Schneider Electric PM5563 PowerLogic Power Meter Installation Guide

June 16, 2024
Schneider Electric

PowerLogic™ PM5563

PM5563 PowerLogic Power Meter

www.se.com PM5500
PM5563 power and energy meter
User manual
HRB1684301

Commercial reference
METSEPM5563
METSEPM5563RD

For California residents only
WARNING: Cancer and Reproductive Harm www.P65Warnings.ca.gov

Note: Do not use the product if it is damaged.
Contact Schneider Electric customer care representative for support (www.se.com/support).

Safety precautions

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA, CSA Z462 or applicable local standards.
  • Turn off all power supplying this device and the equipment in which it is installed before working on the device or equipment.
  • Always use a properly rated voltage sensing device to confirm that all power is off.
  • Follow guidelines in the Wiring section (5) of this document.
  • Do not exceed the device’s ratings for maximum limits.
  • Do not use this device for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.
  • Never short the secondary of a voltage transformer (VT).
  • Never open circuit a current transformer (CT).
  • Always use grounded external CTs for current inputs.
  • Do not use water or any liquid material to clean the product. Use a cleaning cloth to remove dirt. If dirt cannot be removed, contact local Technical Support representative.

Failure to follow these instructions will result in death or serious injury.

Dimensions

Mounting

Wiring

Straight-line topology only.
Loop or ring topology is not supported.

| | | |
---|---|---|---|---
I1+, I1-, I2+, I2-, I3+, I3-, I4+, I4-| 0.82 – 3.31 mm² (18 – 12 AWG)| | (PH2)| 0.9 – 1.0 N·m (8.0 – 9.0 in·lb)
V1, V2, V3, VN| 0.82 – 3.31 mm² (18 – 12 AWG)| 7 mm (0.28 in)|  (M3)| 0.5 – 0.6 N·m (4.4 – 5.3 in·lb)
L1, L2
+, -, , C| 0.05 – 3.31 mm² (30 – 12 AWG)| 6 mm (0.24 in)|  (M3)
S1+, S1-, S2+, S2-, S3+, S3-, S4+, S4 –
D1+, D1-, D2+, D2-
| VT| CT| N.O. switch
---|---|---|---
TT| TI| Interruptor normally activated
TT| TC| Commutator normalement ouvert
Voltage converter| Power converter| Switch with normally open contacts
IEC| | |
ANSI| | | |

A 500 mA fuses and disconnect switch
B Shorting block
C VT primary fuses and disconnect switch
◆ indicates wiring for a balanced system
Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the operator.
The fuses / circuit breakers must be rated for the installation voltage and sized for the available fault current.
Fuse for neutral terminal is required if the source neutral connection is not grounded.

Control power

D 500 mA fuses
L1 and L2 are non-polarized. If using an AC power supply with neutral, connect neutral to the meter’s L2 terminal.
Always use a fuse on L1. Fuse L2 when connecting an ungrounded neutral to the control power.
If using a control power transformer, fuse both primary and secondary sides of the transformer.
The fuses / circuit breakers must be rated for the installation voltage and sized for the available fault current.

Terminal covers

A Voltage terminal cover
B Voltage terminal sealing point
C Current terminal cover
D Current terminal sealing points
E Control power terminal cover
F Control power terminal sealing point

To install terminal covers:
Note: Use steel cable with 1.6 mm (1/16 in) diameter and 152.4 mm (6 in) adjustable length for sealing.

  1. Install the voltage terminal cover (A) and seal it at the sealing point (B).
  2. Install the current terminal cover (C) and seal it at the sealing points (D).
  3. Install the control power terminal cover (E) and seal it at the sealing point (F).

Description

A Voltage inputs
B Control power
C Remote display port
D Ethernet ports
E Digital outputs
F Current inputs
G Digital (status) inputs
H RS-485 comms
I Alarm / energy pulsing LED
J Heartbeat / serial comms LED
K Ethernet comms LEDs

Basic setup

Set up the Ethernet port:

  1. Disconnect your computer from the network. If your computer has wireless communications, make sure you disable the wireless network connection as well.
  2. Use an Ethernet cable to connect the computer to one of the meter’s Ethernet ports.
  3. Open a web browser and enter 169.254.0.10 in the address box.
  4. Log in to the meter webpages as a Product Master (default Username = user2, Password = pass2).
  5. Click Settings > Ethernet Settings.
  6. Modify the Ethernet setup parameters with the settings your system administrator assigned for the meter, then click Save Changes.
  7. Disconnect the computer from the meter and connect the meter’s Ethernet port to the network.

Perform basic setup:

  1. Start ION Setup.
  2. Add an Ethernet site.
  3. Add the meter to the Ethernet site using the IP address programmed above and enter the meter’s Modbus address in the Com1 ID field (default Com1 ID = 1).
  4. Open the Basic Setup screen.
  5. Edit all the meter parameters to match your power system and electrical wiring.
  6. Exit and save your settings.

Verification

Use a web browser to connect to the meter. Navigate to the real-time data screens and verify that the meter readings are correct.

Specifications

Control power
• AC: 100 to 480 V ± 10%
• Frequency: 45 to 65 Hz
• DC: 125 to 250 V DC ± 20%
• AC burden:
◦ Max. 5.0 W / 16.0 VA / 15.2 VAR at 480 V L-N
• DC burden:
◦ Typical 3.1 W at 125 V DC, max. 5 W
• Installation category III| Voltage inputs
• Measured voltage: 20 to 400 V L-N / 20 to 690 V L-L (Wye) or 20 to 600 V L-L (Delta)
• Frequency: 50/60 Hz ± 10%
• Permanent overload: 480 V L-N or 828 V L-L
• Impedance: 5 MΩ
• Uimp: 6 kV for 1.2 μs
• Measurement category III
---|---
Current inputs
• Nominal 5 A (Class 0.2S) or 1 A (Class 0.5S)
• Measured current: 50 mA to 10 A
• Withstand: 20 A continuous, 50 A @ 10 sec/hr, 500 A @ 1 sec/hr
• Impedance: < 0.3 mΩ
• Burden: < 0.024 VA at 10 A| Digital outputs
• Type: Form A
• Reference voltage: 40 V
• Maximum: 30 V AC / 60 V DC
Status inputs
• Type: Externally excited
• ON state: 30 V AC / 60 V DC max
• OFF state: 0 to 4 V DC| Environment
• -25 to 70 °C (-13 to 158 °F) operating temperature
• Humidity rating: 5% to 95% RH noncondensing, maximum dewpoint 37°C (99°F)
• Pollution degree 2
• Altitude: ≤ 3000 m
• IP30 (except connectors) (IEC 60529)
• For indoor use only.

EAC Interstate Standards

GOST 31819.21-2012
GOST 31819.23-2012

Representative Offices

Authorized suppliers:
Schneider Electric Russia
Address: 12/1 Dvintsev st., 127018 Moscow, Russia
Tel.: +7 (495) 777 99 90
Fax: +7 (495) 777 99 92
Schneider Electric Kazakhstan
Address: Dostyk ave 38, Ken Dala business center, Almaty, Kazakhstan
A25D9D1
Тel.: +7 (727) 357 23 57
Fax: +7 (727) 357 24 39

Serial Number Decoding

A Product reference code
B Model number identification code
C Running serial number for the product

China ROHS Certificate

The “Administrative Measures for the Restriction of Hazardous Substances in Electric Appliance and Electronic Products” requires this document to be shipped with all PM5563 products to the People’s Republic of China. Purchasers in other countries may disregard.

Product: PowerLogic™ PM5563 (METSEPM5563)

Part Name Hazardous Substances
(Pb) (Hg)
Metal parts O
Plastic parts O
PCBA X

This table is made according to SJ/T 11364.
O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572.
X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part is above the limit as stipulated in GB/T 26572.

Notices

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it.
Electrical equipment should be installed, operated, serviced and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
PowerLogic and Schneider Electric are trademarks or registered trademarks of Schneider Electric in France, the USA and other countries.

  • This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations.
  • If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired.
  • The safety of any system incorporating this product is the responsibility of the assembler/installer of the system.

As standards, specifications and designs change from time to time, always ask for confirmation of the information given in this publication.

Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.se.com
Schneider Electric Limited
Stafford Park 5
Telford TF3 3BL
United Kingdom
EAV91010-05
© 2022 Schneider Electric. All rights reserved.
05/2022

Documents / Resources

| Schneider Electric PM5563 PowerLogic Power Meter [pdf] Installation Guide
PM5563 PowerLogic Power Meter, PM5563, PowerLogic Power Meter, Power Meter, Meter
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals