DELTA DVP04PT-H2 Temperature Measurement Module Instruction Manual
- June 3, 2024
- Delta
Table of Contents
- DVP04PT-H2 Temperature Measurement Module
- Product Profile & Dimensions
- External Wiring
- Electrical Specifications
- 1| O| R/W| Modes of CH1 ~ CH4| CH1 mode: b0 ~ b3 CH2 mode: b4 ~ b7 CH3 mode:
- 2| O| R/W| CH1 average time| Range of settings in CH1 to CH4: K1 to K100.
- 3| O| R/W| CH2 average time
- 4| O| R/W| CH3 average time
- 5| O| R/W| CH4 average time
- 6| X| R| Average °C temp. measured at CH1| Average Celsius temperature
- 7| X| R| Average °C temp. measured at CH2
- 8| X| R| Average °C temp. measured at CH3
- 9| X| R| Average °C temp. measured at CH4
- 12| X| R| Average °F temp. measured at CH1| Average Fahrenheit temperature
- 13| X| R| Average °F temp. measured at CH2
- 14| X| R| Average °F temp. measured at CH3
- 15| X| R| Average °F temp. measured at CH4
- 18| X| R| Present °C temp. measured at CH1| Present Celsius temperature
- 19| X| R| Present °C temp. measured at CH2
- 20| X| R| Present °C temp. measured at CH3
- 21| X| R| Present °C temp. measured at CH4
- 24| X| R| Present °F temp. measured at CH1| Present Fahrenheit temperature
- 25| X| R| Present °F temp. measured at CH2
- 26| X| R| Present °F temp. measured at CH3
- 27| X| R| Present °F temp. measured at CH4
- 30| X| R| Error status| Register for storing all error statuses. See the
- 31| O| R/W| Communication address| The RS-485 communication addresses. Range:
- 32| O| R/W| Communication format| 6 communication speeds: 4,800 bps /9,600
- 33| O| R/W| Returning to default setting| Take the setting of CH1 for
- 34| O| R| Firmware version| Displaying the current firmware version in hex;
- 35 ~ #48| For system use
- 53| #73| #93| #113| O| R/W| KP| Default = K121
- 54| #74| #94| #114| O| R/W| KI| Integral constant, Default = K2,098.
- 55| #75| #95| #115| O| R/W| KD| Derivative constant, Default = K-29.
- 56| #76| #96| #116| O| R/W| Upper limit of I value| Range: K-32,760 to
- 57| #77| #97| #117| O| R/W| Lower limit of I value| Range: K-32,760 to
- 58| #78| #98| #118| X| R| I value| Current accumulated offset value. Default
- 59| #79| #99| #119| O| R/W| Heating/cooling control| 0: Heater, 1: Cooler.
- 60| #80| #100| #120| O| R/W| Upper limit of output| Range: K-32,760 to
- 61| #81| #101| #121| O| R/W| Lower limit of output| Range: K-32,760 to
- 62| #82| #102| #122| X| R| Output percentage| Range: K0 to K1,000, Unit:
- 63| #83| #103| #123| X| R| Output width| Width of control output, Unit: ms.
- 64| #84| #104| #124| X| R| Output cycle| Cycle of control output, Unit: ms.
- 65| #85| #105| #125| X| R| Output volume| Default = K0
- 66| #86| #106| #126| X| R/W| PID_Run/Stop| 0: Stop, 1: Run. Default = K0.
- 67| #87| #107| #127| X| R/W| Auto Tune| 0: Disabled, 1: Auto-tuning Default =
- Temperature / Digital Value Curve
- Documents / Resources
Temperature Measurement Module
DVP04PT-H2
Instruction Manual
DVP04PT-H2 Temperature Measurement Module
DVP04PT-H2 is able to receive 4 points of resistance temperature detectors (PT100, PT1000, NI100, and NI1000) and convert them into 16-bit digital signals. Besides, through the user of FROM/TO instructions in DVP-EH2 MPU program, the data in DVP04PT-H2 can be read or written. There are 49 16-bit control registers (CR) in it. DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).
This sheet only provides instructions that include electrical and other
specifications as well as wiring. For more details of program design and
instructions, please refer to “DVP-PLC Application Manual: Programming”. For
any further information of peripherals, refer to “DVP-PLC Application Manual
Special Modules”
DVP04PT-H2 is an OPEN-TYPE device. It should be installed in a control cabinet
free of airborne dust, humidity, electric shock and vibration. To prevent non-
maintenance staff from operating DVP04PT-H2, or to prevent an accident from
damaging DVP04PT-H2, the control cabinet in which DVP04PT-H2 is installed
should be equipped with a safeguard. For example, the control cabinet in which
DVP04PT-H2 is installed can be unlocked with a special tool or key.
DO NOT connect AC power to any of I/O terminals, otherwise serious damage may
occur. Please check all wiring again before DVP04PT-H2 is powered up.
After DVP04PT-H2 is disconnected, Do NOT touch any terminals in a minute. Make
sure that the ground terminal ****on DVP04PT-H2 is correctly grounded in order
to prevent electromagnetic interference.
Please keep the wire as short as possible when wiring a platinum resistance
thermometer (RTD) to the controller and please route power wires as far as
possible from load wires to prevent interference and induced noise.
Make sure settings of resistance temperature detectors in CR#1 are correct, or
serious error may occur in measurements.
Product Profile & Dimensions
Unit: mm
- DIN rail (35mm)
- Connection port for extension module
- Model name
- POWER, ERROR, A/D indicator
- DIN rail clip
- Terminals
- Mounting hole
- I/O terminals
- Mounting port for extension module
I/O Terminal Layout
External Wiring
1: Wiring for analog inputs should use cables of resistive temperature sensors or double shielding cables and should be separated from other power cables that may cause interferences. To prevent the measuring results from being affected by the line resistance, use 3-wire temperature sensor. The terminals should be screwed at torque 1.95 kg-cm (1.7 in-lbs).
2: Terminal FG is the ground location for noise suppression.
*3: Connect **terminal on both the power supply module and DVP04PT-H2 to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet.
Note:** DO NOT wire empty terminals. Use 60/75°C copper conductors only.
Electrical Specifications
Power supply voltage | 24 VDC (20.4 to 28.8 VDC) (-15 to +20%) |
---|---|
Analog output channel | 4 channels/module |
Applicable sensors | 3-WIRE PT100 / NI100 / PT1000 / NI1000 3850 PPM/°C (DIN |
43760 JIS C1604-1989)
Current excitation| 1.53 mA/200 μA
Range of input temp.| See the table in “Temperature/Digital Value Curve”
section.
Range of digital conversion| See the table in “Temperature/Digital Value
Curve” section.
Resolution| 0.1°C/0.18°F*1
Output impedance| 0.5Ω or less
Overall accuracy| ±0.6% when in full scale within the range of 0 to 55°C, 32
to 131°F
Response time| 400 ms × number of channels
Isolation| Isolation between digital circuits and analog circuits. 500 VDC
between digital circuits and ground
500 VDC between analog circuits and ground
500 VDC between analog circuits and digital circuits 500 VDC between 24 VDC
and ground
Format of digital data| 15 significant bits out of 16 bits are available; in
2’s complement
Average function| Provided; available for setup in CR#2 to CR#5; Range: K1 to
K100
Self-diagnosis| Upper and lower bound detection/channel
Communication mode (RS-485)| Supported, including ASCII/RTU mode. Default
communication format: 9600, 7, E, 1, ASCII; refer to CR#32 for details on the
communication format.
Note1: RS-485 cannot be used when connected to PLC CPUs. Note2: Use extension
module wizard in ISPSoft to search or modify the control register (CR) in the
modules.
Serial connection with DVP-PLC MPU| The modules are numbered from “0 to 7”
automatically by their distance from MPU. 0 is the closest to MPU and 7 is the
furthest. Maximum 8 modules are allowed to connect to the PLC and will not
occupy any digital I/O points.
*1: The unit of temperature would be displayed as 0.1°C/0.1°F. If the temperature unit is set to be Fahrenheit, the second decimal place would not be shown.
Other Specifications
Power supply
Max. rated power consumption| 24 VDC (20.4 to 28.8 VDC) (-15 to +20%), 2.5 W
supplied by external power.
Environment
Operation/storage| 1. Operation: 0 to 55°C (temperature), 5 to 95%
(humidity), pollution degree 2
2. Storage: -25 to 70°C (temperature), 5 to 95% (humidity)
Vibration/shock immunity| Standard: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Control Register
CR# | Attrib. | Content | Explanation |
---|---|---|---|
#0 | O | R | Model name |
You can read the model name from the program and see if the module exists.
1| O| R/W| Modes of CH1 ~ CH4| CH1 mode: b0 ~ b3 CH2 mode: b4 ~ b7 CH3 mode:
b8 ~ b11 CH4 mode: b12 ~ b15
Take setting up (b3, b2, b1, b0) of CH1 for example (Default = H’0000):
1. (0, 0, 0, 0): PT100
2. (0, 0, 0, 1): NI100
3. (0, 0, 1, 0): PT1000
4. (0, 0, 1, 1): NI1000
5. (0, 1, 0, 0): 0 to 300Ω
6. (0, 1, 0, 1): 0 to 3,000Ω
7. (1, 1, 1, 1): Disabled
2| O| R/W| CH1 average time| Range of settings in CH1 to CH4: K1 to K100.
Default =K10.
Please note that the average times set in CR#2 to CR#5 can only be written in
once.
3| O| R/W| CH2 average time
4| O| R/W| CH3 average time
5| O| R/W| CH4 average time
6| X| R| Average °C temp. measured at CH1| Average Celsius temperature
measured at CH1 ~ CH4.
Unit: 0.1°C
7| X| R| Average °C temp. measured at CH2
8| X| R| Average °C temp. measured at CH3
9| X| R| Average °C temp. measured at CH4
CR#6 to CR#9 are the average Celsius temperatures measured at CH1 to CH4 obtained from the average time settings in CR#2 ~ CR#5.
12| X| R| Average °F temp. measured at CH1| Average Fahrenheit temperature
measured at CH1 ~ CH4.
Unit: 0.1°F
13| X| R| Average °F temp. measured at CH2
14| X| R| Average °F temp. measured at CH3
15| X| R| Average °F temp. measured at CH4
CR#12 to CR#15 are the average Fahrenheit temperatures measured at CH1 to CH4
obtained from the average time settings in CR#2 to CR#5.
CR#| Attrib.| Content| Explanation
---|---|---|---
18| X| R| Present °C temp. measured at CH1| Present Celsius temperature
measured at CH1 ~ CH4.
Unit: 0.1°C
19| X| R| Present °C temp. measured at CH2
20| X| R| Present °C temp. measured at CH3
21| X| R| Present °C temp. measured at CH4
24| X| R| Present °F temp. measured at CH1| Present Fahrenheit temperature
measured at CH1 ~ CH4.
Unit: 0.1°F
25| X| R| Present °F temp. measured at CH2
26| X| R| Present °F temp. measured at CH3
27| X| R| Present °F temp. measured at CH4
30| X| R| Error status| Register for storing all error statuses. See the
table of error status for more information.
31| O| R/W| Communication address| The RS-485 communication addresses. Range:
01 to 254, Default = K1.
32| O| R/W| Communication format| 6 communication speeds: 4,800 bps /9,600
bps /19,200 bps / 38,400 bps /57,600 bps /115,200 bps. Data formats include:
ASCII: 7, E, 1/ 7,O,1 / 8,E,1 / 8,O,1 / 8,N,1 / 7,E,2 /7,O,2 / 7,N,2 / 8,E,2 /
8,O,2 / 8,N,2
RTU: 8, E, 1 / 8,O,1 / 8,N,1 / 8,E,2 / 8,O,2 / 8,N,2 Default:
ASCII,9600,7,E,1(CR#32=H‘0002)
Please refer to✽CR#32 at the bottom of the page for more details.
33| O| R/W| Returning to default setting| Take the setting of CH1 for
example: b0: Reserved, b1: Reserved When b2 is set to 1, all settings will
return to default ones.
Definitions of ERR LED: (Default of b12 to b15 = 1111)
1. When b12 = 1 and CH1 wired to empty external contact, ERR LED will flash.
2. When b13 = 1 and CH2 wired to empty external contact, ERR LED will flash.
3. When b14 = 1 and CH3 wired to empty external contact, ERR LED will flash.
4. When b15 = 1 and CH2 wired to empty external contact, ERR LED will flash.
34| O| R| Firmware version| Displaying the current firmware version in hex;
e.g. version 1.0A is indicated as H’010A
35 ~ #48| For system use
Symbols: O: Latched, X: Non-latched
R: Able to read data by using FROM instruction or RS-485 communication. W:
Able to write data by using TO instruction or RS-485 communication.
✽Reset Module (Firmware V4.06 or above): Having connected the external power
24V, write the reset code H’4352 for CR#0, then disconnect and reboot to
complete the setup.
✽CR#32 Communication Format Setting:
– Firmware V4.04 (and lower): Data format (b11~b8) is not available, ASCII
format is 7, E, 1 (code H’00xx), RTU format is 8, E, 1 (code H’C0xx/H’80xx).
– Firmware V4.05 (and higher): Refer to the following table for setup. For new
communication format, please take note that modules in the original code
H’C0xx/H’80xx is changed to 8E1 for RTU.
b15 ~ b12 | b11 ~ b8 | b7 ~ b0 |
---|---|---|
ASCII/RTU & High/Low Bit Exchange of CRC | Data Format | Communication Speed |
Description
H’0| ASCII| H’0| 7,E,11| H’6| 7,E,21| H’01| 4800 bps
H’8| RTU, No High/Low Bit Exchange of CRC| H’1| 8,E,1| H’7| 8,E,2| H’02| 9600
bps
H’2| –| H’8| 7,N,21| H’04| 19200 bps
H’C| RTU, High/Low Bit Exchange of CRC| H’3| 8,N,1| H’9| 8,N,2| H’08| 38400
bps
H’4| 7,O,11| H’A| 7,O,2*1| H’10| 57600 bps
H’5| 8.O,1| H’B| 8,O,2| H’20| 115200 bps
ex: To setup 8N1 for RTU (High/Low Bit Exchange of CRC), communication speed
is 57600 bps, write H’C310 in CR #32.
Note *1. Supports ASCII mode ONLY.
▲ CR#0 ~ CR#34: The corresponding parameter addresses H’4064 ~ H’4086 are for users to read/write data by RS-485 communication. When using RS-485, you have to first separate the module from the PLC MPU.
- Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data into register).
- The latched CR should be written by RS-485 communication to stay latched. The CR will not be latched if written by MPU through TO/DTO instruction; however, when using TO/DTO instruction to modify the PID control registers, all latched CR will stay latched.
CR#30: Error status
Error status| Value| b15 ~ b12| b11| b10| b9| b8| b7| b6| b5| b4| b3| b2| b1|
b0
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Abnormal power supply| K1
(H’1)| Reserved| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 1
Wired to empty external contact| K2
(H’2)| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 1| 0
Incorrect mode setting| K4
(H’4)| 0| 0| 0| 0| 0| 0| 0| 0| 0| 1| 0| 0
OFFSET/GAIN error| K8
(H’8)| 0| 0| 0| 0| 0| 0| 0| 0| 1| 0| 0| 0
Memory self-test fail| K16
(H’10)| 0| 0| 0| 0| 0| 0| 0| 1| 0| 0| 0| 0
Abnormal digital range| K32
(H’20)| 0| 0| 0| 0| 0| 0| 1| 0| 0| 0| 0| 0
Incorrect average times setting| K64
(H’40)| 0| 0| 0| 0| 0| 1| 0| 0| 0| 0| 0| 0
Instruction error| K128
(H’80)| 0| 0| 0| 0| 1| 0| 0| 0| 0| 0| 0| 0
CH1 wired to empty external contact| K256 (H’100)| 0| 0| 0| 1| 0| 0| 0| 0| 0|
0| 0| 0
CH2 wired to empty external contact| K512 (H’200)| 0| 0| 1| 0| 0| 0| 0| 0| 0|
0| 0| 0
CH3 wired to empty external contact| K1024 (H’400)| 0| 1| 0| 0| 0| 0| 0| 0| 0|
0| 0| 0
CH4 wired to empty external contact| K2048 (H’800)| 1| 0| 0| 0| 0| 0| 0| 0| 0|
0| 0| 0
Note: Each error status is determined by the corresponding bit (b0 ~ b11)
and there may be more than 2 errors occurring at the same time. 0 = normal; 1
= error.
PID Control Registers
CR# | Latched | Content | Explanation |
---|---|---|---|
CH1 | CH2 | CH3 | CH4 |
#51 | #71 | #91 | #111 |
#52 | #72 | #92 | #112 |
= K2.
53| #73| #93| #113| O| R/W| KP| Default = K121
54| #74| #94| #114| O| R/W| KI| Integral constant, Default = K2,098.
55| #75| #95| #115| O| R/W| KD| Derivative constant, Default = K-29.
56| #76| #96| #116| O| R/W| Upper limit of I value| Range: K-32,760 to
K32,760
Default = K0.
57| #77| #97| #117| O| R/W| Lower limit of I value| Range: K-32,760 to
K32,760
Default = K0.
58| #78| #98| #118| X| R| I value| Current accumulated offset value. Default
= K0.
59| #79| #99| #119| O| R/W| Heating/cooling control| 0: Heater, 1: Cooler.
Default = K0.
60| #80| #100| #120| O| R/W| Upper limit of output| Range: K-32,760 to
K32,760
Default = K4,000.
61| #81| #101| #121| O| R/W| Lower limit of output| Range: K-32,760 to
K32,760
Default = K0. .
62| #82| #102| #122| X| R| Output percentage| Range: K0 to K1,000, Unit:
0.1%. Default = K0.
63| #83| #103| #123| X| R| Output width| Width of control output, Unit: ms.
Default = K0.
64| #84| #104| #124| X| R| Output cycle| Cycle of control output, Unit: ms.
Default = K0.
65| #85| #105| #125| X| R| Output volume| Default = K0
66| #86| #106| #126| X| R/W| PID_Run/Stop| 0: Stop, 1: Run. Default = K0.
67| #87| #107| #127| X| R/W| Auto Tune| 0: Disabled, 1: Auto-tuning Default =
K0.
✽ The CR#51 ~ CR#127 listed above do not support RS-485 read/write.
✽ When using TO/DTO instruction to modify PID control registers, latched CR
and PID control registers will stay latched.
Temperature / Digital Value Curve
Temperature Measurement Mode (°C/°F):
Thermo couple | Range of input temperature | Range of digital conversion |
---|---|---|
°C (Min. / Max.) | °F (Min. / Max.) | °C (Min. / Max.) |
PT100 | -180 to 800°C | -292 to 1,472°F |
--- | --- | --- |
NI100 | -80 to 170°C | -112 to 338°F |
PT1000 | -180 to 800°C | -292 to 1,472°F |
NI1000 | -80 to 170°C | -112 to 338°F |
300 Ω | 0 to 300 Ω | K0 to K30,000 |
3k Ω | 0 to 3,000 Ω | K0 to K30,000 |
DVP-0070530-02
20220112