Acuity Brands EU2C Emergency Light Instruction Manual
- June 10, 2024
- Acuity Brands
Table of Contents
Acuity Brands EU2C Emergency Light
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
- WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE. For your protection, read and follow these warnings and instructions carefully before installing or maintaining this equipment. These instructions do not attempt to cover all installation and maintenance situations. If you do not understand these instructions or additional information is required, contact Lithonia Lighting or your local Lithonia Lighting distributor.
- WARNING: RISK OF ELECTRIC SHOCK – NEVER CONNECT TO, DISCONNECT FROM, OR SERVICE WHILE EQUIPMENT IS ENERGIZED.
- WARNING: RISK OF FIRE. Lamps are hot. Keep combustible material away from hot parts. Observe lamp manufacturer’s warnings, recommendations and restrictions on lamp operation and maintenance. Make sure lamps are correctly installed.
- CAUTION: The battery in this unit may not be fully charged. After electricity is connected to unit, let battery charge for at least 24 hours, then normal operation of this unit should take effect. To check, press the TEST button. The lamps on the unit should turn on.
- NOTE: Complies with California Title 20. Product label is marked with .
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
- Do not use outdoors. Suitable for use in 10 o1 °C-40° C (50° F-104° • F) indoor damp locations. Consult local building code for approved wiring and installation.
- Disconnect AC power before servicing and installation.
- Do not mount near gas or electric heaters.
- Do not use this equipment for anything other than its intended use.
- The use of accessory equipment not recommended by the manufacturer will void product listing and warranty and may cause an unsafe condition.
- Any service on this equipment should be performed by qualified personnel only.
- Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel.
- Do not ceiling mount.
- Use caution when servicing batteries.
- Cap unused wires with enclosed wire nuts or other approved method.
- Make sure wire terminations are secure and leads are properly tucked in appropriate wire channels.
INSTALLATION
NOTE: Max mounting height is 10.8 ft to achieve at least 1 ft-candle of illuminance in emergency mode.
INSTALLATION INSTRUCTION
J-BOX MOUNTING:
- Connect RED lead to HOT of the power supply from 120-277V. Connect the WHITE lead to the NEUTRAL of the supply.
- Attach back plate to J-Box and secure with screws.
- Complete the battery connection. (Fig. B, page 1)
- Align snaps and push housing directly onto the back plate (Fig. C, page 1 ). Apply continuous AC power.
- After the battery has been left to charge for 24 hours, test the unit by pushing the test switch and the LED lamp head will turn ON.
CONDUIT MOUNTING:
-
Secure back plate to wall surface using keyhole knockouts on the back plate.
-
Route wires through hole in conduit flange and make conduit connection. Connect RED lead to HOT of the power supply from
120-277V. Connect the WHITE lead to the NEUTRAL of the supply. -
Complete the battery connection (Fig. B, page 1 ).
-
Align snaps and push housing directly onto the back plate. Apply continuous AC power.
-
After battery has been left to charge for 24 hours, test the unit by pushing the test switch and the LED lamp head will turn ON.
WALL MOUNTING:
-
Secure back plate to wall surface using keyhole knockouts on the back plate.
-
Feed fixture leads through back plate and connect to AC power supply. Connect RED lead to HOT of the power supply from
120-277V. Connect the WHITE lead to the NEUTRAL of the supply. -
Complete the battery connection (Fig. B, page 1 ).
-
Align snaps and push housing directly onto the back plate. Apply continuous AC power.
-
After battery has been left to charge for 24 hours, test the unit by pushing the test switch and the LED lamp head will turn ON.
OPERATION:
- During an electrical power failure, the LED lamps will automatically come on for a minimum of 90 minutes.
- To test, press the “TEST” switch. The emergency LED lamps will illuminate and LED indicator will turn OFF. When the switch
is released, the lamps will turn OFF and the LED indicator will turn ON.
LED STATUS INDICATOR KEY and TROUBLESHOOTING:
TESTING:
National Electric Code (NEC) and NFPA 101 (current Life Safety code) requires
that routine tests need to be performed as: Once every
month, the unit needs to be tested for duration of 30 seconds. Push in and
hold the test switch to perform this test. Once every 12
months, a full 90 minute (per UL requirements) test needs to be performed on
the unit. Disconnect power to the unit and leave it in the
emergency mode. The lamps should stay ON for at least 90 minutes. Written
records of the testing are to be kept for examination by the
authority having jurisdiction.
TROUBLESHOOTING:
-
If the charge indicator is OFF with AC applied: Check that the circuit breaker for the AC Supply is ON. Note: The status indicator does not light in Test or Emergency mode.
-
If the charge indicator light is RED with AC applied: Check that battery is properly connected. If the battery is too low the status indicator may be RED as well. Charge for 24 hours and validate if condition corrects itself. If not replace battery
-
If the Emergency lights are dim, battery not fully charged. Allow battery to recharge for 24 hours and then retest. If lights are still
dim, replace battery. -
If emergency mode does not last 90 minutes and there are remote lamps connected to the equipment: Turn OFF the AC supply
and disconnect the remote circuit wires from the equipment. Turn ON the AC supply, charge for 24 hours and validate if emergency mode will run for 90 minutes. If this fails, replace the battery. If it passes, then check the remote circuit for short or overload condition and correct as required. Reconnect the remote circuit wires and restore AC power. If the load is within the specification of the unit and turn ON at all, the unit is defective, replace the unit. If the charge will not last 90 minutes after 24 hours of charging, replace the battery.