JADE RXRD-01MDDAM3 Vertical Airflow Economizers Installation Guide
- September 17, 2024
- jade
Table of Contents
INSTALLATION INSTRUCTIONS
MODELS RXRD-01MDDAM3
VERTICAL AIRFLOW ECONOMIZERS
RXRD-01MDDAM3 Vertical Airflow Economizers
WARNING
THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO
AVOID UNSATISFACTORY OPERATION OR DAMAGE TO THE PRODUCT AND POSSIBLE UNSAFE
CONDITIONS, INCLUDING ELECTRICAL SHOCK, REFRIGERANT LEAKAGE AND FIRE, THE
INSTALLATION INSTRUCTIONS PROVIDED WITH THIS ACCESSORY MUST BE STRICTLY
FOLLOWED AND THE PARTS SUPPLIED USED WITHOUT SUBSTITUTION. DAMAGE TO THE
PRODUCT RESULTING FROM NOT FOLLOWING THE INSTRUCTIONS OR USING UNAUTHORIZED
PARTS MAY BE EXCLUDED FROM THE MANUFACTURER’S WARRANTY COVERAGE.
WARNING
DISCONNECT ELECTRICAL POWER TO THE UNIT. FAILURE TO DO SO CAN CAUSE ELECTRICAL
SHOCK RESULTING IN PERSONAL INJURY OR DEATH.
WARNING
ADDING POWERED EXHAUST MAY BE REQUIRED IN BUILDINGS WITH EXCESSIVE ENVELOPE
AIR LOSSES AND/ OR RESTRICTIVE RETURN AIR CONDITIONS TO THE UNIT PREVENTING
ADEQUATE RETURN AIR TO THE UNIT WHEN ECONOMIZER IS OPEN TO OUTSIDE AIR.
TOOLS REQUIRED FOR INSTALLTION:
3/8” Electric drill with 5/16” socket awl
TABLE 1
ITEM | DESCRIPTION | QTY | PART NO. |
---|---|---|---|
1 | Economizer with actuator and outside air enthalpy sensor | 1 | |
2 | Economizer upper panel | 1 | |
3 | Hood left side | 1 | |
4 | Hood right side | 1 | |
5 | Hood divider | 1 | |
6 | Permanent water entrainment filter 20” x 20” x 1” | 1 | |
7 | JADE W7220 controller with attached wiring harness | 1 | |
8 | Hardware bag with mixed air temperature sensor | 2 |
Note: This economizer meets state and national codes for leakage. The economizer must be installed square with +/- 1/32” to maintain tight damper seal.
STEP 1:
Immediately upon receipt, all cartons and contents should be inspected for
transit damage. Units with damaged cartons should be opened immediately. If
damage is found, it should be noted on the delivery papers and a damage claim
filed with the last carrier. Compare carton(s) contents to the PACKAGE
CONTENTS List (Table 1) above to note any missing items.
STEP 2:
Remove HORIZONTAL RETURN COVER, TOP FILTER ACCESS DOOR, and LOWER PANEL from
the unit and retain for reuse (SEE FIGURE 1). Retain screws. Note: the bottom
panel will be used for the top of the economizer hood.
STEP 3:
Remove the jumper plug (PL7) from economizer harness in HVAC unit. Slide the
economizer into the return air section (SEE FIGURES 2 and 3). Screw in place.
After economizer is installed, connect unit’s 12-pin ECONOMIZER PLUG (PL6??)
to economizer mating plug (PL20??). If not using a field-installed smoke
detector kit, reinstall the jumper plug (PL7) into other 12-pin plug from
economizer – note this 12pin plug will have only 3 wires connected to it. If
using a fieldinstalled smoke detector, discard the jumper plug (PL7) and
install the smoke detector kit using provided instructions.
STEP 4:
Relocate the outside air enthalpy sensor from its shipping location to its
operating position (SEE FIGURE 3). Screw in place. Remove the tape holding
relief dampers closed.
Note: if using optional power exhaust kit, install it before the next
step.
STEP 5:
Install UPPER ECONOMIZER PANEL onto unit, at top of economizer (SEE FIGURE 4).
This panel provides a transition between the filter door and the hood top.
Screw in place through pre-punched hole in panel and into top hole of
economizer damper.
To ensure proper location, UPPER PANEL will be 25 7/8” from bottom of unit as
shown in FIGURE 4.
STEP 6:
Locate the LOWER PANEL removed in STEP 2 and slide it underneath the
ECONOMIZER UPPER PANEL. Note the LOWER PANEL is used as the hood top. Insert
LEFT HOOD SIDE and RIGHT HOOD SIDE under the LOWER PANEL. Screw hood together
(SEE FIGURE 5).
STEP 7:
Install the HOOD DIVIDER between the LEFT HOOD SIDE and RIGHT HOOD SIDE (SEE
FIGURE 6). Screw in place. Insert the permanent filter into the hood using the
hood divider to rest the filter on, and using filter clips at top of hood to
retain it in place (SEE FIGURE 7).
STEP 8:
With all line high voltage to unit disconnected, remove the panel on back side
of unit covering the unit’s electrical control box. The Honeywell JADE W7220
controller is provided with an attached wiring harness installed, and must be
field-installed in the control box of the unit as shown in FIGURE 8 below. The
mounting holes for the JADE controller are pre-punched to ensure proper
location.
The unit’s economizer harness factory-mounted in the unit is factory-plugged
into the unit control board inside the unit control compartment. The plug on
the end of the unit’s economizer harness has 12-pin terminals.
Unplug the unit’s economizer harness from the unit terminal board, and
reconnect it to the female 12-pin plug on the JADE W7220 controller harness.
Connect the 12-pin male plug on the JADE
W7220 controller harness onto the unit’s terminal board. See wiring diagram in
this instruction.
Note: mixed air / discharge sensor has been factory installed and wired
in unit for economizer use.
STEP 9:
Install all other kits including carbon dioxide sensor, dual enthalpy upgrade
kit, etc.
STEP 10:
Reinstall the unit’s horizontal return panel and the filter access panel.
STEP 11:
Upon unit startup, follow the JADE W7220 economizer controller setup
instructions on the following pages.
DIRECT MOUNT ECONOMIZER OPERATION
GENERAL
This accessory economizer package is designed to save energy costs by using
outdoor air for cooling and ventilation in place of mechanical cooling
whenever possible. The economizer continuously monitors indoor and outdoor air
conditions and compares them to a user-selected setpoint to determine if free
cooling is available. The economizer utilizes a fully-modulating damper
actuator, which will control the outside air damper and return air damper in
order to maintain a factory-set mixed air/discharge air temperature.
ACCESSORIES
(-)XRX-AV04 – Dual Enthalpy Upgrade Kit For maximum energy savings, this
upgrade kit will allow the economizer to compare the outdoor air enthalpy to
the return air enthalpy, instead of a user-selected setpoint to determine if
“free cooling” is available. This Sylk Bus Sensor is a combination temperature
and humidity sensor which is powered by and communicates on the two-wire
communication bus of the W7220 economizer logic module. All OA (Outside Air)
and RA (Return Air) sensors are the same. Sensor must be set for the type of
sensing using the three DIP switches located on the sensor during
INSTALLATION.
Dip Switch Setting | C1 | C2 | C3 |
---|---|---|---|
Return Air Enthalpy Sensor | ON | OFF | OFF |
Outside Air Enthalpy Sensor | OFF | OFF | OFF |
(-)XRX-AR02 – Wall-Mounted Carbon Dioxide Sensor For installations requiring
Demand Control Ventilation (DCV) based upon indoor air levels of carbon
dioxide (CO2). When the unit supply fan is running, the CO2 sensor modulates
the outside air damper to maintain a user-selected CO2 level inside the
occupied space.
Energy savings are achieved by not bringing in excessive amounts of outdoor
air when the indoor air conditions are suitable. Energy savings can be
substantial on buildings with highly variable occupancy rates.
NOTE: The (-)XRX-AR02 has a default setting of a 2-10 Vdc output for a
500-1500 ppm CO2 input. The W7220 economizer controller requires jumper pins
on the sensor to be relocated to provide a 0-2000 ppm input.
SW1 | SW1 | AN (ppm) | Relay (ppm) |
---|---|---|---|
ON | ON | 0 to 1000 | 1000 |
OFF | ON | 0 to 2000 ← | 1200 |
ON | OFF | 500 to 1500 | 800 |
OFF | OFF | 500 to 2000 | 1200 |
Power Exhaust Kit
For installations requiring more space static pressure relief than can be
obtained with the standard barometric relief damper included with the
economizer, a power exhaust kit can be added.
ADJUSTMENT METHOD
The user interface consists of an LCD display and a 4-button keypad on the
front of the Economizer module. The LCD is a 16 character by 2 line dot matrix
display.
Power Up Cycle
All setpoints and advanced settings are restored after any power loss (a power
loss is assumed if voltage falls below 18 Vac). Normal operation is restored
when power returns above 18 Vac.
Initial Menu Display
On initial startup, Honeywell displays on the first line and Economizer W7220
on the second line. After a brief pause, the revision of the software appears
on the first line (second line is blank). It then displays W7220 ↓ on the
first line and STATUS on the second line.
Key pad
The four navigation buttons illustrated in Figure 9 are used to scroll through
the menus and menu items, select menu items, and to change parameter and
configuration settings.
Us ing the Key pad with Menus
To use the keypad when working with menus:
-
Press the ▲ button to move to the previous menu.
-
Press the ▼ button to move to the next menu.
-
Press the ← button (Enter) to display the first item in the currently displayed menu.
-
Press the ↑ button (Menu up) to exit a menu’s item and return to the list of menus.
Using the Key pad with Settings and Parameters To use the keypad when working with Setpoints, System and Advanced Settings, Checkout tests, and Alarms: -
Navigate to the desired menu.
-
Press the ← button (Enter) to display the first item in the currently displayed menu.
-
Use the ▲ and ▼ buttons to scroll to the desired parameter.
-
Press the ← button (Enter) to display the value of the currently displayed item.
-
Press the ▲ button to increase (change) the displayed parameter value. a
-
Press the ▼ button to decrease (change) the displayed parameter value. a
-
Press the ← button to accept the displayed value and store it in non-volatile RAM.
-
When the value is accepted, CHANGE STORED is displayed on the LCD.
-
Press the ← button (Enter) to return to the current menu parameter.
-
Press the ↑ button (MenuUp/Exit) to return to the previous menu.
Time-out and Screensaver
When no buttons have been pressed for 10 minutes, the LCD displays a screen
saver, which cycles through the Status items.
Each Status items displays in turn and cycles to the next item after 5
seconds.
SETUP AND CONFIGURATION
Before being placed into service, the JADE™ Economizer module must be setup
and configured for the installed system. Use the System Setup menu, the
Advanced Setup menu (if necessary), and the Setpoints menu to accomplish this.
Menu Structure
The following tables illustrate the complete hierarchy of menus and parameters
for the JADE™ Economizer system.
The Menus in display order are:
- STATUS
- SETPOINTS
- SYSTEM SETUP
- ADVANCED SETUP
- CHECKOUT
- ALARMS
IMPORTANT
Your menu parameters may be different depending on your configuration. For
example if you do not have a DCV (CO2) sensor, then none of the DCV parameters
appear.
When values are displayed, pressing and holding the ▲ or ▼ button causes the
display to automatically increment.
STATUS MENU
Parameter| Parameter Default Value| Parameter Range and
Incremeent a| Notes
---|---|---|---
ECON AVAIL| NO| YES/NO| YES = economizing available; the system can use Out
door Air for free cooling when required.
ECONOMIZING| NO| YES/NO| YES = Outdoor Air being used for 1st stage cooling.
OCCUPIED| NO| YES/NO| YES = 24 Vac OCC signal received from space thermostat
in put.
NO = 0 Vac on terminal OCC.
HEAT PUMP| COOL| COO/HEAT| Displays COOL or HEAT when SYSTEM is set to heat
pump (nonconventional)
COOL Y1-IN| OFF| **** ON/OFF| Y1-I signal from space thermostat input for
cooling stage 1 or heat pump heating stage 1. ON = 24 Vac on terminal Y1-I OFF
= 0 Vac on terminal Y1-I
COOL Y1-OUT| OFF| ON/OFF| Cool Stage 1 Relay Output to stage 1 mechanical
cooling (Y1-OUT terminal).
COOL Y2-IN| OFF| ON/OFF| Y2-I signal from space thermostat input for second
stage cooling or heat pump heating stage 2. ON = 24 Vac on terminal Y2-I OFF =
0 Vac on terminal Y2-I
COOL Y2-OUT| OFF| ON/OFF| Cool Stage 2 Relay Output to mechanical cooling
(Y2-OUT terminal).
MA TEMP| .°F| -40 to 150°F| Displays value of measured mixed air from MAT
sensor. Displays -.- if not connected, short, or out-of-range.
DA TEMP| .°F| -40 to 150°F| Displays when Discharge Air Sylk Bus sensor is
connected and displays measured discharge air temperature. Displays -.-°F if
sensor sends in valid value, if not connected, short or out-of-range.
OA TEMP| .°F| -40 to 140°F| Displays measured value of out door air
temperature. Displays -°F if sensor sends in valid value, if not connected,
short or out-of-range.
OA HUM| %| 0 to 100%| Displays measured value of out door humidity.
Displays -% if not connected, short, or out-of-range.
RA TEMP| .°F| 0 to 140°F| If field installed Dual Enthalpy sensor is
connected, displays measured value of return air temperature. Displays -°F if
sensor sends in valid value, if not connected, short or out-of-range.
RA HUM| %| 0 to 100%| If field installed Dual Enthalpy sensor is connected,
displays measured value of return air humidity. Displays -% if sensor sends in
valid value, if not connected, short or out-of-range.
IN CO2| ppm| “0 to 2000 (3500) ppm”| If field installed CO2 sensor is
connected, displays value of measured CO2. In valid if not connected, short or
out-of-range. May be adjusted in Advanced menu by Zero off set and Span.
DCV STATUS| n/a| n/a| If field in stalled CO2 sensor is connected, displays ON
if above setpoint and OFF if be low setpoint.
DAMPER OUT| _%| 0 to 100%| Displays output position to the damper actuator.
When used with Honeywell communicating actuator the damper out is in XX.X%
ACT POS.| n/a| 0 to 100%| Displays actual position of actuator.
ACT COUNT| n/a| 1 to 65,535| Displays number of times actuator has cycled. 1
Cycle equals 180° of movement in any direction.
ACTUATOR| n/a| OK/Alarm| Displays Error on ALARM MENU if voltage or torque is
below actuator range.
EXH1 OUT| OFF| ON/OFF| Output of EXH1 terminal. – ON = relay closed; OFF =
relay open.
EXH2 OUT| OFF| ON/OFF| Output of AUX1 O terminal; displays only if AUX1 O =
EXH2
ERV| OFF| ON/OFF| Output of AUX1 O terminal; displays only if AUX1 O = ERV
“MECH COOL ON HEAT STGS ON”| 0| 0, 1, or 2| Displays stage of mechanical
cooling that is active. Displays the stage of heat pump heating that is
active.
FAN SPEED| n/a| LOW/HIGH| Displays speed of fan on a 2-speed fan unit
W (HEAT IN)| n/a| ON/OFF| Displays status of heat on a 2-speed fan unit.
SETPOINTS MENU
Parameter| Parameter Default Value| Parameter Range and
Incremeenta| Notes
---|---|---|---
MAT SET| 53°F| 38 to 70°F; incremented by 1| Setpoint determines where the
economizer will modulate the OA damper to maintain the mixed air temperature.
