KOZY HEAT Slayton 60 Direct Vent Fireplace Instructions

June 10, 2024
Kozy Heat

Slayton 60 Direct Vent Fireplace

Please leave these reference guides at the installation location until the installation is finished. See owners manual for full installation and finishing instructions before making final decisions as information is subject to change.

Specifications

(all measurements are in inches)

  • GAS LINE OPENING: LEFT/RIGHT SIDES
  • ELECTRICAL ACCESS: RIGHT SIDE

Model| BTU| Height| Front Width| Back Width| Depth| Glass Viewing
Area
---|---|---|---|---|---|---
Actual| Framing| Actual| Framing| Actual| Framing| Actual| Framing
SLA‐60| 55,000| 31‐1/16| 36‐7/8| 66| 71‐1/8| 66| 71‐1/8| 15‐13/16| 19| 58‐7/16 x 14‐1/4

Framing Opening

KOZY HEAT Slayton 60 Direct Vent Fireplace

Finishing Clearances

NON‐COMBUSTIBLE ZONEKOZY HEAT Slayton 60 Direct Vent Fireplace -
CombusƟble Material Allowed

Dimension  SLA‐60
N 72‐5/8
O 38‐3/8

Mantel Clearances

KOZY HEAT Slayton 60 Direct Vent Fireplace - CombusƟble Material Allowed
1

Dimension

P| Q| R| S| T
40‐1/4| 14‐1/4| 17‐1/4| 31‐3/16| 62‐1/4

Finish Trim Kit

Important!
If you are finishing around the fireplace with le or stone make sure that you install the Finishing Trim Kit at the framing stage.
The trim kit allows for your finishing board and your le/stone to finish up against, creating a shadowbox for the face to sit inside.

Horizontal Termination Framing

KOZY HEAT Slayton 60 Direct Vent Fireplace - CombusƟble Material Allowed
2

Dimension SLA‐60
U 19
V 53‐7/8
W 61‐3/8
X 53‐7/8
Y 61‐3/8

KOZY HEAT Slayton 60 Direct Vent Fireplace - CombusƟble Material Allowed
3

Horizontal Venting Minimum Requirements

Note specific gas type minimumsKOZY HEAT Slayton 60 Direct Vent
Fireplace - CombusƟble Material Allowed 4Consult venting chart in manual for op ons above minimum requirements
H = Horizontal
V = Vertical

Requirement SLA‐60
(NG) Vertical Min 12 + 6 + 90o Elbow
(NG) Horizontal Min 9
(NG) Horizontal Max 36

KOZY HEAT Slayton 60 Direct Vent Fireplace - CombusƟble Material Allowed
5

Requirement SLA‐60
(LP) Vertical Min 24 + 90o Elbow
(LP) Horizontal Min 9
(LP) Horizontal Max 24

Heat Shield Requirements

KOZY HEAT Slayton 60 Direct Vent Fireplace - CombusƟble Material Allowed
6The vertical vent heat shield must be installed for EVERY type of venting applica on.
The horizontal vent heat shield must be installed when incorporating minimum horizontal venting.
Align the (3) screw holes on the horizontal heat shield tabs to the corresponding (3) screw holes on the vertical heat shield necessary for your installation

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals