INSTALLATION INSTRUCTIONS
A guide for qualified electricians
Pack contents:
1 x LED Panel Light
1 x Driver
Model:
600P4K
600x600mm TP(b) LED Panel With Lifud Driver
These instructions are provided as a guideline to assist you.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION AND RETAIN FOR FUTURE REFERENCE
READ THIS FIRST:
Check the pack and make sure you have all of the parts listed on the front of this booklet. If not, contact the outlet where you bought this product.
This product must be installed by a competent person in accordance with the current building and IEE wiring regulations.
As the buyer, installer and/or user of this product it is your own responsibility to ensure that this fitting is fit for the purpose for which you have intended it. Eterna Lighting cannot accept any liability for loss, damage or premature failure resulting from inappropriate use.
Switch off the mains before commencing installation and remove the appropriate circuit fuse or lock off MCB.
Disconnect the driver from the electrical supply before flash or high voltage testing.
Do not connect to a circuit which also has inductive loads connected; switching of inductive loads will generate spikes which may damage electronic components within your driver.
This unit is suitable for indoor use only.
This product is suitable for use in living areas; it is not suitable for bathroom zones 0, 1, 2, or other areas where contact with moisture is likely (see diagram opposite and current IEE Wiring Regulations for details). If being fitted in a bathroom a 30mA RCD must be used.
Bathroom Zones Diagram
This product is designed for permanent connection to fixed wiring: this must be a suitable circuit (protected with the appropriate MCB or fuse).
This product is suitable for installation on surfaces with normal flammability e.g. wood, plasterboard and masonry. It is not suitable for use on highly flammable surfaces (e.g. polystyrene, textiles).
If installing / mounting a light fitting to a plastic ceiling, you must seek advice from the ceiling manufacturer regarding the type and specification of light fittings that may be used.
Before making fixing hole(s), check that there are no obstructions hidden beneath the mounting surface such as pipes or cables.
Make sure that the fixings are strong enough to support the considerable weight of the fitting and hold it rigidly.
Do not cover the fitting with any insulating materials.
The fitting must be positioned so that there is at least 0.5m (500mm) between the LED and any illuminated surface.
Do not attach to surfaces which are damp, freshly painted or otherwise electrically conductive (e.g. metallic surfaces).
When making connections ensure that the terminals are tightened securely and that no strands of wire protrude. Check that the terminals are tightened onto the bared conductors and not onto any insulation.
This product is not intended to be used by children and persons with sensory, physical and/or mental impairments that would prevent them from using it safely.
You are advised at every stage of your installation to double-check any electrical connections you have made. After you have completed your installation there are electrical tests that should be carried out, these tests are specified in the current IEE wiring and building regulations.
EVENTUALLY, YOU MAY WANT TO REPLACE THIS PRODUCT:
Regulations require the recycling of Waste from Electrical and Electronic Equipment (European “WEEE Directive” effective August 2005—UK WEEE Regulations effective 2nd January 2007). Environment Agency Registered Producer: WEE/GA0248QZ.
WHEN YOUR PRODUCT COMES TO THE END OF ITS LIFE OR YOU CHOOSE TO REPLACE IT, PLEASE RECYCLE IT WHERE FACILITIES EXIST – DO NOT DISPOSE WITH HOUSEHOLD WASTE.
CLEANING:
Clean this fitting only with a soft dry cloth.
Do not use any chemical or abrasive cleaners.
IF YOU EXPERIENCE PROBLEMS:
If you believe your product is defective, please return it to the place where you bought it. Our Technical Team will gladly advise on any Eterna Lighting product, but may not be able to give specific instructions regarding individual installations.
LED LAMP SPECIFICATIONS:
Luminaire lumens (with diffuser) | 3600 lm |
---|---|
Lumens from chip (no diffuser) | 5500 lm |
Useful lumens | 3500 lm |
Rated Wattage | 36W |
Rated luminous flux | 3500 lm |
Nominal life time of the lamp | 35,000 hrs |
Colour temperature | 4000K |
Number of switching cycles before premature lamp failure | 15,000 |
Warm-up time up to 60% of the full light output | <2s |
Dimmable | No |
Nominal beam angle | 120° |
Rated power | 36W |
Rated lamp lifetime | 35,000 hrs |
Displacement factor | ≥0.9 |
Lumen maintenance factor at end of nominal life | ≥0.7 |
Starting time | <0.5s |
Colour rendering | ≥80 |
Colour consistency | Within a six step Macadam ellipse |
Rated peak intensity | 1150cd |
Rated beam angle | 120° |
Voltage / Frequency | 240V~50Hz |
Lumen efficacy: 100 lm / W
This product contains a Light Source of Energy Efficiency Class D
Not suitable for accent lighting
See website for more information on replacability and recycling
INSTALLATION:
Switch off the mains before commencing installation.
- Make connections to the electrical supply in accordance with the following code:
Live – Brown wire marked (L)
Neutral – Blue wire marked (N)
This product is double insulated – do not connect to earth.
- If terminal cover from input side of driver has been removed, replace terminal cover.
- Install the fitting into position within the suspended ceiling, laying the unit to rest on the T-bar section (See Fig 1. for instructions). Alternatively you can surface mount the panel using a surface mounting box ( SURFMK ).
- Suspension of the panel can be achieved by purchasing the suspension kit: SUSPACK. (See Fig 2 for instructions).
- Restore power and the unit should illuminate.
LAMP REPLACEMENT:
The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced.
FIG 1 – Ceiling Insert Of The Panel Light
FIG 2 – Ceiling Hanging Of The Panel Light
LAYOUT RESTRICTIONS ON TP(b) LIGHTING DIFFUSERS
LAYOUT RESTRICTIONS ON LIGHTING DIFFUSERS IN SUSPENDED CEILINGS
Maximum classification of lower surface| Use of space below the
diffusers| Maximum area of each diffuser panel| Max total area of
diffuser panels as percentage of floor area of the space in which the ceiling
is located| Minimum separation distance between diffuser panels
---|---|---|---|---
TP (a)| Any except protected stairway| No limit| No limit| No limit
TP (b)| Rooms| 5.sq m| 50| 3m
TP (b)| Circulation spaces except protected stairways| 5.sq m| 15| 3m