Eterna PRCIRMW3 9W 18W LED Tri Colour Emergency Circular Bulkhead Instruction Manual
- June 9, 2024
- Eterna
Table of Contents
- Eterna PRCIRMW3 9W 18W LED Tri Colour Emergency Circular Bulkhead
- EVENTUALLY, YOU MAY WANT TO REPLACE THIS PRODUCT
- LAMP REPLACEMENT
- INDUSTRIAL BATTERIES
- BATTERY REPLACEMENT
- REPLACEMENT BATTERY TYPE
- CLEANING
- IF YOU EXPERIENCE PROBLEMS:
- READ THIS FIRST
- INTRODUCTION
- INSTALLATION
- OPERATION CHECKS
- UNDERSTANDING THE CONTROLS
- SENSITIVITY / DETECTION RANGE
- HOLD-TIME
- DAYLIGHT SENSOR / THRESHOLD
- CORRIDOR FUNCTION / STAND-BY TIME
- CORRIDOR DIMMING LEVEL / STAND-BY DIMMING LEVEL
- STEP DIM MW SENSOR SPECIFICATIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Eterna PRCIRMW3 9W 18W LED Tri Colour Emergency Circular Bulkhead
EVENTUALLY, YOU MAY WANT TO REPLACE THIS PRODUCT
Regulations require the recycling of Waste from Electrical and Electronic
Equipment (European “WEEE Directive” effective August 2005—UK WEEE Regulations
effective 2nd January 2007). Environment Agency Registered Producer:
WEE/GA0248QZ.
WHEN YOUR PRODUCT COMES TO THE END OF ITS LIFE OR YOU CHOOSE TO REPLACE IT,
PLEASE RECYCLE IT WHERE FACILITIES EXIST DO NOT DISPOSE WITH HOUSEHOLD WASTE.
LAMP REPLACEMENT
The light source is designed to last the lifetime of the luminaire.
The light source contained in this luminaire shall only be replaced by the
manufacturer, serv ice agent or a similar qualified person.
CAUTION, RISK OF ELECTRIC SHOCK.
INDUSTRIAL BATTERIES
Within certain products Eterna Lighting Ltd places lead acid, lithium ion, nickel cadmium & nickel metal hydride batteries on the market. Industrial batteries are subject to waste regulation under the Waste Batteries and Accumulators Regulations 2009 and should be disposed of responsibly. Purchasers may be able to dispose of their waste industrial batteries locally via legitimate licensed trade waste contractors. Eterna is obliged to take back, free of charge and within a reasonable time, waste industrial batteries of the same chemistry supplied to a Purchaser, for treatment and recycling and is required to do this in any calendar year new industrial batteries are placed on the market. In certain circumstances, this may include batteries not originally supplied by Eterna. If any Purchaser requires Eterna to take back Industrial batteries, they should write to the Operations Director, Eterna Lighting Ltd, Huxley Close, NN8 6AB, who will then advise on the necessary arrangements for the receipt, proper treatment and recycling of, the waste industrial batteries.
BATTERY REPLACEMENT
If after routine operation check, the lamp does not remain lit for the three hour period, a new battery pack may be required.
- Switch off the electricity at the mains (both permanent live and switch live) and allow batteries to fully discharge then reconnect to supply and allow charging for 24 hours.
- Test again for 3 hours, if light does not remain lit, then change the battery pack as follows:
- Remove the diffuser.
- Remove the battery case from the gear tray, remove the battery and cut the wires.
- Write current date on the new battery pack and fit a new battery with a suitable connector.
- Refit gear tray and diffuser.
- Restore power and allow charging for 24 hours.
- Perform full operation check and update test record.
REPLACEMENT BATTERY TYPE
- 3.2V 1500mAh Lithium
CLEANING
Clean this fitting only with a soft dry cloth. Do not use any chemical or abrasive cleaners.
IF YOU EXPERIENCE PROBLEMS:
If you believe your product is defective, please return it to the place where you bought it. Our Technical Team will gladly advise on any Eterna Lighting product, but may not be able to give specific instructions regarding individual installations.
See website for more information on replacability and recycling
Email: sales@eterna-lighting.co.uk /
technical@eterna-lighting.co.uk
Visit our website: www.eterna-lighting.co.uk
READ THIS FIRST
Check the pack and make sure you have all of the parts listed on the front of
this booklet. If not, contact the outlet where you bought this product.
This product must be installed by a competent person in accordance with the
current building and IEE wiring regulations.
As the buyer, installer and/or user of this product it is your own
responsibility to ensure that this fitting is fit for the purpose for which
you have intended it. Eterna Lighting cannot accept any liability for loss,
damage or premature failure resulting from inappropriate use.
This product is designed and constructed according to the principles of the
appropriate British Standard and is intended for normal domestic service.
Using this fitting in any other environments may result in a shortened working
life, for example where there is prolonged periods of use or higher than
normal ambient temperatures such as lighting public or shared spaces or in
nursing /care home facilities.
Switch off the mains before commencing installation and remove the appropriate
circuit fuse or lock off MCB.
Suitable for outdoor use.
This product is suitable for use in living areas, Bathroom Zone 2 and outsides
of zones.
If being fitted in a bathroom a 30mA RCD must be used.
This product is designed for permanent connection to fixed wiring: this must
be a suitable circuit (protected with the appropriate MCB or fuse).
This product is suitable for installation on surfaces with normal flammability
e.g. wood, plasterboard and masonry. It is not suitable for use on highly
flammable surfaces (e.g. polystyrene, textiles).
Before making fixing hole(s), check that there are no obstructions hidden
beneath the mounting surface such as pipes or cables.
The chosen location of your new fitting should allow for the product to be
securely mounted (e.g. to a ceiling joist) and safely connected to the mains
supply (lighting circuit).
When making connections ensure that the terminals are tightened securely and
that no strands of wire protrude. Check that the terminals are tightened onto
the bared conductors and not onto any insulation.
This product is double insulated, do not connect any part to Earth.
This product is not intended to be used by children and persons with sensory,
physical and/or mental impairments that would prevent them from using it
safely.
You are advised at every stage of your installation to double-check any
electrical connections you have made. After you have completed your
installation there are electrical tests that should be carried out, these
tests are specified in the current IEE wiring and building regulations.
The batteries supplied with this fitting are a consumable part and therefore
may be outside of any warranty offered.
INTRODUCTION
The LED utility light incorporates a microwave sensing device which
continuously scans the operating zone and immediately switches the light on
when it detects movement in that area. This means that whenever movement is
detected within the range of the sensor the light will switch on automatically
and illuminate the area you have selected to light. While there is movement
within range of the unit the light will remain on.
A microwave sensor is an active motion detector emitting high-frequency
electro-magnetic waves at 5.8GHz and receiving their echo. The sensor detects
change in the echo pattern within its detection zone and the light is then
triggered. The wave can pass through doors, glass and thin walls and will
continually monitor the signal within the detection area.
INSTALLATION
Isolate mains and lock off.
Choose the location of your new fitting giving consideration to all of the
points listed above.
-
Unscrew gear tray screw and allow the gear tray to rest on its hinge.
-
Drill holes in the back of your fitting for your fixing screws, take care and drill gently to ensure a clean hole through. Use a drill bit sized appropriately to your fixing screws (not supplied).
-
Using the back of your fitting as a template, mark the position of your fixing holes on your mounting surface.
-
Prepare the holes in your mounting surface as appropriate for your fixings.
-
Pierce the rubber grommet in the back of your fitting making a hole just large enough to make a tight fit around the incoming mains cable.
-
Thread the cable through the grommet and offer the fitting to the ceiling / wall.
-
Secure the fitting in place. Note if protection against ingress of moisture is required, the heads of screws must be covered with a silicone or similar sealant.
-
Check that the grommet is still correctly fitted in the cable entry hole and around the incoming cable.
-
Make the electrical connections to the terminal block according to the markings:
Brown to live (L)
Blue to neutral (N) -
Mark the current date on the battery pack.
-
Ensure that the battery plug is connected to the socket on the driver.
-
Set power to the desired option by selecting appropriate switch setting on the driver: 9W / 14W / 18W options
-
Set colour temperature to the desired option by selecting appropriate switch setting on the driver.
DL| Daylight| 6500K
---|---|---
CW| Cool White| 4400K
WW| Warm White| 3000K -
Set the desired settings on the microwave.
-
Replace gear tray and secure in position.
-
Offer the diffuser onto the top of the fitting and tighten securely making sure the gasket is correctly fitted in place.
-
Restore the power and switch on. A green LED light should always be present indicating the fitting is charging.
NOTE: For non-maintained operation, remove link wire from L and L1.
For switched operation, remove link wire and make a switched supply into L1.
NOTE: In warm white (3000K) and daylight white (6500K) operation only one
set of LEDs will illuminate, in cool white (4400K) both sets of LEDs will
illuminate.
An Earth connection is not required for the operation of these Class II
luminaires. The addition of the Earth terminal provides a loop-in/loop out
facility which allows connectivity through to other Class I luminaires in the
same lighting circuit.
OPERATION CHECKS
Periodic testing should be carried out to ensure emergency lighting is operating correctly. Interruption of the supply, causing the fitting to be energised from the battery, should be carried out by the operation of a local keyswitch or other isolation device. During this period all fittings should be examined visually to ensure that they are functioning correctly. At the end of the test period the supply shall be restored and all indicator lamps or devices checked to ensure that the normal supply has been restored.
DAILY:
Visual inspection of the battery charge LED.
EACH MONTH:
Isolate the power supply for a period sufficient to ensure that each lamp is
illuminated. Endorse the test record form supplied.
ONCE EACH YEAR:
Isolate the power supply and check that the light is still illuminated after 3
hours. Endorse the test record form.
Because of the possibility of a failure of the normal lighting supply
occurring shortly after a period of testing of the emergency lighting system
or during the subsequent recharge period, all full duration tests shall
wherever possible be undertaken preceding time of low risk to allow for
battery recharge.
NOTE: please keep this instruction booklet and the test record in a safe place. A fire officer or other authorised person may want to see your record of inspection and testing.
UNDERSTANDING THE CONTROLS
REFER TO STEP DIM MICROWAVE SENSOR PICTURE OPPOSITE:
The motion detector can turn on the light based on movement. With this
detector built in, light is automatically on when needed and dimmed to preset
level before it is totally off.
SENSITIVITY / DETECTION RANGE
Sensitivity can be adjusted by selecting the combination on the DIP switches for different applications.
| 1|
---|---|---
I| ON| 100%
II| OFF| 50%
HOLD-TIME
Hold-time refers to the time period that the light remains 100% on if no more movement is detected.
| 2| 3|
---|---|---|---
I| ON| ON| 5sec
II| ON| OFF| 90sec
III| OFF| OFF| 180sec
IV| OFF| ON| 10min
DAYLIGHT SENSOR / THRESHOLD
Daylight threshold can be preset on DIP switches. Light will always turn on upon movement if daylight sensor is disabled.
| 4|
---|---|---
I| ON| Disable
II| OFF| 10Lux
CORRIDOR FUNCTION / STAND-BY TIME
This is the time period that the light remains at a low level before it is completely turned off.
| 5| 6|
---|---|---|---
I| ON| ON| 0Sec
II| ON| OFF| 10Sec
III| OFF| ON| 10Min
IV| OFF| OFF| +
CORRIDOR DIMMING LEVEL / STAND-BY DIMMING LEVEL
Light can be dimmed to different levels after hold-time.
| 7|
---|---|---
I| ON| 10%
II| OFF| 30%
STEP DIM MW SENSOR SPECIFICATIONS
PRODUCT TYPE | STEP DIM MICROWAVE MOTION SENSOR |
---|---|
Operating Voltage | 220-240VAC 50/60Hz |
HF System | 5.8GHz |
Transmission Power | <0.2mW |
Detection Angle | 150° Max |
Power Consumption | <0.3W |
Detection Range | Max. 6m adjustable |
Dectection sensitivity | 50% / 100% |
Hold time | 5s / 90s /180s / 10 min |
Corridor function | 0s / 10s / 10 min / Disable |
Corridor Dimming Level | 10% / 30% |
Daylight sensor | 10 lux / Disable |
Mounting | Indoors, ceiling and wall |
Light Control | 10lux, disable |
Working Temp | -20 to +60 degree |
Rated Load | 400W (Inductive load) 800W (Resistive load) 270W (LED) |
Eterna Lighting Ltd
RED DIRECTIVE – Microwave Occupancy Sensor Full declaration available at:
www.eterna-lighting.co.uk/red-declaration
Product Code: | Product Description: |
---|
Product Location:
Installation Date:| Installation Test Duration:
Installed By:
Month|
Test
| Year:| Year:| Year:| Year:| Year:
---|---|---|---|---|---|---
Sign| Date| Sign| Date| Sign| Date| Sign| Date| Sign| Date
01| Short| | | | | | | | | |
02| Short| | | | | | | | | |
03| Short| | | | | | | | | |
04| Short| | | | | | | | | |
05| Short| | | | | | | | | |
06| Short| | | | | | | | | |
07| Short| | | | | | | | | |
08| Short| | | | | | | | | |
09| Short| | | | | | | | | |
10| Short| | | | | | | | | |
11| Short| | | | | | | | | |
12| 3 Hour Endurance| | | | | | | | | |
CIRCULAR OPAL
LED LAMP SPECIFICATIONS:| 9W| 14W| 18W
Luminaire lumens (with diffuser): Warm White, Cool White, Daylight White
| 3000K – 1090 lm
4400K – 1160 lm
6500K – 1130 lm
| 3000K – 1610 lm
4400K – 1770 lm
6500K – 1700 lm
| 3000K – 1970 lm
4400K – 2190 lm
6500K – 2080 lm
Lumens from chip (array): Warm White, Cool White, Daylight White
| 3000K – 1220 lm
4400K – 1300 lm
6500K – 1270 lm
| 3000K – 1810 lm
4400K – 1990 lm
6500K – 1900 lm
| 3000K – 2210 lm
4400K – 2470 lm
6500K – 2350 lm
Useful lumens (array): Warm White, Cool White, Daylight White
| 3000K – 980 lm
4400K – 1050 lm
6500K – 1020 lm
| 3000K – 1450 lm
4400K – 1600 lm
6500K – 1520 lm
| 3000K – 1770 lm
4400K – 1970 lm
6500K – 1880 lm
Rated Wattage| 9W| 14W| 18W
Rated luminous flux
| 3000K – 980 lm
4400K – 1050 lm
6500K – 1020 lm
| 3000K – 1450 lm
4400K – 1600 lm
6500K – 1520 lm
| 3000K – 1770 lm
4400K – 1970 lm
6500K – 1880 lm
Nominal life time of the lamp| 50,000 hrs| 50,000 hrs| 50,000 hrs
Colour temperature| 3000/4400/6500K| 3000/4400/6500K| 3000/4400/6500K
Number of switching cycles before premature lamp failure|
≥15000
|
≥15000
|
≥15000
Warm-up time up to 60% of the full light output| Instant full light| Instant
full light| Instant full light
Dimmable| No| No| No
Nominal beam angle| 120°| 120°| 120°
Rated power| 9W| 14W| 18W
Rated lamp lifetime| 50,000 hrs| 50,000 hrs| 50,000 hrs
Displacement factor| 0.97| 0.97| 0.97
Lumen maintenance factor at end of nominal life| ≥80| ≥80| ≥80
Starting time| Instant full light| Instant full light| Instant full light
Colour rendering| ≥0.8| ≥0.8| ≥0.8
Colour consistency| Within 6 step Macadam ellipse| Within 6 step Macadam
ellipse| Within 6 step Macadam ellipse
Rated peak intensity
| 3000K – 243cd
4400K – 260cd
6500K – 252cd
| 3000K – 361cd
4400K – 396cd
6500K – 378cd
| 3000K – 441cd
4400K – 492cd
6500K – 468cd
Rated beam angle| 120°| 120°| 120°
Voltage / Frequency| 220-240V~50Hz| 220-240V~50Hz| 220-240V~50Hz
Lumen efficacy
| 3000K – 121 lm / W
4400K – 129 lm / W
6500K – 126 lm / W
| 3000K – 115 lm / W
4400K – 126 lm / W
6500K – 121 lm / W
| 3000K – 109 lm / W
4400K – 122 lm / W
6500K – 116 lm / W
This product contains a Light Source of Energy Efficiency Class F
Not suitable for accent lighting
CIRCULAR PRISMATIC
LED LAMP SPECIFICATIONS:| 9W| 14W| 18W
Luminaire lumens (with diffuser): Warm White, Cool White, Daylight White
| 3000K – 1180 lm
4400K – 1270 lm
6500K – 1230 lm
| 3000K – 1715 lm
4400K – 1890 lm
6500K – 1780 lm
| 3000K – 2055 lm
4400K – 2270 lm
6500K – 2180 lm
Lumens from chip (array): Warm White, Cool White, Daylight White
| 3000K – 1220 lm
4400K – 1300 lm
6500K – 1265 lm
| 3000K – 1810 lm
4400K – 1990 lm
6500K – 1890 lm
| 3000K – 2210 lm
4400K – 2460 lm
6500K – 2350 lm
Useful lumens (array): Warm White, Cool White, Daylight White
| 3000K – 1140 lm
4400K – 1225 lm
6500K – 1190 lm
| 3000K – 1630 lm
4400K – 1790 lm
6500K – 1690 lm
| 3000K – 1950 lm
4400K – 2160 lm
6500K – 2070 lm
Rated Wattage| 9W| 14W| 18W
Rated luminous flux
| 3000K – 1140 lm
4400K – 1225 lm
6500K – 1190 lm
| 3000K – 1630 lm
4400K – 1790 lm
6500K – 1690 lm
| 3000K – 1950 lm
4400K – 2160 lm
6500K – 2070 lm
Nominal life time of the lamp| 50,000 hrs| 50,000 hrs| 50,000 hrs
Colour temperature| 3000/4400/6500K| 3000/4400/6500K| 3000/4400/6500K
Number of switching cycles before premature lamp failure|
≥15000
|
≥15000
|
≥15000
Warm-up time up to 60% of the full light output| Instant full light| Instant
full light| Instant full light
Dimmable| No| No| No
Nominal beam angle| 120°| 120°| 120°
Rated power| 9W| 14W| 18W
Rated lamp lifetime| 50,000 hrs| 50,000 hrs| 50,000 hrs
Displacement factor| 0.97| 0.97| 0.97
Lumen maintenance factor at end of nominal life| ≥80| ≥80| ≥80
Starting time| Instant full light| Instant full light| Instant full light
Colour rendering| ≥0.8| ≥0.8| ≥0.8
Colour consistency| Within 6 step Macadam ellipse| Within 6 step Macadam
ellipse| Within 6 step Macadam ellipse
Rated peak intensity
| 3000K – 398cd
4400K – 428cd
6500K – 415cd
| 3000K – 570cd
4400K – 627cd
6500K – 592cd
| 3000K – 683cd
4400K – 754cd
6500K – 722cd
Rated beam angle| 120°| 120°| 120°
Voltage / Frequency| 220-240V~50Hz| 220-240V~50Hz| 220-240V~50Hz
Lumen efficacy
| 3000K – 131 lm / W
4400K – 141 lm / W
6500K – 137 lm / W
| 3000K – 122 lm / W
4400K – 135 lm / W
6500K – 127 lm / W
| 3000K – 114 lm / W
4400K – 126 lm / W
6500K – 121 lm / W
This product contains a Light Source of Energy Efficiency Class F
Not suitable for accent lighting
SQUARE OPAL
LED LAMP SPECIFICATIONS:| 9W| 14W| 18W
Luminaire lumens (with diffuser): Warm White, Cool White, Daylight White
| 3000K – 1080 lm
4400K – 1150 lm
6500K – 1120 lm
| 3000K – 1630 lm
4400K – 1770 lm
6500K – 1700 lm
| 3000K – 1980 lm
4400K – 2200 lm
6500K – 2070 lm
Lumens from chip (array): Warm White, Cool White, Daylight White
| 3000K – 1210 lm
4400K – 1290 lm
6500K – 1260 lm
| 3000K – 1830 lm
4400K – 1995 lm
6500K – 1900 lm
| 3000K – 2220 lm
4400K – 2470 lm
6500K – 2330 lm
Useful lumens (array): Warm White, Cool White, Daylight White
| 3000K – 970 lm
4400K – 1040 lm
6500K – 1010 lm
| 3000K – 1460 lm
4400K – 1600 lm
6500K – 1530 lm
| 3000K – 1780 lm
4400K – 1980 lm
6500K – 1870 lm
Rated Wattage| 9W| 14W| 18W
Rated luminous flux
| 3000K – 970 lm
4400K – 1040 lm
6500K – 1010 lm
| 3000K – 1460 lm
4400K – 1600 lm
6500K – 1530 lm
| 3000K – 1780 lm
4400K – 1980 lm
6500K – 1870 lm
Nominal life time of the lamp| 50,000 hrs| 50,000 hrs| 50,000 hrs
Colour temperature| 3000/4400/6500K| 3000/4400/6500K| 3000/4400/6500K
Number of switching cycles before premature lamp failure|
≥15000
|
≥15000
|
≥15000
Warm-up time up to 60% of the full light output| Instant full light| Instant