LOW T LOCK| 32°F| -45 to 80°F; incremented by 1| Setpoint determines outdoor
temperature when the mechanical cooling cannot be turned on. Commonly referred
to as the Compressor lockout.
DRYBLB SET| 63°F| 48 to 80°F; incremented by 1| Setpoint determines where the
economizer will assume outdoor air temperature is good for free cooling; e.g.;
at 63ºF unit will economizer at 62ºF and below and not economize at 64ºF and
above. There is a 2ºF deadband.
ENTH CURVE| ES3| ES1, ES2, ES3, ES3, or ES5| Does not display if a field
installed Dual Enthalpy kit is connected. Enthalpy boundary “curves” for
economizing using single enthalpy comparison between outdoor air enthalpy and
setpoint.
DCV SET| 1100 ppm| 500 to 2000 ppm increment by 100| Displays ONLY if field
installed CO2 sensor is connected. Setpoint for Demand Control Ventilation of
space. Above the setpoint, the OA dampers will modulate open to bring in
additional OA to maintain a space ppm level below the setpoint.
MIN POS| 2.8 V| 2 to 10 Vdc| Displays ONLY if a CO2 sensor is NOT connected.
With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed
fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is
2.8V
VENTMAX| 2.8 V| 2 to 10 Vdc| Displays only if a field installed CO2 sensor is
connected. Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the same
setting as MIN POS would be if you did not have the CO2 sensor.
100 to 9990 cfm increment by 10| If OA, MA, RA and CO2 sensors are connected
and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM
and displays from 100 to 9990 cfm.
2 to 10 Vdc| With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H
(high speed fan) settings are required. Default for VENTMAX L is 3.2V and
VENTMAX H is 2.8V.
VENTMIN| 2.25 V| 2 to 10 Vdc| Dis plays only if field in stalled CO2 sen sor
is con nected. Used for Va (ven ti la tion min cfm) setpoint. This is the ven
ti la tion re quire ment for less than max i mum oc cu pancy of the space.
100 to 9990 cfm increment by 10| If OA, MA, RA and CO2 sen sors are con nected
and DCV CAL EN ABLE is set to AUTO mode, the OA damp ers are con trolled by
CFM and dis plays from 100 to 9990 cfm.
2 to 10 Vdc| With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H
(high speed fan) set tings are re quired. De fault for VENTMIN L is 2.5V and
VENTMIN H is 2.25V.
ERV OAT SP| 32°F| 0 to 50°F; increment by 1| Only when AUX1 O = ERV
EXH1 SET| 50%| 0 to 100%; increment by 1| Setpoint for OA damper position when
exhaust fan 1 is powered by the economizer. With 2-speed fan units Exh1 L (low
speed fan) and Exh1 H (high speed fan) settings are required. Default for Exh1
L is 65% and Exh1 H is 50%.
EXH2 SET| 75%| 0 to 100%; increment by 1| Setpoint for OA damper position when
exhaust fan 2 is powered by the economizer. Only used when AUX1 O is set to
EHX2. With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed
fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%.
SYSTEM SETUP MENU
Parameter| Parameter Default Value| Parameter Range and
Incremeent a| Notes
---|---|---|---
INSTALL| 01/01/2011| | Display order = MM/DD/YY. Setting order = DD, MM, then
YY.
UNITS DEG| °F| °F or °C| Sets economizer controller in degrees Fahrenheit or
Celsius.
EQUIPMENT| HP O/B| CONV HP O/B| HP O/B = Enables Heat Pump mode. Use AUX2 I
for Heat Pump (“B” – signal) input from thermostat. CONV = conventional.
AUX2 I| HP(B)| Shutdown (SD) Heat (W1) HP(O) HP(B)| In HP O/B mode: HP(O) =
energize heat pump on Cool; HP(B) = energize heat pump on Heat.In CONV mode:
SD = Enables configuration of shutdown; W = Informs controller that system is
in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode for W. Shutdown is
not available in the two speed fan mode.
FAN TYPE| 1 speed| 1 speed/ 2speed| Sets economizer controller for operation
of 1 speed or 2 speed supply fan NOTE: 2-speed fan option also needs Heat (W1)
programmed in AUX 2 In.
FAN CFM| 5000cfm| 100 to 15000 cfm; increment by 100| This is the airflow
capacity of the rooftop unit or air handler. The value is found in the unit
I&O manual or specification sheet. The cfm of the indoor fan is only used with
the DCVCAL ENA parameter set in the AUTO mode.
AUX1 OUT| EXH2| NONE ERV EXH2 SYS| • NONE = not configured (output is
not used)
• ERV= Energy Recovery Ventilator
• EXH2 = second damper position relay closure for second exhaust fan.
• SYS = use output as an alarm signal
OCC| INPUT| INPUT or ALWAYS| The indoor fan “G” or “ON” Signal. Can also be
used with a setback thermostat with occupancy out (24 Vac), where the 24 Vac
is input “INPUT” to the OCC terminal. If no occupancy output from the
thermostat then change program to “ALWAYS”.
FACTORY DEFAULT| NO| NO or YES| Resets all set points to factory defaults when
set to YES. LCD will briefly flash YES and change to NO but all parameters
will change to factory default values.
ADVANCE SETUP MENU
Parameter| Parameter Default Value| Parameter Range and
Incremeent a| Notes
---|---|---|---
MA LO SET| 45ºF| 35 to 55ºF increment by 1°| Temp to activate Freeze
Protection (close damper and alarm if temp falls below setup value)
FREEZE POS| CLO| CLO MIN| Damper position when freeze protection is active
(closed or MIN POS).
CO2 ZERO| 0 ppm| 0 to 500 ppm increment by 10| Displays only if field
installed CO2 sensor is connected. CO2 ppm level to match CO2 sensor start
level.
CO2 SPAN| 2000 ppm| 1000 to 3000 ppm; increment by 50| Displays only if field
installed CO2 sensor is connected. CO2 ppm span to match CO2 sensor.
STG3 DLY| 2.0h| 0 min, 5 min, 15 min, then 15 min intervals. Up to 4h or OFF|
Delay after stage 2 for cool has been active. Turns on 2nd stage of cooling
when economizer is 1st stage and mechanical cooling is 2nd stage. Allows three
stages of cooling, 1 economizer and 2 mechanical. OFF = no Stage 3 cooling.
SD DMPR POS| CLO| CLO OPN| Indicates shutdown signal from space thermostat.
When controller receives 24 Vac input on the SD terminal in conventional mode,
the OA damper will open if programmed for OPN and OA damper will close if
programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut
off.
DCVCAL ENA| MAN| MAN (manual) AUTO| Displays only if all sensors (RA, OA, MA
and CO2) are connected. Turns on the DCV automatic control of the dampers.
Resets ventilation based on the RA, OA and MA sensor conditions. This
operation is not operable with a 2-speed fan unit.
MAT T CAL| 0.0 F°| +/-2.5F°| Allows for the operator to adjust for an out of
calibration mixed air temperature sensor.
OAS T CAL| 0.0F°| +/-2.5F°| Allows for the operator to adjust for an out of
calibration outdoor air temperature sensor.
OAS H CAL| 0% RH| +/-10% RH| Allows for the operator to adjust for an out of
calibration outdoor air humidity sensor.
RA T CAL| 0.0F°| +/-2.5F°| If field installed Dual Enthalpy sensor is
connected, allows for the operator to adjust for an out of calibration
temperature sensor.
RA H CAL| 0% RH| +/-10% RH| If field installed Dual Enthalpy sensor is
connected, allows for the operator to adjust for an out of calibration
humidity sensor.
DA T CAL| 0.0F°| +/-2.5F°| Allows for the operator to adjust for an out of
calibration Discharge Air Sylk Bus temperature sensor.
2SP FAN DELAY| 5 Minutes| 0 to 20 minutes in 1 minute increments.| When in
economizing mode this is the delay for the high speed fan to try to satisfy
the call for second stage cooling before the first stage mechanical cooling is
enabled.
CHECKOUT MENU
Parameter| Parameter Default Value| Parameter Range and
Incremeenta| Notes
---|---|---|---
DAMPER VMIN-HS| n/a| n/a| Positions damper to VMIN position
DAMPER VMAX-HS| n/a| n/a| Positions damper to VMAX position.
DAMPER VMAX-LS| With 2-speed fan units the damper will position to VMAX low
speed fan.
DAMPER OPEN| n/a| n/a| Positions outside air damper to the full open position.
DAMPER CLOSE| n/a| n/a| Positions outside air damper to the fully closed
position.
CONNECT Y1-O| n/a| n/a| Closes the Y1-O relay (Y1-O); energizes 1st stage
compressor.
CONNECT Y2-O| n/a| n/a| Closes the Y2-O relay (Y2-O); energizes 2nd stage
compressor.
CONNECT EXH1| n/a| n/a| Closes the power exhaust fan 1 relay (EXH1)
CONNECT EXH2| n/a| n/a| Energizes the EXH2 output. The EXH2-O can be replaced
by:
• ERV
• EXH2
• SYS
• AUX1 O
Based on AUX1 O switch settings or is not available if AUX1 O is set to NONE
Check out Tests
Use the Checkout menu to test the damper operation and any configured outputs.
Only items that are configured are shown in the
Checkout menu.
To perform a Checkout test:
- Scroll to the desired test in the Checkout menu using the ▲ and ▼ buttons.
- Press the ← button to select the item.
- RUN? appears on the display.
- Press the ← button to start the test.
- The unit pauses and then displays TEST RUNNING.
- Press the button ↑ (Menu up) to end the test (e.g. turn off the relay). Test stops automatically after 10 minutes without a command or mode change, and will resume normal operation.
The checkout tests can all be performed at the time of installation or any time during the operation of the system as a test that the system is operable.
NOTE: Be sure to allow for enough time for compressor startup and
shutdown between checkout tests so that you do not short- cycle the
compressors and damage them from extreme short-cycling.
ALARM MENU
Parameter| Parameter Default Value| Parameter Range and Incremeent a|
Notes
---|---|---|---
MA T SENS ERR| n/a| n/a| Alarms display only when they are active. The menu
title “ALARMS (_)”includes the number of active alarms in parenthesis ().
