Sunricher Wall Controller SR-ZV9001T3-DIM-US Manual

June 8, 2024
SUNRICHER

Sunricher

Wall Controller

SKU: SR-ZV9001T3-DIM-US

Quickstart

This is a
secure
Wall Controller
for
U.S. / Canada / Mexico
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
1. Set primary controller/gateway into inclusion mode (Please refer to your primary controllers manual on how to turn your controller into inclusion).2. Make sure the wall controller does not belong to any Z-Wave network (please refer to the part How to check whether the wall controller included to a network of this manual).3. Short press the inclusion/exclusion button, or press and hold down ALL ON/OFF button for over 3 seconds, the wall controller will be set to inclusion mode, and waiting to be included, then LED indicator turns on and blinks 6 times quickly to indicate successful inclusion.Once the wall controller quits inclusion mode, the LED indicator will turns off. There are 3 methods for the wall controller to quit inclusion mode:1. Automatically quits after successful inclusion.2. Quits after 25 seconds timeout.3. Press and hold down ALL ON/OFF button for over 3 seconds, or short press the inclusion/exclusion button to quit.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The Wall controller is a Security Enabled Z-Wave Plus device that can both control other Z-Wave devices and activate scenes in Gateways. The wall controller can be included and operated in any Z-Wave network with other Z-Wave certified devices from other manufacturers and/or other applications. All nonbattery operated nodes within the network will act as repeaters regardless of vendor to increase reliability of the network.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Press and hold down inclusion/exclusion button for over 8 seconds, LED indicator blinks slowly to indicate successful factory reset, release inclusion/exclusion button, the wall controller will restart automatically.Note: Factory reset is not recommended for exclusion, please use this procedure only if the primary controller/gateway is missing or otherwise inoperable.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

1. Set primary controller/gateway into inclusion mode (Please refer to your primary controllers manual on how to turn your controller into inclusion).2. Make sure the wall controller does not belong to any Z-Wave network (please refer to the part How to check whether the wall controller included to a network of this manual).3. Short press the inclusion/exclusion button, or press and hold down ALL ON/OFF button for over 3 seconds, the wall controller will be set to inclusion mode, and waiting to be included, then LED indicator turns on and blinks 6 times quickly to indicate successful inclusion.Once the wall controller quits inclusion mode, the LED indicator will turns off. There are 3 methods for the wall controller to quit inclusion mode:1. Automatically quits after successful inclusion.2. Quits after 25 seconds timeout.3. Press and hold down ALL ON/OFF button for over 3 seconds, or short press the inclusion/exclusion button to quit.

Exclusion

There are two exclusion methods:Method 1: Exclusion from the primary controller/gateway as follows:1. Set the primary controller/gateway into exclusion mode (Please refer to your primary controllers manual on how to set your controller into exclusion).2. Short press the inclusion/exclusion button, or press and hold down ALL ON/OFF button for over 3 seconds, the wall controller will be set to exclusion mode, and waiting to be excluded, then LED indicator turns on and shows 3 short blinks and 1 long blink to indicate successful exclusion.Once the wall controller quits exclusion mode, the LED indicator will turns off. There are 3 methods for the wall controller to quit exclusion mode:1. Automatically quits after successful exclusion.2. Quits after 25 seconds timeout.3. Press and hold down ALL ON/OFF button for over 3 seconds, or short press the inclusion/exclusion button to quit.Method 2: Factory reset the wall controller will force the wall controller to be excluded from a network. (please refer to the part Factory Reset of this manual)

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 1| 1. Send Command Class Device Reset Locally to associated devices of this group to report factory reset information when factory reset the wall controller.2. Double click a group number of the wall controller to send command toassociated devices of this group using Command Class Central Scene.
---|---|---
2| 12| Press button u00221u0022 to activate group.1.Press and hold down button u00221u0022 to switch the associated devices with Basic Set commands.2.Press brightness value buttons(or the dim wheel around the central button) direct control of associated devices using the Multilevel Switch Set commands.3.Short press Scene button S1/S2/S3, direct control of associated devices using Scene Activation Set, Scene ID = 0x10 /0x20 / 0x30.4.Press and hold down Scene button S1/S2/S3, direct control of associated devices using Scene Conf Set, Scene ID = 0x10 / 0x20 / 0x30.
3| 12| Press button u00222u0022 to activate group.1.Press and hold down button u00222u0022 to switch the associated devices with Basic Set commands.2.Press brightness value buttons(or the dim wheel around the central button) direct control of associated devices using the Multilevel Switch Set commands.3.Short press Scene button S1/S2/S3, direct control of associated devices using Scene Activation Set, Scene ID = 0x10 / 0x20 / 0x30.4.Press and hold down Scene button S1/S2/S3, direct control of associated devices using Scene Conf Set, Scene ID= 0x10 / 0x20 / 0x30.
4| 12| Press button u00223u0022 to activate group.1.Press and hold down button u00223u0022 to switch the associated devices with Basic Set commands.2.Press brightness value buttons(or the dim wheel around the central button) direct control of associated devices using the Multilevel Switch Set commands.3.Short press Scene button S1/S2/S3, direct control of associated devices using Scene Activation Set, Scene ID = 0x10 / 0x20 / 0x30.4.Press and hold down Scene button S1/S2/S3, direct control of associated devices using Scene Conf Set, Scene ID = 0x10 / 0x20 / 0x30.

Technical Data

Hardware Platform ZM5101
Device Type Wall Controller
Network Operation Always On Slave
Firmware Version HW: 1 FW: 1.10
Z-Wave Version 6.71.01
Certification ID ZC10-18066130
Z-Wave Product Id 0x0330.0x0301.0xA109
Z-Wave Scene Type Central Scene
Firmware Updatable Updatable by Consumer by RF
Security V2 S2_UNAUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Central Scene V3
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Powerlevel
  • Security
  • Security 2
  • Supervision
  • Transport Service V2
  • Version V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic V2
  • Scene Activation
  • Scene Actuator Conf
  • Switch Multilevel V4

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

SUNRICHER User Manuals

Related Manuals