Check programmes
Using…………………………………………………………………… 29 Comfort protection mode……………………………………………..
27 Competent person……………………………………………………….. 4 Connection diagram
…………………………………………………… 21 D Data plate …………………………………………………………………. 10 DCF sensor
………………………………………………………………. 28 Design Heat pump …………………………………………………………….. 9
Disposal……………………………………………………………………. 30 Documents …………………………………………………………………. 8
E Electricity ……………………………………………………………………. 4 F Fault list, deleting
………………………………………………………. 28 Fault memory Querying ……………………………………………………………… 28
Fault memory, deleting……………………………………………….. 28 Front casing Fitting
………………………………………………………………….. 24 Removing…………………………………………………………….. 15 Frost
damage Heating installation …………………………………………………. 5
Preventing……………………………………………………………… 5 Functionality ……………………………………………………………. 10
Heat pump …………………………………………………………….. 9 H Handing over to the end user
………………………………………. 27 Heat pump Connecting…………………………………………………………… 16 Protecting
against frost ………………………………………….. 30 Heating installation Filling
………………………………………………………………….. 18 I Installation assistant Restarting
……………………………………………………………. 28 Installation assistant, ending ………………………………………..
24 Installer level, calling up ……………………………………………… 25 Instructions Validity
………………………………………………………………….. 8 Intended use……………………………………………………………….. 6 L Live
Monitor Calling up……………………………………………………….. 25, 28 M Maintenance message,
checking …………………………………. 27 P Packaging…………………………………………………………………. 11 Product
Cleaning………………………………………………………………. 28
Q Qualification………………………………………………………………… 4 Querying
Fault memory……………………………………………………….. 28 R Recycling…………………………………………………………………..
30 Regulations ………………………………………………………………… 7 S Safety
device………………………………………………………………. 4 Schematic drawing ………………………………………………………. 4
Scope of delivery
Checking……………………………………………………………… 11 Service message, checking………………………………………….
27 Side casing
Removing…………………………………………………………….. 15 Spare parts………………………………………………………….. 27,
29 Starting
Installation assistant ……………………………………………… 28 Statistics
Calling up…………………………………………………………….. 25 Status codes……………………………………………………………… 28
System
Filling ………………………………………………………………….. 18 T Terminal connection diagram
………………………………………. 21 Tool …………………………………………………………………………… 6 Transport
……………………………………………………………………. 5 Transport locks
Removing…………………………………………………………….. 15 Treating the heating
water…………………………………………… 17 U Using
Check programmes ………………………………………………. 29 V Voltage ……………………………………………………………………….
4 W Wall-mounting …………………………………………………………… 14 Wiring diagram
………………………………………………………….. 21
0020250181_00 geoTHERM Installation and maintenance instructions
61
0020250181_00
0020250181_00 30.05.2017
Supplier Vaillant Ltd. Nottingham Road Belper Derbyshire Telephone 03301003461 info@vaillant.co.uk www.vaillant.co.uk
DE56 1JT
© These instructions, or parts thereof, are protected by copyright and may be
reproduced or distributed only with the manufacturer’s written consent.
We reserve the right to make technical changes.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>