CO2 SENS ERR| n/a| n/a
OA T SENS ERR| n/a| n/a
DA ENTHL ERR| n/a| n/a
SYS ALARM| n/a| n/a| When AUX1 O is set to SYS and there is any alarm (e.g.,
failed sensors, etc.), the AUX1 O terminal has 24 Vac out.
ACT UNDER V| n/a| n/a| Voltage received by Actuator is above expected range
ACT OVER V| n/a| n/a| Voltage received by Actuator is below expected range
ACT STALLED| n/a| n/a| Actuator stopped before achieving commanded position
Alarms
The Economizer module provides alarm messages that display on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before checking for
alarms. This allows time for all the configured devices (e.g. sensors,
actuator) to become operational. The exception is the MA sensor which will
alarm immediately.
If one or more alarms are present and there has been no keypad activity for at
least 5 minutes, the Alarms menu displays and cycles through the active
alarms. You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has been removed (e.g.
replaced faulty sensor), the alarm can be cleared from the display. To clear
an alarm, perform the following:
- Navigate to the desired alarm.
- Press the ← button.
- ERASE? displays.
- Press the ← button.
- ALARM ERASED displays.
- Press the button ↑ (MenuUp/Exit) to complete the action and return to the previous menu.
NOTE: If an alarm still exists after you clear it, it redisplays within 5 seconds.
TYPICAL ADJUSTMENTS
-
Economizer ENTH CURVE Setpoint
a. Only the coolest, driest outside air is used for economizer operation when parameter “ES5” is selected on the SETPOINT MENU. Select parameter “ES1” on the SETPOINT MENU for the greatest energy savings.
b. Adjustments are ES1, ES2, ES3, ES4, ES5.
c. “ES3” is the default setting.
d. Economizer ENTH CURVE Setpoint can be adjusted at any time and may need adjustment for jobsite conditions. e. Single enthalpy strategy: If outdoor air enthalpy is lower than the ENTH CURVE setpoint, then free cooling is available.
f. Dual enthalpy strategy: ENTH CURVE Setpoint is not used. If outdoor air enthalpy is lower than return air enthalpy, then free cooling is available. There is also a high limit boundary for dual enthalpy. The high limit boundary is “ES1” when there are no stages of mechanical cooling energized and “HL” when a compressor stage is energized. Single Enthalpy and Dual Enthalpy High Limit CurvesEnthalpy Curve| Temp. Dry-Bulb (°F)| Temp. Dewpoint (°F)| Enthalpy (btu/lb/da)| Point P1| Point P2
Temp. °F| Humidity %RH| Temp. °F| Humidity %RH
ES1| 80.0| 60.0| 28.0| 80.0| 36.8| 66.3| 80.1
ES2| 75.0| 57.0| 26.0| 75.0| 39.6| 63.3| 80.0
ES3| 70.0| 54.0| 24.0| 70.0| 42.3| 59.7| 81.4
ES4| 65.0| 51.0| 22.0| 65.0| 44.8| 55.7| 84.2
ES5| 60.0| 48.0| 20.0| 60.0| 46.9| 51.3| 88.5
HL| 86.0| 66.0| 32.4| 86.0| 38.9| 72.4| 80.3 -
EXH1 SET – Adjustments for (optional) power exhaust.
a. The outside air damper position at which the power exhaust fan(s) will engage.
b. With 2-speed indoor fan units EXH1 L (low speed fan) and EXH1 H (high speed fan) settings are required.
c. Default for EXH1 L is 65% and EXH1 H is 50%.
d. After the outside air damper output command DAMPER OUT (not ACT POS.) reaches the power exhaust setpoint, the power exhaust output EXH1 is energized after a 45 second delay.
e. Range of adjustment is from 0-100% outside air. -
EXH2 SET – Adjustments for (optional) 2 speed power exhaust.
a. The outside air damper position at which the 2nd speed of the power exhaust fan(s) will engage.
b. With 2-speed indoor fan units EXH2 L (low speed fan) and EXH2 H (high speed fan) settings are required.
c. Default for EXH2 L is 80% and EXH2 H is 75%.
d. After the outside air damper output command DAMPER OUT (not ACT POS.) reaches the power exhaust setpoint, the power exhaust output EXH2 is energized after a 45 second delay to allow the damper to reach the appropriate position.
e. Range of adjustment is from 0-100% outside air. -
MIN POS – Outside Air Damper minimum position
a. Displays ONLY if a CO2 sensor is NOT connected. With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V.
b. Adjust MIN POS to allow the minimum amount of outdoor air, as required by local codes, to enter the building.
c. Range of adjustment is from 0-100% (2-10V); in most applications MIN POS is adjusted to allow 10% to 25% outside air to enter the system.
d. MIN POS can be adjusted at any time.
e. Whenever the “G” (supply fan) signal is present, the damper will open to this minimum position unless the mixed air sensor falls below the MA LO SET (Freeze Protect Mode Setpoint). -
VENTMAX – Demand Control Ventilation (DCV) Maximum Setpoint
a. Displays only if a CO2 sensor is connected.
b. VENTMAX allows the installer to limit the amount of outdoor airflow into the building when DCV overrides the mixed air temperature sensor setpoint. It is normally equal to the minimum amount of outdoor air under maximum occupancy, as required by local codes, to enter the building.
c. VENTMAX can be adjusted at any time. -
VENTMIN – Demand Control Ventilation (DCV) Setpoint
a. Displays only if a CO2 sensor is connected.
b. Is the ventilation requirement for less than maximum occupancy of the space.
c. Compatible CO2 sensors will have a 2-10Vdc output for a 0-2000 ppm CO2 input.
d. DCV modulates the outdoor damper between the VENTMIN and VENTMAX settings to provide ventilation based on occupancy. The carbon dioxide (CO2) sensor is used to indirectly monitor occupancy level.
e. No cooling signal (e.g.Y1, Y2) is required for DCV to override the outdoor air damper when ventilation requires outdoor air.
f. The controller must receive a “G” (supply fan) signal to open the damper.
g. Range of adjustment is from 2 Volts to 10 Volts.
h. VENTMIN can be adjusted at any time.
i. The controller compares the CO2 sensor input to VENT MIN to determine the damper minimum position.
i. If the actual CO2 level is below the setpoint, then the damper minimum position is determined by the damper minimum position (VENTMIN) setting.
ii. If the actual CO2 level rises above the setpoint, then the damper minimum position is overridden proportionally more open up to the VENTMAX setting.
iii. If the mixed air temperature drops below 45°F (MA LO SET – Freeze Protect Mode Setpoint), the DCV input will be overridden and the damper may not open.
j. Ensure proper polarity of the sensor wires when connecting to the economizer controller. Incorrect polarity negates the sensor signal.
NORMAL OPERATION
-
Fan Only (G)
a. Damper will go to minimum position (in 90 seconds or less) whenever the “G” (supply fan) signal is present.
b. When “G” signal is removed, the outside air damper closes against blade seals for tight shutoff of outside air.
c. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then the control will override the minimum position setting and will modulate the outside air damper closed. -
Call for First Stage of Cooling (Y1)
a. Economizer Unavailable (warm outdoor air): Closes the Y1-O relay (Y1-O) which energizes 1st stage compressor.
b. Economizer Available (free cooling): The controller tries to maintain a mixed air temperature of 53°F ± 5 (MAT SET Setpoint) by modulating the outside air damper position. -
Call for Second Stage of Cooling (Y2)
a. Economizer Unavailable (warm outdoor air): Closes the Y2-O relay (Y2-O) which energizes 2nd stage compressor.
b. Economizer Available (free cooling): Closes the Y1-O relay (Y1-O) which energizes 1st stage compressor. The controller tries to maintain a mixed air temperature of 53°F ± 5 (MAT SET Setpoint) by modulating the outside air damper position. After a time period of 2 hours of simultaneous economizer operation and first stage compressor operation, the economizer closes the Y2-O relay (Y2-O) which energizes 2nd stage compressor. -
Call for Heat
a. Standard Air Conditioner with electric or gas heat.(W1 & W2)
i. The Thermostat controls the stages of heating directly.
ii. If the control detects that the supply fan is on (through its “G” input), then the control will open the damper to minimum position.
iii. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then the control will override the minimum position setting and will modulate the outdoor damper closed.
b. Heat Pump Operation (B)
i. The “B” signal from the Thermostat allows operation of the compressors to provide heating without delay.
ii. If the control detects that the supply fan is on (through its “G” input), then the control can open the damper to minimum position.
iii. If the mixed air temperature drops below 45°F (MA LO SET Setpoint), then the control will override the minimum position setting and will modulate the outdoor damper closed.
NOTES
- This economizer requires a two-stage thermostat.
- When diagnosing the system, the best results are obtained by first putting the fan setting on the Thermostat to the “Continuous Fan” mode.
- Operation of the optional power exhaust only depends upon the supply fan running and the damper position (it is possible to set the minimum position high enough to engage the power exhaust in the heating mode).
- Upon loss of power to the unit or economizer, the outside air damper will spring close shut in about 5 seconds.
- The mist eliminator (Permanent Outdoor Air Filter) is of aluminum mesh construction and should be cleaned by flushing regularly with warm soapy water. The replacement mist eliminator size is listed on the first page of these instructions.
- Compressor Time Delays, Compressor Interstage Delays are not provided by the economizer controller.
Table of Inputs and Output Response with and without a CO2 Sensor (DCV)
Inputs to Controller| Outputs from Controller
DCV| Free Cooling Available?| Y1-I| Y2-I| AUX2-I|
FAN| Y1-O| Y2-O| OA Damper Position
None| NO| OFF| OFF| OFF| OFF| OFF| OFF| CLOSED
OFF| OFF| OFF| ON| OFF| OFF| MIN POS
ON| OFF| OFF| ON| ON| OFF| MIN POS
ON| ON| OFF| ON| ON| ON| MIN POS
ON| OFF| ONd| ON| ON| OFF| MIN POS
ON| ON| ONd| ON| ON| ON| MIN POS
YES| OFF| OFF| OFF| ON| OFF| OFF| MIN POS
ON| OFF| OFF| ON| OFF| OFF| MIN POS to 100%
ON| ON| OFF| ON| ON| OFFb| MIN POS to 100%
ON| OFF| ONd| ON| ON| OFF| MIN POS
ON| ON| ONd| ON| ON| ON| MIN POS
Below Setpoint| NO| OFF| OFF| OFF| ON| OFF| OFF| VENTMIN
ON| OFF| OFF| ON| ON| OFF| VENTMIN
ON| ON| OFF| ON| ON| ON| VENTMIN
ON| OFF| ONd| ON| ON| OFF| VENTMIN
ON| ON| ONd| ON| ON| ON| VENTMIN
YES| OFF| OFF| OFF| ON| OFF| OFF| VENTMIN
ON| OFF| OFF| ON| OFF| OFF| VENTMIN to 100%
ON| ON| OFF| ON| ON| OFFb| VENTMIN to 100%
ON| OFF| ONd| ON| ON| OFF| VENTMIN
ON| ON| ONd| ON| ON| ON| VENTMIN
Above Setpoint| NO| OFF| OFF| OFF| ONc| OFF| OFF| VENTMIN to VENTMAX
ON| OFF| OFF| ON| ON| OFF| VENTMIN to VENTMAX
ON| ON| OFF| ON| ON| ON| VENTMIN to VENTMAX
ON| OFF| ONd| ON| ON| OFF| VENTMIN to VENTMAX
ON| ON| ONd| ON| ON| ON| VENTMIN to VENTMAX
YES| OFF| OFF| OFF| ONc| OFF| OFF| VENTMIN to VENTMAX
ON| OFF| OFF| ON| OFF| OFF| VENTMIN to 100%
ON| ON| OFF| ON| ON| OFFb| VENTMIN to 100%
ON| OFF| ONd| ON| ON| OFF| VENTMIN to VENTMAX
ON| ON| ONd| ON| ON| ON| VENTMIN to VENTMAX
With STG3 DLY in ADVANCED SETUP MENU at 2.0 hours, the 2nd stage of mechanical
cooling Y2-O can be energized after a 2 hour delay if the call for Y1-I and
Y2-I have not been satisfied.
The CO2 sensor has a relay output that is active when the CO2 level is above
1200ppm that can be used to energize the indoor fan through the “G” thermostat
input of the unit even if there is not a call for fan, cooling or heating by
the room thermostat. Additional field wiring is required to enable this
option.
AUX2-I is used only on heat pump models to indicate unit is in heat pump
(heating) mode.
Table of Inputs and Output Response with and without a CO2 Sensor (DCV) for Unoccupied Mode
Inputs to Controller| Outputs from Controller
DCV| Free Cooling Available?| Y1-I| Y2-I| AUX2-I|
FAN| Y1-O| Y2-O| OA Damper Position **(Unoccupied)***
None| NO| OFF| OFF| OFF| OFF| OFF| OFF| CLOSED
OFF| OFF| OFF| ON| OFF| OFF| CLOSED
ON| OFF| OFF| ON| ON| OFF| CLOSED
ON| ON| OFF| ON| ON| ON| CLOSED
ON| OFF| ONd| ON| ON| OFF| CLOSED
ON| ON| ONd| ON| ON| ON| CLOSED
YES| OFF| OFF| OFF| ON| OFF| OFF| CLOSED
ON| OFF| OFF| ON| OFF| OFF| CLOSED to 100%
ON| ON| OFF| ON| ON| OFFb| CLOSED to 100%
ON| OFF| ONd| ON| ON| OFF| CLOSED
ON| ON| ONd| ON| ON| ON| CLOSED
Below Setpoint| NO| OFF| OFF| OFF| ON| OFF| OFF| CLOSED
ON| OFF| OFF| ON| ON| OFF| CLOSED
ON| ON| OFF| ON| ON| ON| CLOSED
ON| OFF| ONd| ON| ON| OFF| CLOSED
ON| ON| ONd| ON| ON| ON| CLOSED
YES| OFF| OFF| OFF| ON| OFF| OFF| CLOSED
ON| OFF| OFF| ON| OFF| OFF| CLOSED to 100%
ON| ON| OFF| ON| ON| OFFb| CLOSED to 100%
ON| OFF| ONd| ON| ON| OFF| CLOSED
ON| ON| ONd| ON| ON| ON| CLOSED
Above Setpoint| NO| OFF| OFF| OFF| ONc| OFF| OFF| CLOSED
ON| OFF| OFF| ON| ON| OFF| CLOSED
ON| ON| OFF| ON| ON| ON| CLOSED
ON| OFF| ONd| ON| ON| OFF| CLOSED
ON| ON| ONd| ON| ON| ON| CLOSED
YES| OFF| OFF| OFF| ONc| OFF| OFF| CLOSED
ON| OFF| OFF| ON| OFF| OFF| CLOSED to 100%
ON| ON| OFF| ON| ON| OFFb| CLOSED to 100%
ON| OFF| ONd| ON| ON| OFF| CLOSED
ON| ON| ONd| ON| ON| ON| CLOSED
e Unoccupied Mode is only available by field wiring a normally open (NO) relay
in the “G” signal wiring between the unit and economizer. A thermostat with an
occupied output is required which energizes the relay when the space is
occupied. The relay interrupts the 24 volt “G” signal from the unit indoor fan
when the space is unoccupied.
Mixed Air / Discharge Air Temperature vs. Resistance
Documents / Resources
| JADE
RXRD-01MDDAM3 Vertical Airflow
Economizers
[pdf] Installation Guide
RXRD-01MDDAM3 Vertical Airflow Economizers, RXRD-01MDDAM3, Vertical Airflow
Economizers, Airflow Economizers, Economizers
---|---