JADE RXRD-01MCDAM3 Vertical Airflow Economizers Instruction Manual
- September 16, 2024
- jade
Table of Contents
- RXRD-01MCDAM3 Vertical Airflow Economizers
- Specifications:
- Product Usage Instructions:
- Step 1: Inspecting Contents
- Step 2: Removing Panels
- Step 3: Relocating Sensors
- Step 4: Installing Economizer Panel
- Step 5: Attaching Hood Components
- Q: What should I do if I find transit damage?
- Q: What are the power requirements for this product?
RXRD-01MCDAM3 Vertical Airflow Economizers
“`html
Specifications:
- Model: RXRD-01MCDAM3
- Type: Vertical Airflow Economizers
- Power Requirements: Electrical power
- Tools Required for Installation: 3/8 Electric drill with 5/16
socket, awl
Product Usage Instructions:
Step 1: Inspecting Contents
Upon receipt, inspect all cartons and contents for transit
damage. Note any missing items compared to the PACKAGE CONTENTS
list.
Step 2: Removing Panels
Remove HORIZONTAL RETURN COVER, TOP FILTER ACCESS DOOR, and
LOWER PANEL from the unit and retain for reuse.
Step 3: Relocating Sensors
Relocate the outside air enthalpy sensor to its operating
position and remove tape holding relief dampers closed.
Step 4: Installing Economizer Panel
Install ECONOMIZER TPNL onto unit at the top of the economizer.
Secure in place through pre-punched hole in the panel.
Step 5: Attaching Hood Components
Attach the left hood side and right hood side to the lower
panel. Assemble hood divider A & B and install between the hood
sides.
FAQ:
Q: What should I do if I find transit damage?
A: Note the damage on delivery papers and file a damage claim
with the carrier.
Q: What are the power requirements for this product?
A: Electrical power is required for operation.
“`
INSTALLATION INSTRUCTIONS MODELS RXRD-01MCDAM3
VERTICAL AIRFLOW ECONOMIZERS
! WARNING
THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO
AVOID UNSATISFACTORY OPERATION OR DAMAGE TO THE PRODUCT AND POSSIBLE UNSAFE
CONDITIONS, INCLUDING ELECTRICAL SHOCK, REFRIGERANT LEAKAGE AND FIRE, THE
INSTALLATION INSTRUCTIONS PROVIDED WITH THIS ACCESSORY MUST BE STRICTLY
FOLLOWED AND THE PARTS SUPPLIED USED WITHOUT SUBSTITUTION. DAMAGE TO THE
PRODUCT RESULTING FROM NOT FOLLOWING THE INSTRUCTIONS OR USING UNAUTHORIZED
PARTS MAY BE EXCLUDED FROM THE MANUFACTURER’S WARRANTY COVERAGE.
! WARNING
DISCONNECT ELECTRICAL POWER TO THE UNIT. FAILURE TO DO SO CAN CAUSE ELECTRICAL
SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
! WARNING
ADDING POWERED EXHAUST MAY BE REQUIRED IN BUILDINGS WITH EXCESSIVE ENVELOPE
AIR LOSSES AND/ OR RESTRICTIVE RETURN AIR CONDITIONS TO THE UNIT PREVENTING
ADEQUATE RETURN AIR TO THE UNIT WHEN ECONOMIZER IS OPEN TO OUTSIDE AIR.
3/8″ Electric drill with 5/16″ socket
TOOLS REQUIRED FOR INSTALLTION: awl
TABLE 1
ITEM
DESCRIPTION
QTY
PART NO.
1 Economizer with actuator and outside air enthalpy sensor
1
ECD-RRC0CC-D2EH/X2EH
2 EconomizerTPNL
1
EC1124
3 Hood left side
1
EC1119
4 Hood right side
1
EC1120
5 Hood divider A/B
1
EC1118 / EC1123
6 Hood front support bracket
1
EC1121
7 Permanent water entrainment filter 34 3/4″ x 12 1/4″ x 1″ 8 JADE W7220 controller with attached wiring harness
1
9460-3413
1
9962-1095
9 Hardware bag with C7250 mixed air temperature sensor
1
9908-1128
Note: This economizer meets state and national codes for leakage. The economizer must be installed square with +/- 1/32″ to maintain tight damper seal.
92-107192-17-00
1
FIGURE 1
Horizontal Return Cover
Top Filter Access Panel
Lower Panel
STEP 1: Immediately upon receipt, all cartons and contents should be inspected
for transit damage. Units with damaged cartons should be opened immediately.
If damage is found, it should be noted on the delivery papers and a damage
claim filed with the last carrier. Compare carton(s) contents to the PACKAGE
CONTENTS List (Table 1) above to note any missing items.
STEP 2: Remove HORIZONTAL RETURN COVER, TOP FILTER ACCESS DOOR, and LOWER
PANEL from the unit and retain for reuse (SEE FIGURE 1). Retain screws. Note:
the lower panel will be used for the top of the economizer hood. Note: The
economizer upper panel is shipped taped to the top of the economizer. Remove
and set aside.
STEP 3: Remove the jumper plug (PL36) from economizer harness in HVAC unit.
Slide the economizer into the return air section (SEE FIGURES 2 and 3). Screw
in place. After economizer is installed, connect unit’s 12-pin ECONOMIZER PLUG
(PL34) to economizer mating plug (PL38). If not using a fieldinstalled smoke
detector kit, reinstall the jumper plug (PL36) into other 12-pin plug from
economizer note this 12-pin plug will have only 3 wires connected to it. If
using a field-installed smoke detector, discard the jumper plug (PL36) and
install the smoke detector kit using provided instructions.
STEP 4: Relocate the outside air enthalpy sensor from its shipping location to
its operating position (SEE FIGURE 3). Screw in place. Remove the tape holding
relief dampers closed.
FIGURE 2
Economizer Plug
12 PIN (Male) plug on economizer harness in unit
12 PIN (Female) plug from economizer
Either J7 jumper plug or optional smoke detector
Smoke Detector Plug
12 PIN (Male) plug from economizer
Economizer
92-107192-17-00
2
STEP 5: Install ECONOMIZER TPNL (shipped taped to economizer damper) onto
unit, at top of economizer (SEE FIGURE 5). This panel provides a transition
between the filter door and the hood top. Screw in place through pre-punched
hole in panel and into top hole of economizer damper. To ensure proper
location, TPNL will be 25 7/8″ from bottom of unit (SEE FIGURE 4).
STEP 6: Locate the lower panel removed in Step 2. Attach the left hood side
and right hood side to mounting flange on inside of lower panel. Use supplied
screws to screw in place through pre-punched holes in panel. (SEE FIGURE 5).
STEP 7: Locate hood divider A & B from hood package and assemble together
using provided screws to create a single hood divider (SEE FIGURE 8). Install
the HOOD DIVIDER between the LEFT HOOD SIDE and RIGHT HOOD SIDE (SEE FIGURE
7). Screw in place. Attach partially assembled hood on unit with supplied
screws (SEE FIGURE 7).
STEP 8: Insert the permanent filter into the hood using the hood divider to
rest the filter on. Install the hood front support bracket at top of hood to
hold filters in place (SEE FIGURE 7). Note: mixed air / discharge sensor has
been factory installed and wired in unit for economizer use.
STEP 9: Remove the unit panel covering the indoor blower section. Mount the
provided C7250 mixed air / discharge air sensor in the indoor blower section.
It can be wire tied to harness bundle. Connect two black wires with the 2-pin
plug to the sensor. See wiring diagram and Figure 4.
STEP 10: Install all other kits including carbon dioxide sensor, dual enthalpy
upgrade kit, etc.
STEP 11: Reinstall the unit’s horizontal return panel and the filter access
panel.
STEP 12: Upon unit startup, follow the JADE W7220 economizer controller setup
instructions on the following pages.
FIGURE 4
FIGURE 3
Enthalpy Shipping Position
Outside Air Damper
Enthalpy Operating Position
Economizer
Barometric Relief Dampers
*Attach partially assembled hood onto unit with supplied screws (SEE FIGURE 8).
3
92-107192-17-00
FIGURE 5
Hood Side
FIGURE 6
Upper Economizer Panel
Hood Side
FIGURE 7
Lower Panel
Upper Economizer
Panel
FIGURE 8
Economizer
Upper Panel
Hood Top / Lower Panel
FIGURE 9
Hood Top (Lower Panel)
Left Hood Side
*Front Support Bracket
Hood Divider
*Install after hood filters are in place.
Right Hood Side
Economizer Hood
Hood Divider A/B
Permanent Filter
4
92-107192-17-00
FIGURE 10 W7220 JADE economizer controller field-mounted in control compartment of HVAC unit
Unit control board factory-mounted in control compartment of HVAC unit.
92-107192-17-00
5
DIRECT MOUNT ECONOMIZER OPERATION
GENERAL This accessory economizer package is designed to save energy costs by
using outdoor air for cooling and ventilation in place of mechanical cooling
whenever possible. The economizer continuously monitors indoor and outdoor air
conditions and compares them to a user-selected setpoint to determine if free
cooling is available. The economizer utilizes a fully-modulating damper
actuator, which will control the outside air damper and return air damper in
order to maintain a factory-set mixed air/discharge air temperature.
ACCESSORIES
(-)XRX-BV01 – Dual Enthalpy Upgrade Kit For maximum energy savings, this
upgrade kit will allow the economizer to compare the outdoor air enthalpy to
the return air enthalpy, instead of a user-selected setpoint to determine if
“free cooling” is available. This Sylk Bus Sensor is a combination temperature
and humidity sensor which is powered by and communicates on the two-wire
communication bus of the W7220 economizer logic module. All OA (Outside Air)
and RA (Return Air) sensors are the same. Sensor must be set for the type of
sensing using the three DIP switches located on the sensor during
INSTALLATION.
(-)XRX-AR02 – Wall-Mounted Carbon Dioxide Sensor For installations requiring
Demand Control Ventilation (DCV) based upon indoor air levels of carbon
dioxide (CO2). When the unit supply fan is running, the CO2 sensor modulates
the outside air damper to maintain a user-selected CO2 level inside the
occupied space. Energy savings are achieved by not bringing in excessive
amounts of outdoor air when the indoor air conditions are suitable. Energy
savings can be substantial on buildings with highly variable occupancy rates.
NOTE: The (-)XRX-AR02 has a default setting of a 2-10 Vdc output for a
500-1500 ppm CO2 input. The W7220 economizer controller requires jumper pins
on the sensor to be relocated to provide a 0-2000 ppm input.
SW1 ON OFF ON OFF
SW1 ON ON OFF OFF
AN (ppm) 0 to 1000 0 to 2000 500 to 1500 500 to 2000
Relay (ppm) 1000 1200 800 1200
Dip Switch Setting Return Air Enthalpy Sensor Outside Air Enthalpy Sensor
C1 ON OFF
C2 OFF OFF
C3 OFF OFF
RXRX-AR02 NEW JUMPER POSITION
OUT
AN
SW2 SW1
OFF ON OFF ON 0-100% 20-100% )Voltage )Current
DIP SWITCH LABEL DIP SWITCHES (3)
Wiring Schematic for (-)XRX-AR02 Note: Black & brown wire common.
C7232 24V
RED BLACK
ANALOG + OUT –
YELLOW BROWN ORANGE
GREEN
L1 (HOT) L2 1
POWER SUPPLY PROVIDE
1 DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED
Power Exhaust Kit For installations requiring more space static pressure relief than can be obtained with the standard barometric relief damper included with the economizer, a power exhaust kit can be added.
SYLK BUS TERMINALS (1 AND 2)
92-107192-17-00
6
ADJUSTMENT METHOD
The user interface consists of an LCD display and a 4-button keypad on the
front of the Economizer module. The LCD is a 16 character by 2 line dot matrix
display.
Power Up Cycle
All setpoints and advanced settings are restored after any power loss (a power
loss is assumed if voltage falls below 18 Vac). Normal operation is restored
when power returns above 18 Vac.
Initial Menu Display
On initial startup, Honeywell displays on the first line and Economizer W7220
on the second line. After a brief pause, the revision of the software appears
on the first line (second line is blank). It then displays W7220 on the first
line and STATUS on the second line.
Key pad
The four navigation buttons illustrated in Figure 11 are used to scroll
through the menus and menu items, select menu items, and to change parameter
and configuration settings.
Us ing the Key pad with Menus
To use the keypad when working with menus:
· Press the button to move to the previous menu. · Press the button to move to
the next menu. · Press the button (Enter) to display the first item inthe
currently displayed menu. · Press the button (Menu up) to exit a menu’s
itemand return
to the list of menus.
Using the Key pad with Settings and Parameters
To use the keypad when working with Setpoints, System and Advanced Settings,
Checkout tests, and Alarms:
· Navigate to the desired menu. · Press the button (Enter) to display the
first item in the
currently displayed menu. · Use the and buttons to scroll to the desired
parameter. · Press the button (Enter) to display the value of the currently
displayed item. · Press the button to increase (change) the displayed
parameter value.a · Press the button to decrease (change) the displayed
parameter value.a · Press the button to accept the displayed value and store
it
in non-volatile RAM. · When the value is accepted, CHANGE STORED is displayed
on the LCD. · Press the button (Enter) to return to the current menu
parameter. · Press the button (MenuUp/Exit) to return to the previous
menu.
FIGURE 11
Time-out and Screensaver When no buttons have been pressed for 10 minutes, the
LCD displays a screen saver, which cycles through the Status items. Each
Status items displays in turn and cycles to the next item after 5 seconds.
SETUP AND CONFIGURATION Before being placed into service, the JADETM
Economizer module must be setup and configured for the installed system. Use
the System Setup menu, the Advanced Setup menu (if necessary), and the
Setpoints menu to accomplish this. Menu Structure The following tables
illustrate the complete hierarchy of menus and parameters for the JADETM
Economizer system. The Menus in display order are: · STATUS · SETPOINTS ·
SYSTEM SETUP · ADVANCED SETUP · CHECKOUT · ALARMS IMPORTANT Your menu
parameters may be different depending on your configuration. For example if
you do not have a DCV (CO2) sensor, then none of the DCV parameters appear.
a When values are displayed, pressing and holding the or button causes the
display to automatically increment.
92-107192-17-00
7
STATUS MENU
Parameter
Parameter Parameter Default Range and Value Incremeenta
Notes
ECON AVAIL
NO
YES/NO YES = economizing available; the system can use Out door Air for free cooling when required.
ECONOMIZING
NO
YES/NO YES = Outdoor Air being used for 1st stage cooling.
OCCUPIED
NO
YES/NO
YES = 24 Vac OCC signal received from space thermostat in put. NO = 0 Vac on terminal OCC.
HEAT PUMP
COOL COO/HEAT Displays COOL or HEAT when SYSTEM is set to heat pump (nonconventional)
COOL Y1-IN
OFF
ON/OFF
Y1-I signal from space thermostat input for cooling stage 1 or heat pump heating stage 1. ON = 24 Vac on terminal Y1-I OFF = 0 Vac on terminal Y1-I
COOL Y1-OUT
OFF
ON/OFF Cool Stage 1 Relay Output to stage 1 mechanical cooling (Y1-OUT terminal).
COOL Y2-IN
OFF
ON/OFF
Y2-I signal from space thermostat input for second stage cooling or heat pump heating stage 2. ON = 24 Vac on terminal Y2-I OFF = 0 Vac on terminal Y2-I
COOL Y2-OUT
OFF
ON/OFF Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).
MA TEMP
._°F
-40 to 150°F
Displays value of measured mixed air from MAT sensor. Displays -.- if not connected, short, or out-of-range.
DA TEMP
._°F
Displays when Discharge Air Sylk Bus sensor is connected and displays measured
discharge -40 to 150°F air temperature. Displays -.-°F if sensor sends in
valid value, if not connected, short or
out-of-range.
OA TEMP
._°F
-40 to 140°F
Displays measured value of out door air temperature. Displays -°F if sensor sends in valid value, if not connected, short or out-of-range.
OA HUM
%
0 to 100%
Displays measured value of out door humidity. Displays -% if not connected, short, or out-of-range.
RA TEMP
._°F
0 to 140°F
If field installed Dual Enthalpy sensor is connected, displays measured value of return air temperature. Displays -°F if sensor sends in valid value, if not connected, short or out-of-range.
RA HUM
%
0 to 100%
If field installed Dual Enthalpy sensor is connected, displays measured value of return air humidity. Displays -% if sensor sends in valid value, if not connected, short or out-of-range.
IN CO2
_ppm
“0 to 2000 If field installed CO2 sensor is connected, displays value of measured CO2. In valid if not (3500) ppm” connected, short or out-of-range. May be adjusted in Advanced menu by Zero off set and Span.
DCV STATUS
n/a
n/a
If field in stalled CO2 sensor is connected, displays ON if above setpoint and OFF if be low setpoint.
DAMPER OUT
%
0 to 100%
Displays output position to the damper actuator. When used with Honeywell communicating actuator the damper out is in XX.X%
ACT POS.
n/a
0 to 100% Displays actual position of actuator.
ACT COUNT
n/a
1 to 65,535 Displays number of times actuator has cycled. 1 Cycle equals 180° of movement in any direction.
ACTUATOR
n/a
OK/Alarm Displays Error on ALARM MENU if voltage or torque is below actuator range.
EXH1 OUT
OFF
ON/OFF Output of EXH1 terminal. – ON = relay closed; OFF = relay open.
EXH2 OUT
OFF
ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = EXH2
ERV
OFF
ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = ERV
“MECH COOL ON HEAT STGS ON”
0
0, 1, or 2
Displays stage of mechanical cooling that is active. Displays the stage of heat pump heating that is active.
FAN SPEED
n/a
LOW/HIGH Displays speed of fan on a 2-speed fan unit
W (HEAT IN)
n/a
ON/OFF Displays status of heat on a 2-speed fan unit.
92-107192-17-00
8
SETPOINTS MENU
Parameter MAT SET LOW T LOCK DRYBLB SET DRYBLB DIFF ENTH CURVE DCV SET MIN POS
VENTMAX
VENTMIN
ERV OAT SP EXH1 SET EXH2 SET
Parameter Default Value 53°F 32°F 63°F 0°F ES3
1100 ppm 2.8 V
2.8 V
2.25 V
32°F 50% 75%
Parameter Range and Incremeenta 38 to 70°F; incremented by 1 -45 to 80°F;
incremented by 1 48 to 80°F; incremented by 1
0° – 6°F increment of 2°
ES1, ES2, ES3, ES3, or ES5
500 to 2000 ppm increment by 100
2 to 10 Vdc
2 to 10 Vdc
100 to 9990 cfm increment by 10
2 to 10 Vdc
2 to 10 Vdc 100 to 9990 cfm increment by 10
2 to 10 Vdc 0 to 50°F; increment by 1 0 to 100%; increment by 1
0 to 100%; increment by 1
Notes
Setpoint determines where the economizer will modulate the OA damper to
maintain the mixed air temperature.
Setpoint determines outdoor temperature when the mechanical cooling cannot be
turned on. Commonly referred to as the Compressor lockout.
Setpoint determines where the economizer will assume outdoor air temperature
is good for free cooling; e.g.; at 63ºF unit will economizer at 62ºF and below
and not economize at 64ºF and above. There is a 2ºF deadband.
Drybulb Differential will only show if using dual drybulb, i.e. when an
ourdoor air temperature air sensor C7250 is attached to OAT terminals, and a
C7400S sensor is wirred to S-BUS and configured for RAT (Return Air). Free
cooling will be assumed whenever OA temperature is at or below RAT minus this
drybulb differential setting.
Does not display if a field installed Dual Enthalpy kit is connected. Enthalpy
boundary “curves” for economizing using single enthalpy comparison between
outdoor air enthalpy and setpoint.
Displays ONLY if field installed CO2 sensor is connected. Setpoint for Demand
Control Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the
setpoint.
Displays ONLY if a CO2 sensor is NOT connected.
With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed
fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is
2.8V
Displays only if a field installed CO2 sensor is connected. Used for Vbz
(ventilation max cfm) setpoint. VENTMAX is the same setting as MIN POS would
be if you did not have the CO2 sensor.
If OA, MA, RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO
mode, the OA dampers are controlled by CFM and displays from 100 to 9990 cfm.
With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed
fan) settings are required. Default for VENTMAX L is 3.2V and VENTMAX H is
2.8V.
Dis plays only if field in stalled CO2 sen sor is con nected. Used for Va (ven
ti la tion min cfm) setpoint. This is the ven ti la tion re quire ment for
less than max i mum oc cu pancy of the space.
If OA, MA, RA and CO2 sen sors are con nected and DCV CAL EN ABLE is set to
AUTO mode, the OA damp ers are con trolled by CFM and dis plays from 100 to
9990 cfm.
With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed
fan) set tings are re quired. De fault for VENTMIN L is 2.5V and VENTMIN H is
2.25V.
Only when AUX1 O = ERV
Setpoint for OA damper position when exhaust fan 1 is powered by the
economizer. With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%.
Setpoint for OA damper position when exhaust fan 2 is powered by the
economizer. Only used when AUX1 O is set to EHX2. With 2-speed fan units Exh2
L (low speed fan) and Exh2 H (high speed fan) settings are required. Default
for Exh2 L is 80% and Exh2 H is 75%.
92-107192-17-00
9
SYSTEM SETUP MENU
Parameter INSTALL UNITS DEG EQUIPMENT
AUX2 IN
FAN TYPE FAN CFM
AUX1 OUT
OCC FACTORY DEFAULT
Parameter Default Value
01/01/2011 °F
HP O/B
W1
2 speed 5000cfm
EXH2
INPUT NO
Parameter Range and Incremeenta
Notes
Display order = MM/DD/YY. Setting order = DD, MM, then YY.
°F or °C
Sets economizer controller in degrees Fahrenheit or Celsius.
CONV HP O/B
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump (“B” signal) input
from thermostat.
CONV = conventional.
Shutdown (SD) Heat (W1) HP(O) HP(B)
In HP O/B mode: HP(O) = energize heat pump on Cool; HP(B) = energize heat pump
on Heat.
In CONV mode: SD = Enables configuration of shutdown; W = Informs controller
that system is in heating mode. NOTE: If using 2-speed fan mode, you must
program CONV mode for W. Shutdown is not available in the two speed fan mode.
1 speed/ 2 speed
Sets economizer controller for operation of 1 speed or 2 speed supply fan NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.
100 to 15000 This is the airflow capacity of the rooftop unit or air handler. The value is found in the
cfm;
unit I&O manual or specification sheet. The cfm of the indoor fan is only used with the
increment by 100 DCVCAL ENA parameter set in the AUTO mode.
NONE ERV EXH2 SYS
· NONE = not configured (output is not used) · ERV= Energy Recovery Ventilator
· EXH2 = second damper position relay closure for second exhaust fan. · SYS =
use output as an alarm signal
INPUT or ALWAYS
The indoor fan “G” or “ON” Signal. Can also be used with a setback thermostat with occupancy out (24 Vac), where the 24 Vac is input “INPUT” to the OCC terminal. If no occupancy output from the thermostat then change program to “ALWAYS”.
NO or YES
Resets all set points to factory defaults when set to YES. LCD will briefly flash YES and change to NO but all parameters will change to factory default values.
92-107192-17-00
10
ADVANCE SETUP MENU
Parameter MA LO SET FREEZE POS CO2 ZERO CO2 SPAN
STG3 DLY
SD DMPR POS
DCVCAL ENA
MAT T CAL OAS T CAL OAS H CAL RA T CAL RA H CAL DA T CAL 2SP FAN DELAY
Parameter Default Value 45ºF CLO 0 ppm
2000 ppm
2.0h
CLO
MAN
0.0 F° 0.0F° 0% RH 0.0F° 0% RH 0.0F° 5 Minutes
Parameter Range and Incremeenta 35 to 55ºF increment by 1°
CLO MIN 0 to 500 ppm increment by 10 1000 to 3000 ppm; increment by 50 0 min,
5 min, 15 min, then 15 min intervals. Up to 4h or OFF
CLO OPN
MAN (manual) AUTO
+/-2.5F°
+/-2.5F°
+/-10% RH
+/-2.5F°
+/-10% RH
+/-2.5F°
0 to 20 minutes in 1 minute increments.
Notes
Temp to activate Freeze Protection (close damper and alarm if temp falls below
setup value) Damper position when freeze protection is active (closed or MIN
POS).
Displays only if field installed CO2 sensor is connected. CO2 ppm level to
match CO2 sensor start level.
Displays only if field installed CO2 sensor is connected. CO2 ppm span to
match CO2 sensor.
Delay after stage 2 for cool has been active. Turns on 2nd stage of cooling
when economizer is 1st stage and mechanical cooling is 2nd stage. Allows three
stages of cooling, 1 economizer and 2 mechanical. OFF = no Stage 3 cooling.
Indicates shutdown signal from space thermostat. When controller receives 24
Vac input on the SD terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed for CLO. All other
controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut off. Displays only if all
sensors (RA, OA, MA and CO2) are connected. Turns on the DCV automatic control
of the dampers. Resets ventilation based on the RA, OA and MA sensor
conditions. This operation is not operable with a 2-speed fan unit. Allows for
the operator to adjust for an out of calibration mixed air temperature sensor.
Allows for the operator to adjust for an out of calibration outdoor air
temperature sensor. Allows for the operator to adjust for an out of
calibration outdoor air humidity sensor. If field installed Dual Enthalpy
sensor is connected, allows for the operator to adjust for an out of
calibration temperature sensor. If field installed Dual Enthalpy sensor is
connected, allows for the operator to adjust for an out of calibration
humidity sensor. Allows for the operator to adjust for an out of calibration
Discharge Air Sylk Bus temperature sensor. When in economizing mode this is
the delay for the high speed fan to try to satisfy the call for second stage
cooling before the first stage mechanical cooling is enabled.
92-107192-17-00
11
CHECKOUT MENU
Parameter
DAMPER VMIN-HS DAMPER VMAX-HS DAMPER VMAX-LS DAMPER OPEN DAMPER CLOSE CONNECT
Y1-O CONNECT Y2-O CONNECT EXH1
Parameter Default Value n/a
n/a
n/a n/a n/a n/a n/a
CONNECT EXH2
n/a
Parameter Range and Incremeenta
n/a
n/a
n/a n/a n/a n/a n/a
n/a
Notes
Positions damper to VMIN position Positions damper to VMAX position. With
2-speed fan units the damper will position to VMAX low speed fan. Positions
outside air damper to the full open position. Positions outside air damper to
the fully closed position. Closes the Y1-O relay (Y1-O); energizes 1st stage
compressor. Closes the Y2-O relay (Y2-O); energizes 2nd stage compressor.
Closes the power exhaust fan 1 relay (EXH1) Energizes the EXH2 output. The
EXH2-O can be replaced by: · ERV · EXH2 · SYS · AUX1 O Based on AUX1 O switch
settings or is not available if AUX1 O is set to NONE
Check out Tests Use the Checkout menu to test the damper operation and any
configured outputs. Only items that are configured are shown in the Checkout
menu. To perform a Checkout test: 1. Scroll to the desired test in the
Checkout menu using the and buttons. 2. Press the button to select the item.
3. RUN? appears on the display. 4. Press the button to start the test. 5. The
unit pauses and then displays TEST RUNNING. 6. Press the button (Menu up) to
end the test (e.g. turn off the relay). Test stops automatically after 10
minutes without a command or
mode change, and will resume normal operation.
The checkout tests can all be performed at the time of installation or any
time during the operation of the system as a test that the system is operable.
NOTE: Be sure to allow for enough time for compressor startup and shutdown
between checkout tests so that you do not shortcycle the compressors and
damage them from extreme short-cycling.
92-107192-17-00
12
ALARM MENU
Parameter
MA T SENS ERR CO2 SENS ERR OA T SENS ERR DA ENTHL ERR
SYS ALARM
ACT UNDER V ACT OVER V ACT STALLED
Parameter Default Value n/a n/a n/a n/a
n/a
n/a n/a n/a
Parameter Range and Incremeenta
n/a n/a n/a n/a
n/a
n/a n/a n/a
Notes
Alarms display only when they are active. The menu title “ALARMS (_)”includes
the number of active alarms in parenthesis ().
When AUX1 O is set to SYS and there is any alarm (e.g., failed sensors, etc.),
the AUX1 O terminal has 24 Vac out. Voltage received by Actuator is above
expected range Voltage received by Actuator is below expected range Actuator
stopped before achieving commanded position
Alarms The Economizer module provides alarm messages that display on the
2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before checking for alarms.
This allows time for all the configured devices (e.g. sensors, actuator) to
become operational. The exception is the MA sensor which will alarm
immediately.
If one or more alarms are present and there has been no keypad activity for at
least 5 minutes, the Alarms menu displays and cycles through the active
alarms. You can also navigate to the Alarms menu at any time.
Clearing Alarms Once the alarm has been identified and the cause has been
removed (e.g. replaced faulty sensor), the alarm can be cleared from the
display. To clear an alarm, perform the following: 1. Navigate to the desired
alarm. 2. Press the button. 3. ERASE? displays. 4. Press the button. 5. ALARM
ERASED displays. 6. Press the button (MenuUp/Exit) to complete the action and
return to the previous menu.
NOTE: If an alarm still exists after you clear it, it redisplays within 5
seconds.
92-107192-17-00
13
TYPICAL ADJUSTMENTS 1. Economizer ENTH CURVE Setpoint
a. Only the coolest, driest outside air is used for economizer operation when
parameter “ES5” is selected on the SETPOINT MENU. Select parameter “ES1” on
the SETPOINT MENU for the greatest energy savings.
b. Adjustments are ES1, ES2, ES3, ES4, ES5. c. “ES3” is the default setting.
d. Economizer ENTH CURVE Setpoint can be adjusted at
any time and may need adjustment for jobsite conditions.
e. Single enthalpy strategy: If outdoor air enthalpy is lower than the ENTH
CURVE setpoint, then free cooling is available.
f. Dual enthalpy strategy: ENTH CURVE Setpoint is not used. If outdoor air
enthalpy is lower than return air enthalpy, then free cooling is available.
There is also a high limit boundary for dual enthalpy. The high limit boundary
is “ES1” when there are no stages of mechanical cooling energized and “HL”
when a compressor stage is energized.
JADETMECONOMIZER MODULE
Enthalpy Curve
ES1 ES2 ES3 ES4 ES5 HL
Temp. Dry-Bulb (°F)
80.0 75.0 70.0 65.0 60.0 86.0
Single Enthalpy and Dual Enthalpy High Limit Curves
Temp.
Enthalpy
Dewpoint (°F) (btu/lb/da)
Point P1 Temp. °F Humidity %RH
60.0
28.0
80.0
36.8
57.0
26.0
75.0
39.6
54.0
24.0
70.0
42.3
51.0
22.0
65.0
44.8
48.0
20.0
60.0
46.9
66.0
32.4
86.0
38.9
Point P2
Temp. °F Humidity %RH
66.3
80.1
63.3
80.0
59.7
81.4
55.7
84.2
51.3
88.5
72.4
80.3
2. EXH1 SET – Adjustments for (optional) power exhaust.
3. EXH2 SET – Adjustments for (optional) 2 speed power exhaust.
a. The outside air damper position at which the power
a. The outside air damper position at which the 2nd speed of
exhaust fan(s) will engage.
the power exhaust fan(s) will engage.
b. With 2-speed indoor fan units EXH1 L (low speed fan) and EXH1 H (high speed
fan) settings are required.
c. Default for EXH1 L is 65% and EXH1 H is 50%.
d. After the outside air damper output command DAMPER OUT (not ACT POS.)
reaches the power exhaust setpoint, the power exhaust output EXH1 is energized
after a 45 second delay.
e. Range of adjustment is from 0-100% outside air.
b. With 2-speed indoor fan units EXH2 L (low speed fan) and EXH2 H (high speed
fan) settings are required.
c. Default for EXH2 L is 80% and EXH2 H is 75%. d. After the outside air
damper output command DAMPER
OUT (not ACT POS.) reaches the power exhaust setpoint, the power exhaust
output EXH2 is energized after a 45 second delay to allow the damper to reach
the appropriate position. e. Range of adjustment is from 0-100% outside air.
92-107192-17-00
14
4. MIN POS – Outside Air Damper minimum position
NORMAL OPERATION
a. Displays ONLY if a CO2 sensor is NOT connected. With 1. Fan Only (G)
2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan)
settings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V.
b. Adjust MIN POS to allow the minimum amount of outdoor air, as required by
local codes, to enter the building.
c. Range of adjustment is from 0-100% (2-10V); in most applications MIN POS is
adjusted to allow 10% to 25% outside air to enter the system.
a. Damper will go to minimum position (in 90 seconds or less) whenever the “G”
(supply fan) signal is present.
b. When “G” signal is removed, the outside air damper closes against blade
seals for tight shutoff of outside air.
c. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then
the control will override the minimum position setting and will modulate the
outside air damper closed.
d. MIN POS can be adjusted at any time.
2. Call for First Stage of Cooling (Y1)
e. Whenever the “G” (supply fan) signal is present, the
a. Economizer Unavailable (warm outdoor air): Closes the
damper will open to this minimum position unless the
Y1-O relay (Y1-O) which energizes 1st stage compressor.
mixed air sensor falls below the MA LO SET (Freeze
b. Economizer Available (free cooling): The controller tries to
Protect Mode Setpoint).
maintain a mixed air temperature of 53°F ± 5 (MAT SET
5. VENTMAX – Demand Control Ventilation (DCV) Maximum
Setpoint) by modulating the outside air damper position.
Setpoint
3. Call for Second Stage of Cooling (Y2)
a. Displays only if a CO2 sensor is connected.
a. Economizer Unavailable (warm outdoor air): Closes the
b. VENTMAX allows the installer to limit the amount of
Y2-O relay (Y2-O) which energizes 2nd stage compressor.
outdoor airflow into the building when DCV overrides the mixed air temperature
sensor setpoint. It is normally equal to the minimum amount of outdoor air
under maximum occupancy, as required by local codes, to enter the
building.
b. Economizer Available (free cooling): Closes the Y1-O
relay (Y1-O) which energizes 1st stage compressor. The controller tries to
maintain a mixed air temperature of 53°F ± 5 (MAT SET Setpoint) by modulating
the outside air damper position. After a time period of 2 hours of
c. VENTMAX can be adjusted at any time.
simultaneous economizer operation and first stage
6. VENTMIN – Demand Control Ventilation (DCV) Setpoint
compressor operation, the economizer closes the Y2-O
a. Displays only if a CO2 sensor is connected.
relay (Y2-O) which energizes 2nd stage compressor.
b. Is the ventilation requirement for less than maximum 4. Call for Heat
occupancy of the space.
a. Standard Air Conditioner with electric or gas heat.(W1 &
c. Compatible CO2 sensors will have a 2-10Vdc output for a
W2)
0-2000 ppm CO2 input.
i. The Thermostat controls the stages of heating
d. DCV modulates the outdoor damper between the
directly.
VENTMIN and VENTMAX settings to provide ventilation based on occupancy. The carbon dioxide (CO2) sensor is used to indirectly monitor occupancy level.
ii. If the control detects that the supply fan is on (through its “G” input), then the control will open the damper to minimum position.
e. No cooling signal (e.g.Y1, Y2) is required for DCV to override the outdoor air damper when ventilation requires
iii. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then the control will override
outdoor air.
the minimum position setting and will modulate the
f. The controller must receive a “G” (supply fan) signal to
outdoor damper closed.
open the damper.
b. Heat Pump Operation (B)
g. Range of adjustment is from 2 Volts to 10 Volts.
i. The “B” signal from the Thermostat allows operation
h. VENTMIN can be adjusted at any time.
of the compressors to provide heating without delay.
i. The controller compares the CO2 sensor input to VENT MIN to determine the
damper minimum position.
i. If the actual CO2 level is below the setpoint, then the damper minimum
position is determined by the damper minimum position (VENTMIN) setting.
ii. If the actual CO2 level rises above the setpoint, then the damper minimum
position is overridden
ii. If the control detects that the supply fan is on (through its “G” input),
then the control can open the damper to minimum position.
iii. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then
the control will override the minimum position setting and will modulate the
outdoor damper closed.
proportionally more open up to the VENTMAX setting.
iii. If the mixed air temperature drops below 45°F (MA LO SET – Freeze Protect Mode Setpoint), the DCV
input will be overridden and the damper may not
open.
j. Ensure proper polarity of the sensor wires when connecting
to the economizer controller. Incorrect polarity negates
the sensor signal.
92-107192-17-00
15
NOTES
1. This economizer requires a two-stage thermostat.
2. When diagnosing the system, the best results are obtained by first putting
the fan setting on the Thermostat to the “Continuous Fan” mode.
3. Operation of the optional power exhaust only depends upon the supply fan
running and the damper position (it is possible to set the minimum position
high enough to engage the power exhaust in the heating mode).
4. Upon loss of power to the unit or economizer, the outside air damper will
spring close shut in about 5 seconds.
5. Compressor Time Delays, Compressor Interstage Delays are not provided by
the economizer controller.
DCV None
Below Setpoint
Above Setpoint
Table of Inputs and Output Response with and without a CO2 Sensor (DCV)
Inputs to Controller
Outputs from Controller
Free Cooling Y1-I
Available?
Y2-I AUX2-I FAN Y1-O Y2-O
OA Damper Position
OFF
OFF
OFF
OFF
OFF
OFF
CLOSED
OFF
OFF
OFF
ON
OFF
OFF
MIN POS
ON
OFF
OFF
ON
ON
OFF
NO
ON
ON
OFF
ON
ON
ON
MIN POS MIN POS
ON
OFF
ONd
ON
ON
OFF
MIN POS
ON
ON
ONd
ON
ON
ON
MIN POS
OFF
OFF
OFF
ON
OFF
OFF
MIN POS
ON
OFF
OFF
ON
OFF
OFF
MIN POS to 100%
YES
ON
ON
OFF
ON
ON
OFFb
MIN POS to 100%
ON
OFF
ONd
ON
ON
OFF
MIN POS
ON
ON
ONd
ON
ON
ON
MIN POS
OFF OFF
OFF
ON
OFF OFF
VENTMIN
ON
OFF
OFF
ON
ON
OFF
VENTMIN
NO
ON
ON
OFF
ON
ON
ON
VENTMIN
ON
OFF
ONd
ON
ON
OFF
VENTMIN
ON
ON
ONd
ON
ON
ON
VENTMIN
OFF
OFF
OFF
ON
OFF
OFF
VENTMIN
ON
OFF
OFF
ON
OFF
OFF
VENTMIN to 100%
YES
ON
ON
OFF
ON
ON
OFFb
VENTMIN to 100%
ON
OFF
ONd
ON
ON
OFF
VENTMIN
ON
ON
ONd
ON
ON
ON
VENTMIN
OFF
OFF
OFF
ONc
OFF
OFF
VENTMIN to VENTMAX
ON
OFF
OFF
ON
ON
OFF
VENTMIN to VENTMAX
NO
ON
ON
OFF
ON
ON
ON
VENTMIN to VENTMAX
ON
OFF
ONd
ON
ON
OFF
VENTMIN to VENTMAX
ON
ON
ONd
ON
ON
ON
VENTMIN to VENTMAX
OFF
OFF
OFF
ONc
OFF
OFF
VENTMIN to VENTMAX
ON
OFF
OFF
ON
OFF
OFF
VENTMIN to 100%
YES
ON
ON
OFF
ON
ON
OFFb
VENTMIN to 100%
ON
OFF
ONd
ON
ON
OFF
VENTMIN to VENTMAX
ON
ON
ONd
ON
ON
ON
VENTMIN to VENTMAX
B With STG3 DLY in ADVANCED SETUP MENU at 2.0 hours, the 2nd stage of
mechanical cooling Y2-O can be energized after a 2 hour delay if the call for
Y1-I and Y2-I have not been satisfied.
C The CO2 sensor has a relay output that is active when the CO2 level is above
1200ppm that can be used to energize the indoor fan through the “G” thermostat
input of the unit even if there is not a call for fan, cooling or heating by
the room thermostat. Additional field wiring is required to enable this
option.
D AUX2-I is used only on heat pump models to indicate unit is in heat pump
(heating) mode.
92-107192-17-00
16
DCV None Below Setpoint Above Setpoint
Table of Inputs and Output Response with and without a CO2 Sensor (DCV) for Unoccupied Mode
Inputs to Controller
Outputs from Controller
Free Cooling Available?
Y1-I
Y2-I AUX2-I FAN
Y1-O Y2-O
OA Damper Position (Unoccupied)*
OFF
OFF
OFF
OFF
OFF
OFF
CLOSED
OFF
OFF
OFF
ON
OFF
OFF
CLOSED
ON
OFF
OFF
ON
ON
OFF
NO
ON
ON
OFF
ON
ON
ON
CLOSED CLOSED
ON
OFF
ONd
ON
ON
OFF
CLOSED
ON
ON
ONd
ON
ON
ON
CLOSED
OFF
OFF
OFF
ON
OFF
OFF
CLOSED
ON
OFF
OFF
ON
OFF
OFF
CLOSED to 100%
YES
ON
ON
OFF
ON
ON
OFFb
CLOSED to 100%
ON
OFF
ONd
ON
ON
OFF
CLOSED
ON
ON
ONd
ON
ON
ON
CLOSED
OFF
OFF
OFF
ON
OFF OFF
CLOSED
ON
OFF
OFF
ON
ON
OFF
CLOSED
NO
ON
ON
OFF
ON
ON
ON
CLOSED
ON
OFF
ONd
ON
ON
OFF
CLOSED
ON
ON
ONd
ON
ON
ON
CLOSED
OFF
OFF
OFF
ON
OFF
OFF
CLOSED
ON
OFF
OFF
ON
OFF
OFF
CLOSED to 100%
YES
ON
ON
OFF
ON
ON
OFFb
CLOSED to 100%
ON
OFF
ONd
ON
ON
OFF
CLOSED
ON
ON
ONd
ON
ON
ON
CLOSED
OFF
OFF
OFF
ONc
OFF
OFF
CLOSED
ON
OFF
OFF
ON
ON
OFF
CLOSED
NO
ON
ON
OFF
ON
ON
ON
CLOSED
ON
OFF
ONd
ON
ON
OFF
CLOSED
ON
ON
ONd
ON
ON
ON
CLOSED
OFF
OFF
OFF
ONc
OFF
OFF
CLOSED
ON
OFF
OFF
ON
OFF
OFF
CLOSED to 100%
YES
ON
ON
OFF
ON
ON
OFFb
CLOSED to 100%
ON
OFF
ONd
ON
ON
OFF
CLOSED
ON
ON
ONd
ON
ON
ON
CLOSED
e Unoccupied Mode is only available by field wiring a normally open (NO) relay
in the “G” signal wiring between the unit and economizer. A thermostat with an
occupied output is required which energizes the relay when the space is
occupied. The relay interrupts the 24 volt “G” signal from the unit indoor fan
when the space is unoccupied.
Mixed Air / Discharge Air Temperature vs. Resistance
92-107192-17-00
17
Jade W7220 Economizer Wiring Diagram
MS3105
92-107192-17-00
18
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>