MEAN WELL PWM-60-KN Series 60W Constant Voltage PWM Output KNX LED Driver Owner’s Manual

July 30, 2024
MEAN WELL

PWM-60-KN Series 60W Constant Voltage PWM Output KNX LED Driver

Specifications

  • Model: PWM-60-12, PWM-60-24

  • DC Voltage: 12V, 24V

  • Rated Current: 5A, 2.5A

  • Rated Power: 60W

  • Output Dimming Range: 0 – 100%

  • PWM Frequency (Typ.): 200 – 4000Hz (user
    changeable via ETS)

  • Setup, Rise Time: 500ms, 80ms / 115VAC or
    230VAC

  • Hold Up Time (Typ.): 16ms / 115VAC or
    230VAC

  • Voltage Range: 90 – 305VAC, 127 – 431VDC

  • Frequency Range: 47 – 63Hz

  • Power Factor (Typ.): PF > 0.97 / 115VAC, PF

    0.95 / 230VAC, PF > 0.92 / 277VAC @ full load

  • Total Harmonic Distortion: THD < 20%

  • Efficiency (Typ.): 86%

  • AC Current (Typ.): 0.8A / 115VAC, 0.4A /
    230VAC, 0.32A / 277VAC

  • Inrush Current (Typ.): Cold start 50A
    (twidth=350s measured at 50% Ipeak) at 230VAC

  • Max. No. of PSUs on 16A Circuit Breaker: 9
    units (circuit breaker of type B) / 16 units (circuit breaker of
    type C) at 230VAC

Product Usage Instructions

Installation

  1. Ensure the power source meets the voltage and frequency
    requirements specified in the manual.

  2. Connect the LED driver to the power source following the wiring
    diagram provided.

  3. Mount the LED driver in a well-ventilated area away from direct
    sunlight and moisture.

Dimming Setup

To adjust the dimming range, follow these steps:

  1. Access the dimming settings through the ETS interface.

  2. Select the desired dimming percentage within the range of 0 to
    100%.

  3. Verify the dimming operation by testing the connected LED
    fixtures.

Troubleshooting

If you encounter any issues with the LED driver, refer to the
troubleshooting section of the manual or contact customer support
for assistance.

FAQ

Q: Can I use this LED driver with dimmable LED fixtures?

A: Yes, the PWM-60-KN series LED driver supports dimmable LED
fixtures within the specified dimming range.

Q: How can I change the PWM frequency?

A: The PWM frequency can be adjusted via the ETS interface as
per the user manual instructions provided.

Q: What is the maximum number of LED drivers that can be

connected to a 16A circuit breaker?

A: The maximum number of LED drivers depends on the type of
circuit breaker used. Please refer to the manual for specific
details.

P W M – 6 0 – K N 60W Constant Voltage PWM Output KNX LED Driver

series

User’s Manual

– ()

File Name:PWM-60-KN-SPEC 2024-03-12

60W PWM Output KNX LED Driver

PWM-60-KN series

SPECIFICATION

MODEL

PWM-60-12

PWM-60-24

DC VOLTAGE

12V

24V

RATED CURRENT

5A

2.5A

RATED POWER

60W

60W

OUTPUT DIMMING RANGE

0 ~ 100%

PWM FREQUENCY (Typ.) 200~4000Hz user changable via ETS

SETUP, RISE TIME Note.2 500ms, 80ms/ 115AC or 230VAC

HOLD UP TIME (Typ.)

16ms/115VAC or 230VAC

VOLTAGE RANGE Note.3

90 ~ 305VAC 127 ~ 431VDC (Please refer to “STATIC CHARACTERISTIC” section)

FREQUENCY RANGE

47 ~ 63Hz

POWER FACTOR (Typ.)

PF>0.97/115VAC, PF>0.95/230VAC, PF>0.92/277VAC @ full load (Please refer to “POWER FACTOR (PF) CHARACTERISTIC” section)

TOTAL HARMONIC DISTORTION

THD< 20%(@load60%/115VAC, 230VAC; @load75%/277VAC) (Please refer to “TOTAL HARMONIC DISTORTION” section)

INPUT

EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.)

86%

89%

0.8A / 115VAC 0.4A / 230VAC 0.32A / 277VAC COLD START 50A(twidth=350s measured at 50% Ipeak) at 230VAC; Per NEMA 410

MAX. NO. of PSUs on 16A CIRCUIT BREAKER

9 units (circuit breaker of type B) / 16 units (circuit breaker of type C) at 230VAC

LEAKAGE CURRENT

<0.25mA / 277VAC

<0.5W

OVERLOAD

108 ~ 130% rated output power Hiccup mode, recovers automatically after fault condition is removed

SHORT CIRCUIT

Shut down o/p voltage, re-power on to recover

PROTECTION OVER VOLTAGE

15 ~ 17V Shut down o/p voltage, re-power on to recover

28 ~ 34V

OVER TEMPERATURE Shut down o/p voltage, re-power on to recover

WORKING TEMP.

Tcase=-35 ~ +85 (Please refer to ” OUTPUT LOAD vs TEMPERATURE” section)

MAX. CASE TEMP.

Tcase=+85

WORKING HUMIDITY

20 ~ 95% RH non-condensing

ENVIRONMENT STORAGE TEMP., HUMIDITY -35 ~ +80, 10 ~ 95% RH

TEMP. COEFFICIENT

±0.03%/ (0 ~ 50)

VIBRATION

10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along X, Y, Z axes

SAFETY STANDARDS

Note.5

ENEC BS EN/EN61347-1, BS EN/EN61347-2-13, BS EN/EN62384 EAC TP TC 004 approved

independent, GB19510.14,GB19510.1,

KNX STANDARDS

Certified protocol

WITHSTAND VOLTAGE

SAFETY & EMC

ISOLATION RESISTANCE

EMC EMISSION Note.6

I/P-O/P:3.75KVAC
I/P-O/P:100M Ohms / 500VDC / 25/ 70% RH
Compliance to BS EN/EN55015, BS EN/EN61000-3-2 Class C (@load60%) ; BS EN/EN61000-3-3,GB/T 17743, GB17625.1;EAC TP TC 020

EMC IMMUNITY MTBF

Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11; BS EN/EN61547, light industry level (surge immunity Line-Line 2KV),EAC TP TC 020
2135.2K hrs min. Telcordia SR-332 (Bellcore) ; 247.7K hrs min. MIL-HDBK-217F (25)

OTHERS DIMENSION

1505335mm (LWH)

PACKING

0.45Kg;30pcs/16.0Kg/1.0CUFT

NOTE

1. All parameters NOT specially mentioned are measured at 230VAC input, rated current and 25 of ambient temperature. 2. De-rating may be needed under low input voltages. Please refer to “STATIC CHARACTERISTIC” sections for details. 3. Length of set up time is measured at first cold start. Turning ON/OFF the driver may lead to increase of the set up time. 4. The driver is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected
by the complete installation, the final equipment manufacturers must re- qualify EMC Directive on the complete installation again. (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf) 5. This series meets the typical life expectancy of >50,000 hours of operation when Tcase, particularly tc point (or TMP, per DLC), is about 75 or less. 6. Please refer to the warranty statement on MEAN WELL’s website at http://www.meanwell.com 7. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft). 8. For any application note and IP water proof function installation caution, please refer our user manual before using. https://www.meanwell.com/Upload/PDF/LED_EN.pdf
Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

File Name:PWM-60-KN-SPEC 2024-03-12

60W PWM Output KNX LED Driver
DIMMING OPERATION

PWM-60-KN series

AC/L(Brown) AC/N(Blue)

PWM-60-KN

Dimming principle for PWM style output Dimming is achieved by varying the duty cycle of the output current.
Output DC current ON

Io=0A

OFF TON
T

TON Duty cycle(%) =

×100%

T

Output PWM frequency up to 4KHz

Vo+(Red) Vo-(Black) KNX+(Red) KNX-(Black)

KNXInterface Apply KNX signal between KNX+ and KNX-. The application program(database) can be downloaded via Online Catalogs from ETS or via http://www.meanwell.com/productCatalog.aspx

File Name:PWM-60-KN-SPEC 2024-03-12

60W PWM Output KNX LED Driver
OUTPUT LOAD vs TEMPERATURE

PWM-60-KN series

LOAD (%)

THD LOAD (%)

100
80 230VAC Input only
60 50 40
20

-35 -25 -10

0

15

30

50

60

AMBIENT TEMPERATURE,Ta ()

70 (HORIZONTAL)

LOAD (%)

100
80 230VAC Input only
60
40
20

-35 -25 0

20

45

60

70

80

85 (HORIZONTAL)

Tcase ()

STATIC CHARACTERISTIC

100 90 80 70 60 50 40
90 100 125 135 145 155 165 175 180 200 230 305
INPUT VOLTAGE (V) 60Hz De-rating is needed under low input voltage.

TOTAL HARMONIC DISTORTION (THD)

24V Model, Tcase at 75
25

20

15

10

5

0

50%

60%

70%

80%

90%

LOAD

115VAC 230VAC 277VAC
100%

EFFICIENCY(%)

PF

POWER FACTOR (PF) CHARACTERISTIC

Tcase at 75
1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
LOAD

115V 230V 277V

EFFICIENCY vs LOAD

PWM-60-KN series possess superior working efficiency that up to 89% can be reached in field applications. 24V Model, Tcase at 75

95

90

85

80

75

115V

70

230V

65

277V

60

55

50 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

LOAD

File Name:PWM-60-KN-SPEC 2024-03-12

60W PWM Output KNX LED Driver
LIFE TIME

PWM-60-KN series

LIFETIME(Kh)

120

100

80

60

40

20

0

25

35

45

55

65

75

85

Tcase( )

File Name:PWM-60-KN-SPEC 2024-03-12

60W PWM Output KNX LED Driver

PWM-60-KN series

Block Diagram

EMI FILTER

I/P

&

RECTIFIERS

PFC fosc : 50~120KHz PWM fosc : 60~130KHz

PFC CIRCUIT

POWER SWITCHING

O.T.P.

O.L.P.

PWM & PFC CONTROL

RECTIFIERS &
FILTER

O.L.P.

DIMMING CIRCUIT

DETECTION CIRCUIT

O.V.P.

Vo+ VoKNX+ KNX-

Note: PWM fosc here is not related to ouput PWM dimming

Mechanical Specification

Case No. PWM-60KN Unit:mm

AC/L(Brown) AC/N(Blue)

300±20

150 KNX programming button & LED 5

SJTW 18AWG×2C

4.5

tc 35

5
tc : Max. Case Temperature

KNX connector is included in the box

300±10 Ul2464 18AWG×2C(Vo+,Vo-)
Ul2464 20AWG×2C(KNX+,KNX-) 350±10

Vo+(Red) Vo-(Black) KNX+(Red) KNX-(Black)

5 53
13 5
35

Mechanical view of by request
AC/L(Brown) AC/N(Blue)

Vo+(Red) Vo-(Black) KNX+(Red) KNX-(Black)
File Name:PWM-60-KN-SPEC 2024-03-12

60W PWM Output KNX LED Driver
Recommend Mounting Direction

PWM-60-KN series

Installation Manual Connection for KNX-type

AC/L(BROWN) AC/N(BLUE)

Vo+(RED)


Vo-(BLACK)

KNX+(RED)

LED strip or constant voltage LED bulb

KNX-(BLACK) PWM KN series can be ETS adressing/programming WITHOUT connecting to AC mains

KNX Bus

Cautions Before commencing any installation or maintenance work, please disconnect the power supply from the utility. Ensure
that it cannot be re-connected inadvertently! Keep proper ventilation around the unit and do not stack any object on it. Also a 10-15 cm clearance must be kept when
the adjacent device is a heat source. Mounting orientations other than standard orientation or operate under high ambient temperature may increase the
internal component temperature and will require a de-rating in output current. Current rating of an approved primary /secondary cable should be greater than or equal to that of the unit. Please refer
to its specification. Tc max. is identified on the product label. Please make sure that temperature of Tc point will not exceed limit. DO NOT connect “KNX- to Vo-“. The power supply is considered as a component that will be operated in combination with final equipment. Since EMC
performance will be affected by the complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.

File Name:PWM-60-KN-SPEC 2024-03-12