BELL lighting 09094V2 Spectrum High Powered Emergency Bulkhead Installation Guide

September 23, 2024
BELL lighting

BELL lighting 09094V2 Spectrum High Powered Emergency Bulkhead

Specification

  1. Operating environmental temp: O to +55 °c.
  2. Operating relative humidity: less than 90%.
  3. Rated voltage: 220-240V 50/60Hz.
  4. Wattage: 10W.
  5. Conversion time: 1 second.
  6. LED:SMT 2835LED*42pcs.
  7. Lumens: 1200lm.
  8. Emergency duration: more than 180 minutes.
  9. Battery installed or replaced: LiFePO4 3.2V 12000mAh
  10. Recharge time: 24 hours.

Important Information

We recommend that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building control.

  • All tests should be carried out in accordance to EN 50172:2004.
  • BELL will not accept responsibility for any claims arising from a poor installation.
  • The light source of this luminaire is not replaceable: when the light source reaches end of life, the whole luminaire must be replaced.

Important User Advice

  • The ambient room temperature should not exceed 30°C.
  • Ensure that there is adequate free air ventilation around the fitting.
  • Always switch off mains supply before installing.

Installation Instructions : High Power Emergency Bulkhead (09094V2)

Read these instructions before installation and retain for future reference
This equipment should be installed by a competent electrician

Installation

  1. Connect mains supply wiring as follows:
  2. Power line & battery wires should be connected securely, and all screws fixed.
  3. Switch on 220-240V AC supply and check if the green LED indicator illuminates to confirm charging of batteries.
  4. Allow a short period for part charging of the batteries and then isolate the mains supply to the fitting in order to check the correct operation of the fitting in emergency mode. In the first use, after a continuous charge for 24 hours, a mains failure should be simulated to ensure that the fitting works for its specified time (only at a safe & appropriate time). The fitting will be fully charged with 24 hours continuous charging.

The instruction of the switch on PCB. On indicates standard mode.
1 indicates self-test mode.
Please make sure that switch position is set before installation.

RECOMMENDED ROUTINE TEST PROCEDURE
The following tests are designed to ensure the continued protection of your premises and occupants. Because of the possibility of a failure of the normal lighting supply occurring shortly after a period of testing, all tests should, whenever possible, be undertaken at times of least risk, e.g. during daylight hours.

ONCE ADAY
Visual inspection of battery charge led.

ONCE A MONTH
Each unit should be energised from it’s battery for adequate time to ensure, by simulation of a failure of the normal lighting supply, the emergency mode is functioning correctly.

ONCE EACH YEAR
All units should be placed into emergency mode and checked that the duration provided by the battery meets the specified time period.

This product may contain substances that can be hazardous to the environment if not disposed of properly. Electrical and electronic equipment should never be disposed of with general household waste
but must be separated for its correct treatment and recovery.
Where possible recycle your packaging.

Self-Test

  • Self-Test fittings perform a self-commissioning test at first power on. After charging for 24 hours a full duration test (3 hours) is performed. Initial function and duration tests are randomly generated. They are then performed in accordance with standard requirements (every 30 days for function tests and every 52 weeks for duration tests).
  • A single bi-colour indicator LED is fitted in all Seit-Test products. This LED is clearly visible for manual inspection. It indicates the module status. The LED shows permanent green or flashing green when conditions are normal and flashing red if a fault condition is present

Function test

  • A function test is a 2 minutes test that simulates a mains failure and checks the operation of the emergency light source from the battery supply.
  • The local indicator LED slow flashes green whilst the 2 minutes function test is in progress.
  • If there is a failure during a function test the local indicator LED changes to a flashing red.

Duration test

  • A duration test simulates a mains failure. It also checks the operation of the emergency light source from the battery supply for the rated duration of the module.
  • The local indicator LED fast flashes green whilst the duration test is in progress.
  • If there is a failure during a duration test the local indicator LED either changes to flashing red. The battery is required to be fully charged before a duration test can be started.

The test button of the unit has the following functions:

Please refer to following chart below for more complete description/fault indication:

Conducting additional manual tests of self-test fittings may significantly reduce battery life

British Electric Lamps Ltd
BELL House, Foxbridge Way, Normanton Industrial Estate Normanton. West Yorkshire. WF6 1TN

T: +44 (0)1924 893380
F: +44 (0)1924 894320
E: sales@belllighting.co.uk
www.belllighting.co.uk

Technical Helpline +44 (0)1924 893380 www.belllighting.co.uk

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals