SAMSON Refrigerant Leak Monitor Kit 6CH User Guide
- June 3, 2024
- SAMSON
Table of Contents
SAMSON Refrigerant Leak Monitor Kit 6CH
FEATURES
The refrigerant Leak Monitor Kit 6CH offer an ideal solution for multipoint surveillance of machinery room and walk-in freezer rooms where refrigerant gases may be present. The kit is supplied with
- 1 x Monitoring Unit MPU6C
- 4 x Detector New MP-DS-HFC-4000 (product number: 708042)
- 1 x Red combined flash / siren FL-RL-R
- 2 x 100m halogen free cable 3×0.75mm2
Fig. 1
Functional diagram
- The monitoring unit MPU6C can be connected to up to 6 detectors. It can display operating status and alarm information independently for each channel via LEDs. They are suitable for monitoring all HFC and HFO refrigerants.
- The 4 x New MP-DS-HFC-4000 detectors are equipped with the new SEN027 Self Sense sensor. Additional 2 detectors can be purchased separately to fully utilize all channels in MPU6C if required. Once connected, they will continuously measure the gas concentration and provides an analogue signal to the central unit.
Other features include:
- User configurable Alarm time delays.
- Manual/auto alarm reset for each channel
- Built-in service function and self-test program
- Four alarm relays with 230 volts rated SPDT contacts
- Failsafe relay operation on power loss
- Audible alarm
Please Note!
MPU6 is normally supplied with default set alarm thresholds. These must be
verified or reset during commissioning. Alarm levels must always be set on
each channel for proper gas and detector type!
Default settings from factory:
Alarm level | Offset |
---|---|
Alarm C | 1,0V |
Alarm B | 2,0V |
Alarm A | 3,0V |
- Factory gas specific pre-calibration can be delivered upon request. Must be specified when ordering.
Alarm levels, factory settings are:
HFC, HFO, HCFC (ppm) | C=100 | B=1000 | A=2000 |
---|
WIRING DIAGRAMS
FUNCTION
Channel settings
After connecting each detector and applying power, the green LED on each
channel will flash as the pre-heat process commences. After approximately 4
minutes the green LED will be illuminated permanently, and the sensor is fully
operational. Each channel has one yellow and two red warning LEDs. The yellow
LED indicates a low-level gas leak (above alarm threshold C) whilst the two
red LEDs indicate gas concentrations above thresholds B and A.
When gas is detected above the respective alarm threshold the appropriate LED’s will flash until the appropriate time delay has expired when it is permanently illuminated, and the corresponding relay contacts change state. As the gas concentration subsides the LEDs and relays will return to their normal state unless the ‘manual reset’ function has been selected. The audible alarm will be initiated if it is configured with the respective alarm threshold and cannot be muted. Technicians can however inhibit the alarm by selecting ‘Service Mode’.
Central unit details
AUTO/MANUAL ALARM RESET
DIP switch (5) no3 on each channel’s control card manages the alarm reset function. “ON” enables Auto reset and “OFF” enables Manual reset, via depressing “Reset/Test/Service”-button (7).
ALARM TIME DELAY (T1)
DIP-switch (5) controls the alarm time delay for each channel.
no1 no2
- on on No alarm delay
- off on 1 minute delay
- on off 10 minutes delay
- off off 30 minutes delay
TEST MODE
By depressing the “Reset/Test/Service”-button (7) on any channel for 5 seconds
the test program is initiated. This sequentially energizes each LED and relay
at five second intervals. That the test program has started is indicated by
the fact that all LEDs on chosen channel will go out.
SERVICE MODE
Depressing the” Reset/Test/Service” button (7) for 10 seconds will inhibit all
alarm functions for the chosen channel for a period of 60 minutes. Service
mode is indicated by the fact that all LEDs on the chosen channel are
flashing. Whilst in this mode a new 60 minute inhibit period can be initiated
by repeating the process. Normal operation will be automatically resumed after
60 minutes or can be cancelled by depressing the “Reset/Test/ Service”-button
briefly.
FAULT MODE
In the event of a detector failure (GV offset < 0,1V) or disconnection of the
interconnecting wiring a fault condition will be indicated by loss of the
green ‘Active’ LED, the other LEDs start to flash and the alarm relay D is de-
energized. In the event of power failure all relays (A, B, C & D) will be de-
energized. Connections are available for an optional battery back-up to enable
total continuity of operation in the event of a power failure. A 4-hour delay
can be configured for relay D to prevent nuisance alarms. This is activated by
setting DIP switch (5) no4 on the respective channel card to ‘ON’. The
operation of the LEDs will remain unchanged.
INTERNAL BUZZER AND 24VDC AUXILIARY OUTPUT
The internal buzzer (1) and 24VDC output can be activated by the DIP-switch (4) on the terminal board and can be user configured to operate from alarm concentration A(no1), B(no2) or C(no3). Setting the DIP-switch to ON for the respective alarm level, selects the appropriate alarm level. The 24VDC auxiliary alarm output is always activated together with the buzzer. However, by removing jumper Bb (3) the buzzer can be disabled.
Please Note!
After being powered off for prolonged periods the sensor may take several
minutes to stabilize during which time ‘false’ alarms may be initiated. Such
‘false’ alarm shall disappear within a few minutes.
REMOTE DETECTORS
Sensor connection
The “MP” is a range of detectors special designed for use with the MPU units.
Detectors are available for different gases, with different measuring ranges
and in different housings to suit the actual application and environmental
requirements. Examples of gases that are possible to detect are: HFC, HCFC and
mixtures. Other detectors can be connected to MPU unit. Contact us for further
details.
Please Note!
The sensors used in the MP-series have limited selectivity and are therefore
not gas specific. Care should be taken when installing the equipment to
minimize any cross contamination from other gases or vapours.
The cable length between sensor and central unit (MPU) is max 50m.
For further guidance on specific applications contact us.
LOCATION/INSTALLATION
HFC, HFO, HCFC | H3 = 20 cm | X = 50 cm | Y = 20 cm |
---|
Fig. 8
Diagnostic tool DT300 equipped with SM300-SELF SENSE sensor.
| Alarm levels
---|---
C| B| A
Gas concentration
Refrigeration gas:| Sensor type| Nominal GV-offset
[V]
| [V] [ppm]| [V] [ppm]| [V] [ppm]
R134a| SEN 027| 0,4 V| 1,5| 100| 2,8| 1000| 3,2| 2000
R404a / R507C| SEN 027| 0,4 V| 1,5| 100| 3,3| 1000| 3,9|
2000
R407f| SEN 027| 0,4 V| 1,5| 100| 3,7| 1000| 4,2| 2000
R407C| SEN 027| 0,4 V| 1,7| 100| 3,1| 1000| 3,4| 2000
R448A / R449A| SEN 027| 0,4 V| 1,7| 100| 3,7| 1000| 4,2|
2000
R513A| SEN 027| 0,4V| 1,3| 100| 3,3| 1000| 3,8| 2000
R417a| SEN 027| 0,4 V| 1,7| 100| 3,1| 1000| 3,4| 2000
R410A| SEN 027| 0,4 V| 1,5| 100| 3,5| 1000| 3,9| 2000
R22| SEN 027| 0,4 V| 1,0| 100| 3,1| 1000| 3,8| 2000
FUNCTION CONTROL
Please Note!
Testing the system is recommended to be done once a year. A basic function
test can be made using a Service tool.
TROUBLESHOOTING
When we are troubleshooting, we recommend checking these following steps:
- Reset alarm on the test / reset-button if possible.
- Check sensor value and calibrate if necessary / possible.
- Check for possible leak.
- Age of sensor
- Last calibration date of sensor
- Possible contaminations from oil, cleaning aids, silicone, hydrogen, glue, paint
Below is an LED indication guide explaining the different indication options.
LED indication | Interpretation | Solution |
---|---|---|
All four LEDs are lit = A-alarm Green + Yellow + Red + Red | The highest |
alarm level is activated.
| Bottom three LEDs are lit = B-alarm Green + Yellow + Red| Middle alarm is
activated
-Go by the checklist.
| Bottom two LEDs are lit = C-alarm Green + Yellow| Lowest alarm level is activated
-Go by the checklist.
| Top three LEDs flashing = Fault alarm| Possible sensor fault Check sensor connections
Change the sensor if calibration isn’t possible.
| Only one red LED are lit = Fault alarm longer than 4h.| See instructions
for” Fault alarm”
| All four LEDs are flashing = Service Mode
All three relays are frozen for 60min, and no alarms will be triggered.
| Alarm blockage activated for 1h. Relays will not change position when alarm levels are triggered.
Normal mode can be activated by pressing the reset/test button once.
CLAIM/WARRANTY PROCEDURE
Before contacting SAMON for a claim, be sure to have read this guideline and most importantly tested the sensor in the correct way. As our experience is that 99% of all claims in the end is sensor related. A poisoned sensor is not granted by warranty.
SAMON offers 5 years of warranty on our products (excluding the sensor head).
If you have a problem with the product (that is not caused by the sensor) you
must contact SAMON and we will activate an RMA (Return Merchandise
Authorization).
When activating an RMA, SAMON will send out an RMA form that must be filled in
in full and be sent together with the product.
Please Note!
Products that are sent to SAMON without being registered as an RMA will not be
handled as an RMA. SAMON earns the right to refuse products that are sent
without an RMA registration.
A product that is sent to SAMON’s workshop for claim, registered as an RMA
will be checked and tested as soon as possible as SAMON’s intensions are to
minimize the standstill as much as possible for the end user.
Contact info for RMA:
RMA@samon.se
APPENDIX 1
Gas R404a / R507a
Range 0 – 4000 ppm
Gas R407f
Range 0 – 4000 ppm
Gas R407C
Range 0 – 4000 ppm
Gas R448a / R449a
Range 0 – 4000 ppm
Gas R513a
Range 0 – 4000 ppm
Gas R417a
Range 0 – 4000 ppm
Gas R410a
Range 0 – 4000 ppm
Gas R22
Range 0 – 4000 pp
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>