full light| Instant full light
Dimmable| No| No| No
Nominal beam angle| 120°| 120°| 120°
Rated power| 9W| 14W| 18W
Rated lamp lifetime| 50,000 hrs| 50,000 hrs| 50,000 hrs
Displacement factor| 0.97| 0.97| 0.97
Lumen maintenance factor at end of nominal life| ≥80| ≥80| ≥80
Starting time| Instant full light| Instant full light| Instant full light
Colour rendering| ≥0.8| ≥0.8| ≥0.8
Colour consistency| Within 6 step Macadam ellipse| Within 6 step Macadam
ellipse| Within 6 step Macadam ellipse
Rated peak intensity
| 3000K – 223cd
4400K – 239cd
6500K – 223cd
| 3000K – 338cd
4400K – 368cd
6500K – 353cd
| 3000K – 411cd
4400K – 456cd
6500K – 432cd
Rated beam angle| 120°| 120°| 120°
Voltage / Frequency| 220-240V~50Hz| 220-240V~50Hz| 220-240V~50Hz
Lumen efficacy
| 3000K – 120 lm / W
4400K – 128 lm / W
6500K – 124 lm / W
| 3000K – 116 lm / W
4400K – 126 lm / W
6500K – 121 lm / W
| 3000K – 110 lm / W
4400K – 122 lm / W
6500K – 115 lm / W
This product contains a Light Source of Energy Efficiency Class F
Not suitable for accent lighting
SQUARE PRISMATIC
LED LAMP SPECIFICATIONS:| 9W| 14W| 18W
Luminaire lumens (with diffuser): Warm White, Cool White, Daylight White
| 3000K – 1150 lm
4400K – 1250 lm
6500K – 1200 lm
| 3000K – 1730 lm
4400K – 1870 lm
6500K – 1830 lm
| 3000K – 2100 lm
4400K – 2360 lm
6500K – 2200 lm
Lumens from chip (array): Warm White, Cool White, Daylight White
| 3000K – 1200 lm
4400K – 1300 lm
6500K – 1260 lm
| 3000K – 1830 lm
4400K – 2000 lm
6500K – 1910 lm
| 3000K – 2220 lm
4400K – 2470 lm
6500K – 2330 lm
Useful lumens (array): Warm White, Cool White, Daylight White
| 3000K – 1100 lm
4400K – 1200 lm
6500K – 1160 lm
| 3000K – 1640 lm
4400K – 1760 lm
6500K – 1670 lm
| 3000K – 2000 lm
4400K – 2240 lm
6500K – 2100 lm
Rated Wattage| 9W| 14W| 18W
Rated luminous flux
| 3000K – 1100 lm
4400K – 1200 lm
6500K – 1160 lm
| 3000K – 1640 lm
4400K – 1760 lm
6500K – 1670 lm
| 3000K – 2000 lm
4400K – 2240 lm
6500K – 2100 lm
Nominal life time of the lamp| 50,000 hrs| 50,000 hrs| 50,000 hrs
Colour temperature| 3000/4400/6500K| 3000/4400/6500K| 3000/4400/6500K
Number of switching cycles before premature lamp failure|
≥15000
|
≥15000
|
≥15000
Warm-up time up to 60% of the full light output| Instant full light| Instant
full light| Instant full light
Dimmable| No| No| No
Nominal beam angle| 120°| 120°| 120°
Rated power| 9W| 14W| 18W
Rated lamp lifetime| 50,000 hrs| 50,000 hrs| 50,000 hrs
Displacement factor| 0.97| 0.97| 0.97
Lumen maintenance factor at end of nominal life| ≥80| ≥80| ≥80
Starting time| Instant full light| Instant full light| Instant full light
Colour rendering| ≥0.8| ≥0.8| ≥0.8
Colour consistency| Within 6 step Macadam ellipse| Within 6 step Macadam
ellipse| Within 6 step Macadam ellipse
Rated peak intensity
| 3000K – 425cd
4400K – 459cd
6500K – 447cd
| 3000K – 628cd
4400K – 675cd
6500K – 640cd
| 3000K – 767cd
4400K – 860cd
6500K – 805cd
Rated beam angle| 120°| 120°| 120°
Voltage / Frequency| 220-240V~50Hz| 220-240V~50Hz| 220-240V~50Hz
Lumen efficacy
| 3000K – 128 lm / W
4400K – 139 lm / W
6500K – 133 lm / W
| 3000K – 124 lm / W
4400K – 134 lm / W
6500K – 131 lm / W
| 3000K – 117 lm / W
4400K – 131 lm / W
6500K – 122 lm / W
This product contains a Light Source of Energy Efficiency Class E
Not suitable for accent lighting
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>