BELL Lighting 09126 Spectrum 2W Emergency Down Light Installation Guide

September 3, 2024
BELL lighting

09126 Spectrum 2W Emergency Down Light

“`html

Product Information:

Specifications:

  • Model: LED IP20
  • Material: LiFePO4
  • Installation: Surface mounted or recess mounted
  • Dimensions: 97.8mm x 97.8mm
  • Technical Helpline: +44 (0)1924 893380
  • Website: www.belllighting.co.uk
  • Manufacturer: British Electric Lamps Ltd
  • Address: BELL House, Foxbridge Way, Normanton Industrial
    Estate, Normanton, West Yorkshire. WF6 1TN

Product Usage Instructions:

Mounting Options:

Surface mounted product installation:

  1. Drill out installation holes according to dimensions shown in
    the diagram.

  2. Using wall plugs and screws, affix the surface mounted fittings
    to the wall/ceiling.

  3. Wire up the luminaire, insert it into the surface mounted
    accessory in the direction indicated by the arrow to complete the
    installation.

Recess mounted product installation:

  1. Aperture for recessed mounting: 75-90mm

  2. Wire up the luminaire, push the spring on each side upward as
    shown in the diagram.

  3. Insert luminaire into the aperture to complete the
    installation.

Changing the Lens:

  1. Turn the bezel anticlockwise to remove the bezel.
  2. Carefully pry out the lens.
  3. Replace with alternative lens.
  4. Replace the bezel by rotating it clockwise to affix into
    place.

Changing the Battery:

  1. Push the side cover upwards and remove it in the direction
    indicated by the arrow.

  2. Remove the old battery and replace, ensuring correct polarity
    is maintained.

  3. Replace the side cover.

Frequently Asked Questions (FAQ):

Q: What should I do if a mains supply failure occurs during a

functional test?

A: The test shall be postponed, and the system
will enter emergency operation. Following restoration of the mains
supply, a postponed functional test shall re-commence automatically
as soon as conditions permit.

Q: When will a duration test start?

A: A duration test will only be started once
the battery is fully charged. If a mains supply failure occurs
during a duration test, the test shall be postponed, and the system
shall enter emergency operation. Following restoration of the mains
supply, a postponed duration test shall re-commence automatically
once the battery is fully recharged. The indicator will be slow
flashing Green for 5 days once the duration test has been carried
out successfully.

“`

LED IP20

Important Information

LiFePO4

We recommend that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building control.

· All tests should be carried out in accordance to EN 50172:2004.

· BELL will not accept responsibility for any claims arising from poor installation.

· The light source of this luminaire is not replaceable, when the light source reaches end of life, the whole luminaire must be replaced.

Important User Advice

· The ambient room temperature should not exceed 35°C.

· Ensure that there is adequate free air ventilation around the fitting.

· Always switch off mains supply before installing.

Specification 1. Supply Voltage: 220-240VAC 50/60Hz 2. Ambient Room Temperature: 0 to 35°C 3. Insulation Class: II 4. Ingress Protection: IP20 5. Battery Recharge Time: 24 hours 6. Wattage: 1.2W 7. Emergency duration: more than 3 hours 8. Lumens: 150lm (Open), 110lm (Corridor) 9. Battery installed: LiFePO4 3.2V 1500mAh 10. Deep Discharge Protection DDP 11. Non-maintained Operation

unit:mm

97.8

97.8

unit:mm

Installation Instructions: 09126

Read these instructions before97.8installation and retain for future reference 97.8
This equipment should be installed by a competent eLElDecItP2r0ician

Wiring Diagram Connections

LiFePO4

Connections

97.8

97.8

Date

Revision

1.3.2024

1

97.8

97.8

Selecting the test mode: Step 1: Switch the product mode using the switch shown by the arrow. Step 2: Push switch to the left to switch the product mode to manual test mode.
Mounting Options
Step 3: Push switch to the right to switch the product mode to self-test mode

Mounting Options

Changing the lens: Step 1: Turn the bezel anticlockwise to remove the bezel. Step 2: Carefully pry out the lens. Step 3: Replace with alternative lens. Step 4: Replace the bezel by rotating it clockwise to affix into place.
Changing the battery: Step 1: Push the side cover upwards and remove it in the direction indicated by the arrow. Step 2: Remove the old battery and replace, ensuring correct polarity is maintained. Step 3: Replace the side cover.

Surface mounted product installation:

Step 1: Drill out installation holes according to dimensions shown in the diagram.

50.8

Step 2: Using wall plugs and screws, affix the surface mounted fittings to the wall/ceiling.

Step 3: Wire up the luminaire, insert it into the surface mounted accessory in the direction indicated by the arrow to complete the installation..

Recess mounted product installation: Step 1: Aperture for recessed mounting: 75-90mm Step 2: Wire up the luminaire, push the spring on each side upward as shown in the diagram. Step 3: Insert luminaire into the aperture to complete the installation

50.8

75.00

75.00

Technical Helpline +44 (0)1924 893380
www.belllighting.co.uk

British Electric Lamps Ltd BELL House, Foxbridge Way, Normanton Industrial Estate
Normanton, West Yorkshire. WF6 1TN
T: +44 (0)1924 893380 F: +44 (0)1924 894320 E: sales@belllighting.co.uk
www.belllighting.co.uk

Installation Instructions: 09126
Read these instructions before installation and retain for future reference This equipment should be installed by a competent electrician

Date 1.3.2024

Revision 1

Functionality of the test switch
· A short press (1s) on the button starts a function test lasting 5 seconds.
· Holding down the button (>10s) resets the timer (System reset)
Functional test ­ Self-test Mode
· The functional test lasts for 5 seconds and occurs every 7 days, to check the functionality of the emergency unit, the batteries and LED module.
Please note: If a mains supply failure occurs while a functional test is in progress, the test shall be postponed, and the system will enter emergency operation. Following restoration of the mains supply, a postponed functional test shall re-commence automatically as soon as conditions permit.
Duration test ­ Self-test Mode
· 24 hours after installation, a 3-hour duration test is performed.
· 3 hour duration tests are performed every 180 – 182 days to check the battery capacity.
Please note: A duration test will only be started once the battery is fully charged and if a mains supply failure occurs while a duration test is in progress, the test shall be postponed, and the system shall enter emergency operation. Following restoration of the mains supply, a postponed duration test shall re-commence automatically once the battery is fully re-charged.
The indicator will be slow flashing Green for 5 days once the duration test has been carried out successfully.

Indicator LED System status is by the bi-colour indicator LED.

LED Indication Permanent Green Fast flashing Green (0 .25s on 0 .25s off) Slow flashing Green (1s on 1s off) Permanent Red Fast flashing Red (0 .25s on 0 .25s off) Slow flashing Red (1s on 1s off) Green and Red off

Status Standby, System OK Function test underway Duration test underway Lamp failure Battery capacity failure Battery fault Battery Operation

Description Mains operation, battery is charged Function test underway Duration test underway Open Circuit or Short circuit or LED failure Battery failed duration test Incorrect battery voltage or Short circuit or OpenCircuit Emergency mode: Mains disconnected or Mains failure

Please note: · Fault status: If an error is detected, the indicator LED switches to RED. Once the error has been corrected, after re-connecting the battery with
the mains power disconnected, the indicator LED will switch back to GREEN when mains power is re-applied . · Battery failed duration test: After an exchange of the battery and holding down the button (>10S) to reset the timer, the indicator LED will switch
to GREEN · Always select the desired test mode before applying the power. Do not switch test mode whilst the luminaire is powered. · If Self-test mode is selected, additional Manual tests are not required and if performed, will cause premature failuunreit:omfmthe battery.
97.8
This product may contain substances that can be hazardous to the eunnviitr:omnmment if not disposed of prop9e7rl.y8. Electrical and electronic equip9m7.8ent should never be disposed of with general household waste but must be separated for its correct treatment and recovery. Where possible recycle your packaging.

LED IP20

97.8

97.8

97.8

LED IP20

LiFePO4

Connections

LiFePO4
Technical Helpline +44 (0)1924 893380
www.belllighting.co.uk

Connections
British Electric Lamps Ltd BELL House, Foxbridge Way, Normanton Industrial Estate
Normanton, West Yorkshire. WF6 1TN
T: +44 (0)1924 893380 F: +44 (0)1924 894320 E: sales@belllighting.co.uk
www.belllighting.co.uk

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals