BELL Lighting 08710 Arial Stand-Alone Emergency Pack Instructions

June 9, 2024
BELL lighting

08710 Arial Stand-Alone Emergency Pack
Instruction Manual

Read these instructions before installation and retain for future reference
This equipment should be installed by a competent electrician

BELL Lighting 08710 Arial Stand-Alone Emergency Pack

Battery replacement steps:

  1. Open the top cover first
  2. Take out the battery
  3. replace the battery
  4. Replace the cover

Note:
The battery should be changed when the required duration is not reached The battery is replaceable DO NOT cover with insulation

Important Information

We recommend that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building  control.

  • All tests should be carried out in accordance to EN 50172:2004.
  • BELL will not accept responsibility for any claims arising from a poor installation. Important User Advice
  • Always switch off mains supply before installing.
  • Operating Temperature 0°C to +35°C.
  • Do not cover with any insulation.

This product may contain substances that can be hazardous to the environment if not disposed of properly. Electrical and electronic equipment should never be disposed of  with general household waste but must be separated for its correct treatment and recovery.
Where possible recycle your packaging.


Features

Output power :2.5W/3.5W/5W
Insulation Class: II
Ingress Protection:IP20
Emergency Duration: 1.5-3hours
Battery Recharge Time: 16h
Deep Discharge Protection DDP

Battery Discharge & Charge Specification

Parameter Min. Typ. Max. Note
Battery discharge current 300mA 400mA * Measured at 6.4V input from

batteries and ” EM 2.5W”
Output voltage| 10Vdc| –| 90Vdc
Output constant current| 13mA| –| 185mA
Emergency power| 2W| –| 2.6W
Parameter| Min.| Typ.| Max.| Note
---|---|---|---|---
Battery discharge current| 500mA| –| 610mA| Measured at 6.4V input from
batteries and ” EM 3.5W”
Output voltage| 10Vdc| –| 90Vdc
Output constant current|  30mA| –| 250mA
Emergency power| 3.3W| –| 3.9W
Parameter| Min.| Typ.| Max.| Note
---|---|---|---|---
Battery discharge current| 700mA| –| 820mA|
Measured at 6.4V input from
batteries and ” EM 5W”
Output voltage| 10Vdc| –| 90Vdc
Output constant current|  34mA| –| 380mA
Emergency power| 4.6W| –| 5.2W

General Specification

Rated supply voltage 220-240VAC
Mains frequency 50/60Hz
Ambient temperature ta 0°C ~ +35°C
Max. Casing temperature tc 60°C
Item Code Batteries
Power Emergency
Duration Charge
Current Charge

Time
---|---|---|---|---|---
EEC30-2.5W-3H| 6.4V/1500mAhLiFePO4 battery| 2.5W| 3h|  200mA± 10%| 16h
EEC30-3.5W-2H| 6.4V/1500mAhLiFePO4 battery| 3.5W| 2h|  200mA± 10%| 16h
EEC30-5W-1.5H| 6.4V/1500mAhLiFePO4 battery| 5W| 1.5h|  200mA± 10%| 16h

BELL Lighting 08710 Arial Stand-Alone Emergency Pack - Figure
1

Wiring Diagram

The output current of LED driver is under 1.5A
The LED indicator light will not light if:

  1. Mains power off, the light goes into emergency mode
  2. Battery is disconnected when mains power on
  3. Battery to be connected with mains power on (Attention: Please re-connect the battery with mains power off, and then re-set the AC mains power)

BELL Lighting 08710 Arial Stand-Alone Emergency Pack - Figure
2

British Electric Lamps Ltd
Unit A Foxbridge Way, Normanton Industrial Estate
Normanton, West Yorkshire. WF6 1TN

T: +44 (0)1924 893380
F: +44 (0)1924 894320
E:sales@belllighting.co.uk
www.belllighting.co.uk

Documents / Resources

| BELL Lighting 08710 Arial Stand-Alone Emergency Pack [pdf] Instructions
08710 Arial Stand-Alone Emergency Pack, 08710, Arial Stand-Alone Emergency Pack, Alone Emergency Pack, Emergency Pack
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals