JADE RXRD-01MCDAM3 Vertical Airflow Economizers Instruction Manual

September 16, 2024
jade

RXRD-01MCDAM3 Vertical Airflow Economizers

“`html

Specifications:

  • Model: RXRD-01MCDAM3
  • Type: Vertical Airflow Economizers
  • Power Requirements: Electrical power
  • Tools Required for Installation: 3/8 Electric drill with 5/16
    socket, awl

Product Usage Instructions:

Step 1: Inspecting Contents

Upon receipt, inspect all cartons and contents for transit
damage. Note any missing items compared to the PACKAGE CONTENTS
list.

Step 2: Removing Panels

Remove HORIZONTAL RETURN COVER, TOP FILTER ACCESS DOOR, and
LOWER PANEL from the unit and retain for reuse.

Step 3: Relocating Sensors

Relocate the outside air enthalpy sensor to its operating
position and remove tape holding relief dampers closed.

Step 4: Installing Economizer Panel

Install ECONOMIZER TPNL onto unit at the top of the economizer.
Secure in place through pre-punched hole in the panel.

Step 5: Attaching Hood Components

Attach the left hood side and right hood side to the lower
panel. Assemble hood divider A & B and install between the hood
sides.

FAQ:

Q: What should I do if I find transit damage?

A: Note the damage on delivery papers and file a damage claim
with the carrier.

Q: What are the power requirements for this product?

A: Electrical power is required for operation.

“`

INSTALLATION INSTRUCTIONS MODELS RXRD-01MCDAM3
VERTICAL AIRFLOW ECONOMIZERS
! WARNING
THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID UNSATISFACTORY OPERATION OR DAMAGE TO THE PRODUCT AND POSSIBLE UNSAFE CONDITIONS, INCLUDING ELECTRICAL SHOCK, REFRIGERANT LEAKAGE AND FIRE, THE INSTALLATION INSTRUCTIONS PROVIDED WITH THIS ACCESSORY MUST BE STRICTLY FOLLOWED AND THE PARTS SUPPLIED USED WITHOUT SUBSTITUTION. DAMAGE TO THE PRODUCT RESULTING FROM NOT FOLLOWING THE INSTRUCTIONS OR USING UNAUTHORIZED PARTS MAY BE EXCLUDED FROM THE MANUFACTURER’S WARRANTY COVERAGE.

! WARNING
DISCONNECT ELECTRICAL POWER TO THE UNIT. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH.

! WARNING
ADDING POWERED EXHAUST MAY BE REQUIRED IN BUILDINGS WITH EXCESSIVE ENVELOPE AIR LOSSES AND/ OR RESTRICTIVE RETURN AIR CONDITIONS TO THE UNIT PREVENTING ADEQUATE RETURN AIR TO THE UNIT WHEN ECONOMIZER IS OPEN TO OUTSIDE AIR.

3/8″ Electric drill with 5/16″ socket

TOOLS REQUIRED FOR INSTALLTION: awl

TABLE 1

ITEM

DESCRIPTION

QTY

PART NO.

1 Economizer with actuator and outside air enthalpy sensor

1

ECD-RRC0CC-D2EH/X2EH

2 EconomizerTPNL

1

EC1124

3 Hood left side

1

EC1119

4 Hood right side

1

EC1120

5 Hood divider A/B

1

EC1118 / EC1123

6 Hood front support bracket

1

EC1121

7 Permanent water entrainment filter 34 3/4″ x 12 1/4″ x 1″ 8 JADE W7220 controller with attached wiring harness

1

9460-3413

1

9962-1095

9 Hardware bag with C7250 mixed air temperature sensor

1

9908-1128

Note: This economizer meets state and national codes for leakage. The economizer must be installed square with +/- 1/32″ to maintain tight damper seal.

92-107192-17-00
1

FIGURE 1
Horizontal Return Cover

Top Filter Access Panel
Lower Panel

STEP 1: Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers and a damage claim filed with the last carrier. Compare carton(s) contents to the PACKAGE CONTENTS List (Table 1) above to note any missing items.
STEP 2: Remove HORIZONTAL RETURN COVER, TOP FILTER ACCESS DOOR, and LOWER PANEL from the unit and retain for reuse (SEE FIGURE 1). Retain screws. Note: the lower panel will be used for the top of the economizer hood. Note: The economizer upper panel is shipped taped to the top of the economizer. Remove and set aside.
STEP 3: Remove the jumper plug (PL36) from economizer harness in HVAC unit. Slide the economizer into the return air section (SEE FIGURES 2 and 3). Screw in place. After economizer is installed, connect unit’s 12-pin ECONOMIZER PLUG (PL34) to economizer mating plug (PL38). If not using a fieldinstalled smoke detector kit, reinstall the jumper plug (PL36) into other 12-pin plug from economizer ­ note this 12-pin plug will have only 3 wires connected to it. If using a field-installed smoke detector, discard the jumper plug (PL36) and install the smoke detector kit using provided instructions.
STEP 4: Relocate the outside air enthalpy sensor from its shipping location to its operating position (SEE FIGURE 3). Screw in place. Remove the tape holding relief dampers closed.

FIGURE 2

Economizer Plug

12 PIN (Male) plug on economizer harness in unit
12 PIN (Female) plug from economizer

Either J7 jumper plug or optional smoke detector

Smoke Detector Plug

12 PIN (Male) plug from economizer

Economizer

92-107192-17-00
2

STEP 5: Install ECONOMIZER TPNL (shipped taped to economizer damper) onto unit, at top of economizer (SEE FIGURE 5). This panel provides a transition between the filter door and the hood top. Screw in place through pre-punched hole in panel and into top hole of economizer damper. To ensure proper location, TPNL will be 25 7/8″ from bottom of unit (SEE FIGURE 4).
STEP 6: Locate the lower panel removed in Step 2. Attach the left hood side and right hood side to mounting flange on inside of lower panel. Use supplied screws to screw in place through pre-punched holes in panel. (SEE FIGURE 5).
STEP 7: Locate hood divider A & B from hood package and assemble together using provided screws to create a single hood divider (SEE FIGURE 8). Install the HOOD DIVIDER between the LEFT HOOD SIDE and RIGHT HOOD SIDE (SEE FIGURE 7). Screw in place. Attach partially assembled hood on unit with supplied screws (SEE FIGURE 7).
STEP 8: Insert the permanent filter into the hood using the hood divider to rest the filter on. Install the hood front support bracket at top of hood to hold filters in place (SEE FIGURE 7). Note: mixed air / discharge sensor has been factory installed and wired in unit for economizer use.

STEP 9: Remove the unit panel covering the indoor blower section. Mount the provided C7250 mixed air / discharge air sensor in the indoor blower section. It can be wire tied to harness bundle. Connect two black wires with the 2-pin plug to the sensor. See wiring diagram and Figure 4.
STEP 10: Install all other kits including carbon dioxide sensor, dual enthalpy upgrade kit, etc.
STEP 11: Reinstall the unit’s horizontal return panel and the filter access panel.
STEP 12: Upon unit startup, follow the JADE W7220 economizer controller setup instructions on the following pages.
FIGURE 4

FIGURE 3

Enthalpy Shipping Position

Outside Air Damper
Enthalpy Operating Position
Economizer

Barometric Relief Dampers
*Attach partially assembled hood onto unit with supplied screws (SEE FIGURE 8).
3

92-107192-17-00

FIGURE 5

Hood Side

FIGURE 6

Upper Economizer Panel

Hood Side
FIGURE 7

Lower Panel
Upper Economizer
Panel

FIGURE 8

Economizer

Upper Panel

Hood Top / Lower Panel

FIGURE 9

Hood Top (Lower Panel)

Left Hood Side

*Front Support Bracket

Hood Divider

*Install after hood filters are in place.

Right Hood Side

Economizer Hood

Hood Divider A/B

Permanent Filter

4

92-107192-17-00

FIGURE 10 W7220 JADE economizer controller field-mounted in control compartment of HVAC unit

Unit control board factory-mounted in control compartment of HVAC unit.

92-107192-17-00
5

DIRECT MOUNT ECONOMIZER OPERATION

GENERAL This accessory economizer package is designed to save energy costs by using outdoor air for cooling and ventilation in place of mechanical cooling whenever possible. The economizer continuously monitors indoor and outdoor air conditions and compares them to a user-selected setpoint to determine if free cooling is available. The economizer utilizes a fully-modulating damper actuator, which will control the outside air damper and return air damper in order to maintain a factory-set mixed air/discharge air temperature.
ACCESSORIES
(-)XRX-BV01 – Dual Enthalpy Upgrade Kit For maximum energy savings, this upgrade kit will allow the economizer to compare the outdoor air enthalpy to the return air enthalpy, instead of a user-selected setpoint to determine if “free cooling” is available. This Sylk Bus Sensor is a combination temperature and humidity sensor which is powered by and communicates on the two-wire communication bus of the W7220 economizer logic module. All OA (Outside Air) and RA (Return Air) sensors are the same. Sensor must be set for the type of sensing using the three DIP switches located on the sensor during INSTALLATION.

(-)XRX-AR02 – Wall-Mounted Carbon Dioxide Sensor For installations requiring Demand Control Ventilation (DCV) based upon indoor air levels of carbon dioxide (CO2). When the unit supply fan is running, the CO2 sensor modulates the outside air damper to maintain a user-selected CO2 level inside the occupied space. Energy savings are achieved by not bringing in excessive amounts of outdoor air when the indoor air conditions are suitable. Energy savings can be substantial on buildings with highly variable occupancy rates.
NOTE: The (-)XRX-AR02 has a default setting of a 2-10 Vdc output for a 500-1500 ppm CO2 input. The W7220 economizer controller requires jumper pins on the sensor to be relocated to provide a 0-2000 ppm input.

SW1 ON OFF ON OFF

SW1 ON ON OFF OFF

AN (ppm) 0 to 1000 0 to 2000 500 to 1500 500 to 2000

Relay (ppm) 1000 1200 800 1200

Dip Switch Setting Return Air Enthalpy Sensor Outside Air Enthalpy Sensor

C1 ON OFF

C2 OFF OFF

C3 OFF OFF

RXRX-AR02 NEW JUMPER POSITION

OUT

AN

SW2 SW1

OFF ON OFF ON 0-100% 20-100% )Voltage )Current

DIP SWITCH LABEL DIP SWITCHES (3)

Wiring Schematic for (-)XRX-AR02 Note: Black & brown wire common.

C7232 24V

RED BLACK

ANALOG + OUT –

YELLOW BROWN ORANGE

GREEN

L1 (HOT) L2 1
POWER SUPPLY PROVIDE
1 DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED

Power Exhaust Kit For installations requiring more space static pressure relief than can be obtained with the standard barometric relief damper included with the economizer, a power exhaust kit can be added.

SYLK BUS TERMINALS (1 AND 2)

92-107192-17-00
6

ADJUSTMENT METHOD
The user interface consists of an LCD display and a 4-button keypad on the front of the Economizer module. The LCD is a 16 character by 2 line dot matrix display.
Power Up Cycle
All setpoints and advanced settings are restored after any power loss (a power loss is assumed if voltage falls below 18 Vac). Normal operation is restored when power returns above 18 Vac.
Initial Menu Display
On initial startup, Honeywell displays on the first line and Economizer W7220 on the second line. After a brief pause, the revision of the software appears on the first line (second line is blank). It then displays W7220 on the first line and STATUS on the second line.
Key pad
The four navigation buttons illustrated in Figure 11 are used to scroll through the menus and menu items, select menu items, and to change parameter and configuration settings.
Us ing the Key pad with Menus
To use the keypad when working with menus:
· Press the button to move to the previous menu. · Press the button to move to the next menu. · Press the button (Enter) to display the first item inthe
currently displayed menu. · Press the button (Menu up) to exit a menu’s itemand return
to the list of menus.
Using the Key pad with Settings and Parameters
To use the keypad when working with Setpoints, System and Advanced Settings, Checkout tests, and Alarms:
· Navigate to the desired menu. · Press the button (Enter) to display the first item in the
currently displayed menu. · Use the and buttons to scroll to the desired parameter. · Press the button (Enter) to display the value of the currently
displayed item. · Press the button to increase (change) the displayed
parameter value.a · Press the button to decrease (change) the displayed
parameter value.a · Press the button to accept the displayed value and store it
in non-volatile RAM. · When the value is accepted, CHANGE STORED is displayed
on the LCD. · Press the button (Enter) to return to the current menu
parameter. · Press the button (MenuUp/Exit) to return to the previous
menu.

FIGURE 11
Time-out and Screensaver When no buttons have been pressed for 10 minutes, the LCD displays a screen saver, which cycles through the Status items. Each Status items displays in turn and cycles to the next item after 5 seconds. SETUP AND CONFIGURATION Before being placed into service, the JADETM Economizer module must be setup and configured for the installed system. Use the System Setup menu, the Advanced Setup menu (if necessary), and the Setpoints menu to accomplish this. Menu Structure The following tables illustrate the complete hierarchy of menus and parameters for the JADETM Economizer system. The Menus in display order are: · STATUS · SETPOINTS · SYSTEM SETUP · ADVANCED SETUP · CHECKOUT · ALARMS IMPORTANT Your menu parameters may be different depending on your configuration. For example if you do not have a DCV (CO2) sensor, then none of the DCV parameters appear.
a When values are displayed, pressing and holding the or button causes the display to automatically increment.

92-107192-17-00
7

STATUS MENU

Parameter

Parameter Parameter Default Range and Value Incremeenta

Notes

ECON AVAIL

NO

YES/NO YES = economizing available; the system can use Out door Air for free cooling when required.

ECONOMIZING

NO

YES/NO YES = Outdoor Air being used for 1st stage cooling.

OCCUPIED

NO

YES/NO

YES = 24 Vac OCC signal received from space thermostat in put. NO = 0 Vac on terminal OCC.

HEAT PUMP

COOL COO/HEAT Displays COOL or HEAT when SYSTEM is set to heat pump (nonconventional)

COOL Y1-IN

OFF

ON/OFF

Y1-I signal from space thermostat input for cooling stage 1 or heat pump heating stage 1. ON = 24 Vac on terminal Y1-I OFF = 0 Vac on terminal Y1-I

COOL Y1-OUT

OFF

ON/OFF Cool Stage 1 Relay Output to stage 1 mechanical cooling (Y1-OUT terminal).

COOL Y2-IN

OFF

ON/OFF

Y2-I signal from space thermostat input for second stage cooling or heat pump heating stage 2. ON = 24 Vac on terminal Y2-I OFF = 0 Vac on terminal Y2-I

COOL Y2-OUT

OFF

ON/OFF Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).

MA TEMP

._°F

-40 to 150°F

Displays value of measured mixed air from MAT sensor. Displays -.- if not connected, short, or out-of-range.

DA TEMP

._°F

Displays when Discharge Air Sylk Bus sensor is connected and displays measured discharge -40 to 150°F air temperature. Displays -.-°F if sensor sends in valid value, if not connected, short or
out-of-range.

OA TEMP

._°F

-40 to 140°F

Displays measured value of out door air temperature. Displays -°F if sensor sends in valid value, if not connected, short or out-of-range.

OA HUM

%

0 to 100%

Displays measured value of out door humidity. Displays -% if not connected, short, or out-of-range.

RA TEMP

._°F

0 to 140°F

If field installed Dual Enthalpy sensor is connected, displays measured value of return air temperature. Displays -°F if sensor sends in valid value, if not connected, short or out-of-range.

RA HUM

%

0 to 100%

If field installed Dual Enthalpy sensor is connected, displays measured value of return air humidity. Displays -% if sensor sends in valid value, if not connected, short or out-of-range.

IN CO2

_ppm

“0 to 2000 If field installed CO2 sensor is connected, displays value of measured CO2. In valid if not (3500) ppm” connected, short or out-of-range. May be adjusted in Advanced menu by Zero off set and Span.

DCV STATUS

n/a

n/a

If field in stalled CO2 sensor is connected, displays ON if above setpoint and OFF if be low setpoint.

DAMPER OUT

%

0 to 100%

Displays output position to the damper actuator. When used with Honeywell communicating actuator the damper out is in XX.X%

ACT POS.

n/a

0 to 100% Displays actual position of actuator.

ACT COUNT

n/a

1 to 65,535 Displays number of times actuator has cycled. 1 Cycle equals 180° of movement in any direction.

ACTUATOR

n/a

OK/Alarm Displays Error on ALARM MENU if voltage or torque is below actuator range.

EXH1 OUT

OFF

ON/OFF Output of EXH1 terminal. – ON = relay closed; OFF = relay open.

EXH2 OUT

OFF

ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = EXH2

ERV

OFF

ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = ERV

“MECH COOL ON HEAT STGS ON”

0

0, 1, or 2

Displays stage of mechanical cooling that is active. Displays the stage of heat pump heating that is active.

FAN SPEED

n/a

LOW/HIGH Displays speed of fan on a 2-speed fan unit

W (HEAT IN)

n/a

ON/OFF Displays status of heat on a 2-speed fan unit.

92-107192-17-00
8

SETPOINTS MENU

Parameter MAT SET LOW T LOCK DRYBLB SET DRYBLB DIFF ENTH CURVE DCV SET MIN POS
VENTMAX
VENTMIN
ERV OAT SP EXH1 SET EXH2 SET

Parameter Default Value 53°F 32°F 63°F 0°F ES3
1100 ppm 2.8 V
2.8 V
2.25 V
32°F 50% 75%

Parameter Range and Incremeenta 38 to 70°F; incremented by 1 -45 to 80°F; incremented by 1 48 to 80°F; incremented by 1
0° – 6°F increment of 2°
ES1, ES2, ES3, ES3, or ES5
500 to 2000 ppm increment by 100
2 to 10 Vdc
2 to 10 Vdc
100 to 9990 cfm increment by 10
2 to 10 Vdc
2 to 10 Vdc 100 to 9990 cfm increment by 10
2 to 10 Vdc 0 to 50°F; increment by 1 0 to 100%; increment by 1
0 to 100%; increment by 1

Notes
Setpoint determines where the economizer will modulate the OA damper to maintain the mixed air temperature.
Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout.
Setpoint determines where the economizer will assume outdoor air temperature is good for free cooling; e.g.; at 63ºF unit will economizer at 62ºF and below and not economize at 64ºF and above. There is a 2ºF deadband.
Drybulb Differential will only show if using dual drybulb, i.e. when an ourdoor air temperature air sensor C7250 is attached to OAT terminals, and a C7400S sensor is wirred to S-BUS and configured for RAT (Return Air). Free cooling will be assumed whenever OA temperature is at or below RAT minus this drybulb differential setting.
Does not display if a field installed Dual Enthalpy kit is connected. Enthalpy boundary “curves” for economizing using single enthalpy comparison between outdoor air enthalpy and setpoint.
Displays ONLY if field installed CO2 sensor is connected. Setpoint for Demand Control Ventilation of space. Above the setpoint, the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint.
Displays ONLY if a CO2 sensor is NOT connected.
With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V
Displays only if a field installed CO2 sensor is connected. Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sensor.
If OA, MA, RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM and displays from 100 to 9990 cfm.
With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan) settings are required. Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V.
Dis plays only if field in stalled CO2 sen sor is con nected. Used for Va (ven ti la tion min cfm) setpoint. This is the ven ti la tion re quire ment for less than max i mum oc cu pancy of the space.
If OA, MA, RA and CO2 sen sors are con nected and DCV CAL EN ABLE is set to AUTO mode, the OA damp ers are con trolled by CFM and dis plays from 100 to 9990 cfm.
With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan) set tings are re quired. De fault for VENTMIN L is 2.5V and VENTMIN H is 2.25V.
Only when AUX1 O = ERV
Setpoint for OA damper position when exhaust fan 1 is powered by the economizer. With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%.
Setpoint for OA damper position when exhaust fan 2 is powered by the economizer. Only used when AUX1 O is set to EHX2. With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%.

92-107192-17-00
9

SYSTEM SETUP MENU

Parameter INSTALL UNITS DEG EQUIPMENT
AUX2 IN
FAN TYPE FAN CFM
AUX1 OUT
OCC FACTORY DEFAULT

Parameter Default Value
01/01/2011 °F
HP O/B
W1
2 speed 5000cfm
EXH2
INPUT NO

Parameter Range and Incremeenta

Notes

Display order = MM/DD/YY. Setting order = DD, MM, then YY.

°F or °C

Sets economizer controller in degrees Fahrenheit or Celsius.

CONV HP O/B

HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump (“B” ­ signal) input from thermostat.
CONV = conventional.

Shutdown (SD) Heat (W1) HP(O) HP(B)

In HP O/B mode: HP(O) = energize heat pump on Cool; HP(B) = energize heat pump on Heat.
In CONV mode: SD = Enables configuration of shutdown; W = Informs controller that system is in heating mode. NOTE: If using 2-speed fan mode, you must program CONV mode for W. Shutdown is not available in the two speed fan mode.

1 speed/ 2 speed

Sets economizer controller for operation of 1 speed or 2 speed supply fan NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.

100 to 15000 This is the airflow capacity of the rooftop unit or air handler. The value is found in the

cfm;

unit I&O manual or specification sheet. The cfm of the indoor fan is only used with the

increment by 100 DCVCAL ENA parameter set in the AUTO mode.

NONE ERV EXH2 SYS

· NONE = not configured (output is not used) · ERV= Energy Recovery Ventilator
· EXH2 = second damper position relay closure for second exhaust fan. · SYS = use output as an alarm signal

INPUT or ALWAYS

The indoor fan “G” or “ON” Signal. Can also be used with a setback thermostat with occupancy out (24 Vac), where the 24 Vac is input “INPUT” to the OCC terminal. If no occupancy output from the thermostat then change program to “ALWAYS”.

NO or YES

Resets all set points to factory defaults when set to YES. LCD will briefly flash YES and change to NO but all parameters will change to factory default values.

92-107192-17-00
10

ADVANCE SETUP MENU

Parameter MA LO SET FREEZE POS CO2 ZERO CO2 SPAN
STG3 DLY
SD DMPR POS
DCVCAL ENA
MAT T CAL OAS T CAL OAS H CAL RA T CAL RA H CAL DA T CAL 2SP FAN DELAY

Parameter Default Value 45ºF CLO 0 ppm
2000 ppm
2.0h
CLO
MAN
0.0 F° 0.0F° 0% RH 0.0F° 0% RH 0.0F° 5 Minutes

Parameter Range and Incremeenta 35 to 55ºF increment by 1°
CLO MIN 0 to 500 ppm increment by 10 1000 to 3000 ppm; increment by 50 0 min, 5 min, 15 min, then 15 min intervals. Up to 4h or OFF
CLO OPN
MAN (manual) AUTO
+/-2.5F°
+/-2.5F°
+/-10% RH
+/-2.5F°
+/-10% RH
+/-2.5F°
0 to 20 minutes in 1 minute increments.

Notes
Temp to activate Freeze Protection (close damper and alarm if temp falls below setup value) Damper position when freeze protection is active (closed or MIN POS).
Displays only if field installed CO2 sensor is connected. CO2 ppm level to match CO2 sensor start level.
Displays only if field installed CO2 sensor is connected. CO2 ppm span to match CO2 sensor.
Delay after stage 2 for cool has been active. Turns on 2nd stage of cooling when economizer is 1st stage and mechanical cooling is 2nd stage. Allows three stages of cooling, 1 economizer and 2 mechanical. OFF = no Stage 3 cooling.
Indicates shutdown signal from space thermostat. When controller receives 24 Vac input on the SD terminal in conventional mode, the OA damper will open if programmed for OPN and OA damper will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut off. Displays only if all sensors (RA, OA, MA and CO2) are connected. Turns on the DCV automatic control of the dampers. Resets ventilation based on the RA, OA and MA sensor conditions. This operation is not operable with a 2-speed fan unit. Allows for the operator to adjust for an out of calibration mixed air temperature sensor. Allows for the operator to adjust for an out of calibration outdoor air temperature sensor. Allows for the operator to adjust for an out of calibration outdoor air humidity sensor. If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an out of calibration temperature sensor. If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an out of calibration humidity sensor. Allows for the operator to adjust for an out of calibration Discharge Air Sylk Bus temperature sensor. When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled.

92-107192-17-00
11

CHECKOUT MENU

Parameter
DAMPER VMIN-HS DAMPER VMAX-HS DAMPER VMAX-LS DAMPER OPEN DAMPER CLOSE CONNECT Y1-O CONNECT Y2-O CONNECT EXH1

Parameter Default Value n/a
n/a
n/a n/a n/a n/a n/a

CONNECT EXH2

n/a

Parameter Range and Incremeenta
n/a
n/a
n/a n/a n/a n/a n/a
n/a

Notes
Positions damper to VMIN position Positions damper to VMAX position. With 2-speed fan units the damper will position to VMAX low speed fan. Positions outside air damper to the full open position. Positions outside air damper to the fully closed position. Closes the Y1-O relay (Y1-O); energizes 1st stage compressor. Closes the Y2-O relay (Y2-O); energizes 2nd stage compressor. Closes the power exhaust fan 1 relay (EXH1) Energizes the EXH2 output. The EXH2-O can be replaced by: · ERV · EXH2 · SYS · AUX1 O Based on AUX1 O switch settings or is not available if AUX1 O is set to NONE

Check out Tests Use the Checkout menu to test the damper operation and any configured outputs. Only items that are configured are shown in the Checkout menu. To perform a Checkout test: 1. Scroll to the desired test in the Checkout menu using the and buttons. 2. Press the button to select the item. 3. RUN? appears on the display. 4. Press the button to start the test. 5. The unit pauses and then displays TEST RUNNING. 6. Press the button (Menu up) to end the test (e.g. turn off the relay). Test stops automatically after 10 minutes without a command or
mode change, and will resume normal operation.
The checkout tests can all be performed at the time of installation or any time during the operation of the system as a test that the system is operable.
NOTE: Be sure to allow for enough time for compressor startup and shutdown between checkout tests so that you do not shortcycle the compressors and damage them from extreme short-cycling.

92-107192-17-00
12

ALARM MENU

Parameter
MA T SENS ERR CO2 SENS ERR OA T SENS ERR DA ENTHL ERR
SYS ALARM
ACT UNDER V ACT OVER V ACT STALLED

Parameter Default Value n/a n/a n/a n/a
n/a
n/a n/a n/a

Parameter Range and Incremeenta
n/a n/a n/a n/a
n/a
n/a n/a n/a

Notes
Alarms display only when they are active. The menu title “ALARMS (_)”includes the number of active alarms in parenthesis ().
When AUX1 O is set to SYS and there is any alarm (e.g., failed sensors, etc.), the AUX1 O terminal has 24 Vac out. Voltage received by Actuator is above expected range Voltage received by Actuator is below expected range Actuator stopped before achieving commanded position

Alarms The Economizer module provides alarm messages that display on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before checking for alarms. This allows time for all the configured devices (e.g. sensors, actuator) to become operational. The exception is the MA sensor which will alarm immediately.
If one or more alarms are present and there has been no keypad activity for at least 5 minutes, the Alarms menu displays and cycles through the active alarms. You can also navigate to the Alarms menu at any time.
Clearing Alarms Once the alarm has been identified and the cause has been removed (e.g. replaced faulty sensor), the alarm can be cleared from the display. To clear an alarm, perform the following: 1. Navigate to the desired alarm. 2. Press the button. 3. ERASE? displays. 4. Press the button. 5. ALARM ERASED displays. 6. Press the button (MenuUp/Exit) to complete the action and return to the previous menu.
NOTE: If an alarm still exists after you clear it, it redisplays within 5 seconds.

92-107192-17-00
13

TYPICAL ADJUSTMENTS 1. Economizer ENTH CURVE Setpoint
a. Only the coolest, driest outside air is used for economizer operation when parameter “ES5” is selected on the SETPOINT MENU. Select parameter “ES1” on the SETPOINT MENU for the greatest energy savings.
b. Adjustments are ES1, ES2, ES3, ES4, ES5. c. “ES3” is the default setting. d. Economizer ENTH CURVE Setpoint can be adjusted at
any time and may need adjustment for jobsite conditions.

e. Single enthalpy strategy: If outdoor air enthalpy is lower than the ENTH CURVE setpoint, then free cooling is available.
f. Dual enthalpy strategy: ENTH CURVE Setpoint is not used. If outdoor air enthalpy is lower than return air enthalpy, then free cooling is available. There is also a high limit boundary for dual enthalpy. The high limit boundary is “ES1” when there are no stages of mechanical cooling energized and “HL” when a compressor stage is energized.

JADETMECONOMIZER MODULE

Enthalpy Curve
ES1 ES2 ES3 ES4 ES5 HL

Temp. Dry-Bulb (°F)
80.0 75.0 70.0 65.0 60.0 86.0

Single Enthalpy and Dual Enthalpy High Limit Curves

Temp.

Enthalpy

Dewpoint (°F) (btu/lb/da)

Point P1 Temp. °F Humidity %RH

60.0

28.0

80.0

36.8

57.0

26.0

75.0

39.6

54.0

24.0

70.0

42.3

51.0

22.0

65.0

44.8

48.0

20.0

60.0

46.9

66.0

32.4

86.0

38.9

Point P2

Temp. °F Humidity %RH

66.3

80.1

63.3

80.0

59.7

81.4

55.7

84.2

51.3

88.5

72.4

80.3

2. EXH1 SET – Adjustments for (optional) power exhaust.

3. EXH2 SET – Adjustments for (optional) 2 speed power exhaust.

a. The outside air damper position at which the power

a. The outside air damper position at which the 2nd speed of

exhaust fan(s) will engage.

the power exhaust fan(s) will engage.

b. With 2-speed indoor fan units EXH1 L (low speed fan) and EXH1 H (high speed fan) settings are required.
c. Default for EXH1 L is 65% and EXH1 H is 50%.
d. After the outside air damper output command DAMPER OUT (not ACT POS.) reaches the power exhaust setpoint, the power exhaust output EXH1 is energized after a 45 second delay.
e. Range of adjustment is from 0-100% outside air.

b. With 2-speed indoor fan units EXH2 L (low speed fan) and EXH2 H (high speed fan) settings are required.
c. Default for EXH2 L is 80% and EXH2 H is 75%. d. After the outside air damper output command DAMPER
OUT (not ACT POS.) reaches the power exhaust setpoint, the power exhaust output EXH2 is energized after a 45 second delay to allow the damper to reach the appropriate position. e. Range of adjustment is from 0-100% outside air.

92-107192-17-00
14

4. MIN POS – Outside Air Damper minimum position

NORMAL OPERATION

a. Displays ONLY if a CO2 sensor is NOT connected. With 1. Fan Only (G)

2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V.
b. Adjust MIN POS to allow the minimum amount of outdoor air, as required by local codes, to enter the building.
c. Range of adjustment is from 0-100% (2-10V); in most applications MIN POS is adjusted to allow 10% to 25% outside air to enter the system.

a. Damper will go to minimum position (in 90 seconds or less) whenever the “G” (supply fan) signal is present.
b. When “G” signal is removed, the outside air damper closes against blade seals for tight shutoff of outside air.
c. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then the control will override the minimum position setting and will modulate the outside air damper closed.

d. MIN POS can be adjusted at any time.

2. Call for First Stage of Cooling (Y1)

e. Whenever the “G” (supply fan) signal is present, the

a. Economizer Unavailable (warm outdoor air): Closes the

damper will open to this minimum position unless the

Y1-O relay (Y1-O) which energizes 1st stage compressor.

mixed air sensor falls below the MA LO SET (Freeze

b. Economizer Available (free cooling): The controller tries to

Protect Mode Setpoint).

maintain a mixed air temperature of 53°F ± 5 (MAT SET

5. VENTMAX – Demand Control Ventilation (DCV) Maximum

Setpoint) by modulating the outside air damper position.

Setpoint

3. Call for Second Stage of Cooling (Y2)

a. Displays only if a CO2 sensor is connected.

a. Economizer Unavailable (warm outdoor air): Closes the

b. VENTMAX allows the installer to limit the amount of

Y2-O relay (Y2-O) which energizes 2nd stage compressor.

outdoor airflow into the building when DCV overrides the mixed air temperature sensor setpoint. It is normally equal to the minimum amount of outdoor air under maximum occupancy, as required by local codes, to enter the
building.

b. Economizer Available (free cooling): Closes the Y1-O
relay (Y1-O) which energizes 1st stage compressor. The controller tries to maintain a mixed air temperature of 53°F ± 5 (MAT SET Setpoint) by modulating the outside air damper position. After a time period of 2 hours of

c. VENTMAX can be adjusted at any time.

simultaneous economizer operation and first stage

6. VENTMIN – Demand Control Ventilation (DCV) Setpoint

compressor operation, the economizer closes the Y2-O

a. Displays only if a CO2 sensor is connected.

relay (Y2-O) which energizes 2nd stage compressor.

b. Is the ventilation requirement for less than maximum 4. Call for Heat

occupancy of the space.

a. Standard Air Conditioner with electric or gas heat.(W1 &

c. Compatible CO2 sensors will have a 2-10Vdc output for a

W2)

0-2000 ppm CO2 input.

i. The Thermostat controls the stages of heating

d. DCV modulates the outdoor damper between the

directly.

VENTMIN and VENTMAX settings to provide ventilation based on occupancy. The carbon dioxide (CO2) sensor is used to indirectly monitor occupancy level.

ii. If the control detects that the supply fan is on (through its “G” input), then the control will open the damper to minimum position.

e. No cooling signal (e.g.Y1, Y2) is required for DCV to override the outdoor air damper when ventilation requires

iii. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then the control will override

outdoor air.

the minimum position setting and will modulate the

f. The controller must receive a “G” (supply fan) signal to

outdoor damper closed.

open the damper.

b. Heat Pump Operation (B)

g. Range of adjustment is from 2 Volts to 10 Volts.

i. The “B” signal from the Thermostat allows operation

h. VENTMIN can be adjusted at any time.

of the compressors to provide heating without delay.

i. The controller compares the CO2 sensor input to VENT MIN to determine the damper minimum position.
i. If the actual CO2 level is below the setpoint, then the damper minimum position is determined by the damper minimum position (VENTMIN) setting.
ii. If the actual CO2 level rises above the setpoint, then the damper minimum position is overridden

ii. If the control detects that the supply fan is on (through its “G” input), then the control can open the damper to minimum position.
iii. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then the control will override the minimum position setting and will modulate the outdoor damper closed.

proportionally more open up to the VENTMAX setting.

iii. If the mixed air temperature drops below 45°F (MA LO SET – Freeze Protect Mode Setpoint), the DCV

input will be overridden and the damper may not

open.

j. Ensure proper polarity of the sensor wires when connecting

to the economizer controller. Incorrect polarity negates

the sensor signal.

92-107192-17-00
15

NOTES
1. This economizer requires a two-stage thermostat.
2. When diagnosing the system, the best results are obtained by first putting the fan setting on the Thermostat to the “Continuous Fan” mode.
3. Operation of the optional power exhaust only depends upon the supply fan running and the damper position (it is possible to set the minimum position high enough to engage the power exhaust in the heating mode).

4. Upon loss of power to the unit or economizer, the outside air damper will spring close shut in about 5 seconds.
5. Compressor Time Delays, Compressor Interstage Delays are not provided by the economizer controller.

DCV None
Below Setpoint
Above Setpoint

Table of Inputs and Output Response with and without a CO2 Sensor (DCV)

Inputs to Controller

Outputs from Controller

Free Cooling Y1-I
Available?

Y2-I AUX2-I FAN Y1-O Y2-O

OA Damper Position

OFF

OFF

OFF

OFF

OFF

OFF

CLOSED

OFF

OFF

OFF

ON

OFF

OFF

MIN POS

ON

OFF

OFF

ON

ON

OFF

NO

ON

ON

OFF

ON

ON

ON

MIN POS MIN POS

ON

OFF

ONd

ON

ON

OFF

MIN POS

ON

ON

ONd

ON

ON

ON

MIN POS

OFF

OFF

OFF

ON

OFF

OFF

MIN POS

ON

OFF

OFF

ON

OFF

OFF

MIN POS to 100%

YES

ON

ON

OFF

ON

ON

OFFb

MIN POS to 100%

ON

OFF

ONd

ON

ON

OFF

MIN POS

ON

ON

ONd

ON

ON

ON

MIN POS

OFF OFF

OFF

ON

OFF OFF

VENTMIN

ON

OFF

OFF

ON

ON

OFF

VENTMIN

NO

ON

ON

OFF

ON

ON

ON

VENTMIN

ON

OFF

ONd

ON

ON

OFF

VENTMIN

ON

ON

ONd

ON

ON

ON

VENTMIN

OFF

OFF

OFF

ON

OFF

OFF

VENTMIN

ON

OFF

OFF

ON

OFF

OFF

VENTMIN to 100%

YES

ON

ON

OFF

ON

ON

OFFb

VENTMIN to 100%

ON

OFF

ONd

ON

ON

OFF

VENTMIN

ON

ON

ONd

ON

ON

ON

VENTMIN

OFF

OFF

OFF

ONc

OFF

OFF

VENTMIN to VENTMAX

ON

OFF

OFF

ON

ON

OFF

VENTMIN to VENTMAX

NO

ON

ON

OFF

ON

ON

ON

VENTMIN to VENTMAX

ON

OFF

ONd

ON

ON

OFF

VENTMIN to VENTMAX

ON

ON

ONd

ON

ON

ON

VENTMIN to VENTMAX

OFF

OFF

OFF

ONc

OFF

OFF

VENTMIN to VENTMAX

ON

OFF

OFF

ON

OFF

OFF

VENTMIN to 100%

YES

ON

ON

OFF

ON

ON

OFFb

VENTMIN to 100%

ON

OFF

ONd

ON

ON

OFF

VENTMIN to VENTMAX

ON

ON

ONd

ON

ON

ON

VENTMIN to VENTMAX

B With STG3 DLY in ADVANCED SETUP MENU at 2.0 hours, the 2nd stage of mechanical cooling Y2-O can be energized after a 2 hour delay if the call for Y1-I and Y2-I have not been satisfied.
C The CO2 sensor has a relay output that is active when the CO2 level is above 1200ppm that can be used to energize the indoor fan through the “G” thermostat input of the unit even if there is not a call for fan, cooling or heating by the room thermostat. Additional field wiring is required to enable this option.
D AUX2-I is used only on heat pump models to indicate unit is in heat pump (heating) mode.

92-107192-17-00
16

DCV None Below Setpoint Above Setpoint

Table of Inputs and Output Response with and without a CO2 Sensor (DCV) for Unoccupied Mode

Inputs to Controller

Outputs from Controller

Free Cooling Available?

Y1-I

Y2-I AUX2-I FAN

Y1-O Y2-O

OA Damper Position (Unoccupied)*

OFF

OFF

OFF

OFF

OFF

OFF

CLOSED

OFF

OFF

OFF

ON

OFF

OFF

CLOSED

ON

OFF

OFF

ON

ON

OFF

NO

ON

ON

OFF

ON

ON

ON

CLOSED CLOSED

ON

OFF

ONd

ON

ON

OFF

CLOSED

ON

ON

ONd

ON

ON

ON

CLOSED

OFF

OFF

OFF

ON

OFF

OFF

CLOSED

ON

OFF

OFF

ON

OFF

OFF

CLOSED to 100%

YES

ON

ON

OFF

ON

ON

OFFb

CLOSED to 100%

ON

OFF

ONd

ON

ON

OFF

CLOSED

ON

ON

ONd

ON

ON

ON

CLOSED

OFF

OFF

OFF

ON

OFF OFF

CLOSED

ON

OFF

OFF

ON

ON

OFF

CLOSED

NO

ON

ON

OFF

ON

ON

ON

CLOSED

ON

OFF

ONd

ON

ON

OFF

CLOSED

ON

ON

ONd

ON

ON

ON

CLOSED

OFF

OFF

OFF

ON

OFF

OFF

CLOSED

ON

OFF

OFF

ON

OFF

OFF

CLOSED to 100%

YES

ON

ON

OFF

ON

ON

OFFb

CLOSED to 100%

ON

OFF

ONd

ON

ON

OFF

CLOSED

ON

ON

ONd

ON

ON

ON

CLOSED

OFF

OFF

OFF

ONc

OFF

OFF

CLOSED

ON

OFF

OFF

ON

ON

OFF

CLOSED

NO

ON

ON

OFF

ON

ON

ON

CLOSED

ON

OFF

ONd

ON

ON

OFF

CLOSED

ON

ON

ONd

ON

ON

ON

CLOSED

OFF

OFF

OFF

ONc

OFF

OFF

CLOSED

ON

OFF

OFF

ON

OFF

OFF

CLOSED to 100%

YES

ON

ON

OFF

ON

ON

OFFb

CLOSED to 100%

ON

OFF

ONd

ON

ON

OFF

CLOSED

ON

ON

ONd

ON

ON

ON

CLOSED

e Unoccupied Mode is only available by field wiring a normally open (NO) relay in the “G” signal wiring between the unit and economizer. A thermostat with an occupied output is required which energizes the relay when the space is occupied. The relay interrupts the 24 volt “G” signal from the unit indoor fan when the space is unoccupied.
Mixed Air / Discharge Air Temperature vs. Resistance

92-107192-17-00
17

Jade W7220 Economizer Wiring Diagram
MS3105

92-107192-17-00
18

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals