KOZY HEAT Bayport 36 Direct Vent Fireplace Instructions
- June 10, 2024
- Kozy Heat
Table of Contents
Bayport 36 Direct Vent Fireplace
Please leave these reference guides at the installation location until the installation is finished. See owners manual for full installation and finishing instructions before making final decisions as information is subject to change.
Specifications
(all measurements are in inches)
- GAS LINE OPENING: RIGHT SIDE
- ELECTRICAL ACCESS: LEFT SIDE
Model| BTU| Height| Front Width| Back Width| Depth| Glass Viewing
Area
---|---|---|---|---|---|---
Actual| Framing| Actual| Framing| Actual| Framing| Actual| Framing
BAY‐36 (all versions)| 26,500| 32| 42| 35‐3/4| 36‐1/4| 18‐7/8| 36‐1/4|
15‐13/16| 15‐7/8| 29‐1/4 x 23‐3/4
Framing Opening
Finishing Clearances
Finish Trim Kit
Important! If you are finishing around the fireplace with le or stone make
sure that you install the Finishing Trim Kit at the framing stage.
The trim kit allows for your finishing board and your le/stone to finish up
against, creating a shadowbox for the face to sit inside.
Do not use with RSF fronts, all other fronts apply.
Mantel Clearances
NOTE: The clearances allowed here are ONLY for Safety Screen Fronts with
part numbers that include the number 2 ( Example: #B36‐PSF2 )
Clearances outlined in this drawing are for installations with screen front
B36‐RSF2 ONLY ![KOZY HEAT Bayport 36 Direct Vent Fireplace - CombusƟble
Material Allowed 1](https://manuals.plus/wp-content/uploads/2023/04/KOZY-HEAT- Bayport-36-Direct-Vent-Fireplace-CombusƟble-Material-Allowed-1.jpg)
Dimension | BAY‐36 |
---|---|
O | 32 |
P | 1‐1/2 |
Q | 3/4 |
R | 5 |
S | 7 |
T | 9 |
NON‐COMBUSTIBLE ZONE
All other screen front installations must follow the clearances outlined here
Dimension | BAY‐36 |
---|---|
U | 32 |
V | 4‐1/2 |
W | 3/4 |
X | 8 |
Y | 10 |
Z | 12 |
Horizontal Termination Framing
Horizontal Venting Minimum Requirements
H = Horizontal
V = Vertical
Note specific gas type minimums
TOP VENTING | LOG MODEL |
---|---|
Requirement | BAY‐36‐L |
(NG/LP) Vertical Min | 90o Elbow |
(NG/LP) Horizontal Min | 6 |
(NG/LP) Horizontal Max | 8 ft. |
TOP VENTING | GLASS MODEL |
---|---|
Requirement | BAY‐36‐G |
(NG/LP) Vertical Min | 6 + 90o Elbow |
(NG/LP) Horizontal Min | 6 |
(NG/LP) Horizontal Max | 8 ft. |
REAR VENTING | BOTH MODELS |
---|---|
Requirement | BAY‐36‐L/G |
(NG) Horizontal Min | 6 |
(NG) Horizontal Max | 48 |
(LP) Horizontal Min | 6 |
(LP) Horizontal Max | 12 |
Consult venting chart in the manual for all options above minimum requirements
Heat Shield Requirements
The vertical vent
heat shield must be installed for EVERY type of venting applica on.
The horizontal vent heat shield must be installed when incorporating minimum
horizontal venting and is positioned according to the gas type.