EATON 107631 Moeller Series NZM Molded Case Circuit Breaker Owner’s Manual

June 9, 2024
EATON

EATON 107631 Moeller Series NZM Molded Case Circuit Breaker Owner’s Manual
EATON 107631 Moeller Series NZM Molded Case Circuit
Breaker

Catalog Number: 107631

Eaton Moeller series NZM – Molded Case Circuit Breaker. Circuit-breaker, 3p, 15A, box terminals, N2-AF15-BT-NA

General specifications

Product Name
Eaton Moeller series NZM – Molded Case Circuit Breaker

Certifications

IEC 60947-2 UL 489 CE marking UL listed CSA-C22.2 No. 5-09 UL (Category Control Number DIVQ) UL (File No. E31593) CSA (Class No. 1432- 01) Specially designed for North America IEC CSA (File No. 22086) CSA certified IEC/EN 60947 UL/CSA

Product specifications

Rated operational current for specified heat dissipation (In) 15 A

Short-circuit rating
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz 5 kA

Clearances and creepage distances

Meets the product standard’s requirements.

Electromagnetic compatibility

Is the panel builder’s responsibility. The specifications for the switchgear must be observed.

Mounting Method

DIN rail (top hat rail) mounting optional Built-in device fixed built-in technique Fixed

Amperage Rating 15 A

Lifting

Does not apply, since the entire switchgear needs to be evaluated.

Terminal capacity (copper strip)

Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched) Max. 10 segments of 16 mm x 0.8 mm at box terminal   Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched) Min. 2 segments of 9 mm x 0.8 mm at box terminal

Handle type Rocker lever

Verification of thermal stability of enclosures

Meets the product standard’s requirements.

Ambient storage temperature – min 40 °C

Protection against direct contact

Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110

Terminal capacity (copper busbar)

M8 at rear-side screw connection
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 20 mm x 5 mm direct at switch rear-side connection

Connections for external conductors

Is the panel builder’s responsibility.

Special features

Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit breaker (Rated short-circuit breaking capacity Icn) Rated current = rated uninterrupted current: 15 A Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate. Fixed overload releases Ir

Ambient operating temperature – max 70 °C

Position of connection for main current circuit Front side

Climatic proofing

Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30

Terminal capacity (copper stranded conductor/cable)

4 mm² – 3/0 mm² (1x) direct at switch rear-side connection
4 mm² – 350 mm² (1x) at box terminal
4 mm² – 350 mm² (1x) at tunnel terminal

Features

Motor drive optional Protection unit

Low-voltage HBC fuse – max 355 A gG/gL

Lifespan, electrical

6500 operations at 400 V AC-3
7500 operations at 690 V AC-1
6500 operations at 415 V AC-3
10000 operations at 400 V AC-1
5000 operations at 690 V AC-3

Electrical connection type of main circuit Frame clamp

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz 50kA

Impulse withstand voltage Is the panel builder’s responsibility.

Utilization category A (IEC/EN 60947-2)

Number of poles Three-pole

Ambient operating temperature – min -25 °C

Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

Terminal capacity (control cable)

14 mm² – 18 mm² (1x)
16 mm² – 18 mm² (2x)

Equipment heat dissipation, current-dependent 2.87 W

Instantaneous current setting (Ii) – min 350 A

Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

Testing of enclosures made of insulating material

Is the panel builder’s responsibility.

Rated operational current

300 A (380/400 V AC-1, making and breaking capacity)
300 A (415 V AC-1, making and breaking capacity)
15 A (660-690 V AC-3, making and breaking capacity)
15 A (690 V AC -1, making and breaking capacity)

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz

85 kA

Application

Branch circuits, feeder circuits Use in unearthed supply systems at 690 V

Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

Rated short-circuit making capacity Icm at 240 V, 50/60 Hz 187 kA

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz 35 kA

Degree of protection (IP), front side

IP40 (with insulating surround)
IP66 (with door coupling rotary handle)

Rated short-circuit making capacity Icm at 525 V, 50/60 Hz 53 kA

Rated short-circuit making capacity Icm at 690 V, 50/60 Hz 40 kA

Instantaneous current setting (Ii) – max 350 A

Overload current setting (Ir) – min 15 A

Short delay current setting (Isd) – min 0 A

Number of auxiliary contacts (normally closed contacts) 0

Terminal capacity (copper solid conductor/cable)

6 mm² – 11 mm² (1x) direct at switch rear-side connection
6 mm² – 12 mm² (1x) at box terminal
16 mm² (1x) at tunnel termina

Degree of protection (terminations)

IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal)

Rated operating voltage Ue (UL) – max 600Y/347 V, 480 V

10.9.2 Power-frequency electric strength

Is the panel builder’s responsibility.

Short-circuit release non-delayed setting – min 350 A

Degree of protection

IP20 (basic degree of protection, in the operating controls area) IP20

Overvoltage category III

Rated short-time withstand current (t = 1 s) 1.9 kA

Short delay current setting (Isd) – max 0 A

Rated impulse withstand voltage (Uimp) at auxiliary contacts 6000 V

Number of auxiliary contacts (change-over contacts) 0

Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Functions

System and cable protection Current limiting circuit breaker

Corrosion resistance

Meets the product standard’s requirements.

Resistance to ultra-violet (UV) radiation

Meets the product standard’s requirements.

Inscriptions

Meets the product standard’s requirements.

Isolation

500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)

Circuit breaker frame type

NZM2

Direction of incoming supply

As required

Shock resistance

20 g (half-sinusoidal shock 20 ms)

Rated insulation voltage (Ui)

1000 V

Terminal capacity (aluminum solid conductor/cable)

16 mm² (1x) at tunnel terminal