BELL lighting 08747 Panel Emergency Pack Installation Guide
- September 2, 2024
- BELL lighting
Table of Contents
BELL lighting 08747 Panel Emergency Pack
Read these instructions before installation and retain for future reference
This equipment should be installed by a competent electrician
Important Information
We recommend that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building control.
- All tests should be carried out in accordance to EN 50172:2004.
- BELL will not accept responsibility for any claims arising from a poor installation.
Important User Advice
- Always switch off mains supply before installing.
- Operating Temperature 0°C to +35°C.
- Do not cover with any insulation.
This product may contain substances that can be hazardous to the environment
if not disposed of properly. Electrical and electronic equipment should never
be disposed of with general household waste but must be separated for its
correct treatment and recovery.
Where possible recycle your packaging.
Features
- Output power: 2.5W/3.5W/5W
- Insulation Class: II
- Ingress Protection: IP20
- Emergency Duration: 1.5-3hours
- Battery Recharge Time: 16h
- Deep Discharge Protection DDP
Battery Replacement Steps
- Open the top cover first
- Take out the battery
- Replace the battery
- Replace the cover
Note:
- The battery should be changed when the required duration is not reached
- The battery is replaceable
- DO NOT cover with insulation
Specifications
Battery Discharge & Charge Specification
General Specification
- Rated supply voltage 220-240VAC
- Mains frequency 50/60Hz
- Ambient temperature ta 0°C ~ +35°C
- Max. Casing temperature tc 60°C
Item Code| Batteries| Emergency Power| Emergency Duration|
Charge Current| Charge Time
---|---|---|---|---|---
EEC30-2.5W-3H| 6.4V/1500mAhLiFePO4 battery| 2.5W| 3h| 200mA± 10%| 16h
Wiring Diagram
The output current of LED driver is under 1.5A
The LED indicator light will not light if:
- Mains power off, the light goes into emergency mode
- Battery is disconnected when mains power on
- Battery connected with mains power on (Attention: Please re-connect the battery with mains power off, and then re-set the AC mains power)
Mechanical Outline
unit: mm
Note: EEC30EL/H-BS/ST can switch functions through the DIP switch.
- Step 1: Before you switching the BS/ST function, please disconnect the L/N and battery cable.
- Step 2: Switch the product mode through the switch indicated by the arrow.
- Step 3: Turn the switch down to switch the product to standard mode.
- Step 4: Turn the switch up to switch the product to self-test mode.
Notice:
- The function switching shall only be operated after L/N and battery cable are disconnected.
Indicator LED System
Indicator LED System status is by a bi-color indicator LED
Notice
- Once the error has been corrected reconnect the battery and then re apply the mains power.
- The indicator LED will switch back to green with the mains power on.
- After exchanging the battery hold down the test button for 10 seconds and the indicator LED will switch to Green.
Testing/Commissioning
Testing/Commissioning(self test)
Functionality of the test button
- A short press (>1s) on the button start a function test lasting 5 seconds (The battery’s capacity should be more than 5% = charging 30mins
- Holding down the button(>10s) resets the timer(System-reset)
Function test
- The 5 second long, each 7 days’ function test serves to check the functionality of the emergency unit, the batteries and LED module.
Notice
If a mains supply failure occurs while a function test is in progress, the test will be postponed and the system will enter emergency operation. Following restoration of the mains supply, a postponed functional test will re-commence automatically as soon as conditions permit.
Duration Test
- First test: After 24 hours of AC mains power input, the emergency lighting unit will enter into a 3-hour duration test.
- Half year duration test: Conduct 3-hour duration test every 180-182 days to check the battery capacity.
Notice
- A duration test will only be started when the battery supply is fully charged. If a mains supply failure occurs while a duration test is in progress, the test will be postponed and the system will enter emergency operation. Following the restoration of the mains supply, the postponed duration test will re-commence automatically when the battery supply is fully recharged.
- The indicator will be slow flashing Green for 5 days if the duration test is carried out successfully.
FAQ
- Q: When should the battery be replaced?
- A: The battery should be replaced when the required emergency duration is not being met.
- Q: What should be done if the LED indicator light does not turn on?
- A: If the LED indicator light does not turn on, check for mains power status, battery connection, and follow the re-connection instructions provided in the manual.
- Q: Can the product be recycled?
- A: Where possible, recycle the packaging of the product to minimize environmental impact.
Contacts
- Technical Helpline +44 (0)1924 893380
- www.belllighting.co.uk