ICM CONTROLS 334-LF Head Pressure Control Kit Installation Guide
- September 7, 2024
- ICM CONTROLS
Table of Contents
ICM CONTROLS 334-LF Head Pressure Control Kit
Specifications
- Product: Head Pressure Control Kit
- Model: Odyssey Split System Cooling, 5 to 12.5 Tons
- Input Voltage: 120-600VAC
- Manufacturer Part Number: X13651682
- Pressure Range: 35 psig to 465 psig
Product Usage Instructions:
Installation
- Only qualified personnel should install the equipment.
- Ensure all field wiring is performed by qualified personnel following NEC and local/state/national electrical codes.
- Follow the specific installation instructions provided in the manual.
Safety Precautions
- Always wear proper Personal Protective Equipment (PPE) as described in the manual.
- Observe all safety warnings and precautions mentioned in the manual and on equipment labels.
- Follow Environmental Health and Safety (EHS) policies during installation and servicing.
Operation
- Read the manual thoroughly before operating the unit.
- Ensure proper field wiring and grounding to avoid hazards.
- Monitor pressure levels within the specified range during operation.
Maintenance
- Schedule regular maintenance checks as recommended by the manufacturer.
- Service the equipment only with authorized components and tools.
Frequently Asked Questions (FAQ)
-
Q: Who should install the equipment?
A: Only qualified personnel should install and service the equipment to prevent hazards and ensure proper functioning. -
Q: What refrigerant does this equipment use?
A: This equipment uses R-454B refrigerant, which is flammable (A2L). Ensure to use R454B rated service equipment and components. -
Q: What are the safety precautions to be followed?
A: Always wear Personal Protective Equipment (PPE), follow EHS policies, and adhere to proper field wiring and grounding requirements to avoid hazards and ensure safety.
Installation Guide
Head Pressure Control Kit
Odyssey Split System Cooling, 5 to 12.5 Tons
BAYLOAMS10: TTA060, 072, 076, 090, 101, 120, 126, 150 and TWA060, 072, 076, 090, 101, 120
SAFETY WARNING
Only qualified personnel should install and service the equipment. The
installation, starting up, and servicing of heating, ventilating, and air-
conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an
unqualified person could result in death or serious injury. When working on
the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal
safety and the proper operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against
unsafe practices.
CAUTION
Indicates a situation that could result in equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the
earth’s naturally occurring stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified chemicals that may affect
the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs).
Not all refrigerants containing these compounds have the same potential impact
to the environment. Trane advocates the responsible handling of all
refrigerants.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the
environment, our customers, and the air conditioning industry. All technicians
who handle refrigerants must be certified according to local rules. For the
USA, the Federal Clean Air Act (Section 608) sets forth the requirements for
handling, reclaiming, recovering and recycling of certain refrigerants and the
equipment that is used in these service procedures. In addition, some states
or municipalities may have additional requirements that must also be adhered
to for responsible management of refrigerants. Know the applicable laws and
follow them.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly
installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for field wiring
installation and grounding as described in NEC and your local/state/national
electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions
below:
- Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
- When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
- If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
- All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
- Non-Trane personnel should always follow local regulations.
WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result
in equipment failure, and possibly fire, which could result in death, serious
injury, or equipment damage.
The equipment described in this manual uses R-454B refrigerant which is
flammable (A2L). Use ONLY R-454B rated service equipment and components. For
specific handling concerns with R-454B, contact your local representative.
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time, and to make changes
to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
Revision History
Updates throughout the document to includes the R454–B refrigerant.
Pre-Installation
General Information
Table 1. Low ambient controller specifications
Volts, AC | 208, 240, 380, 415, 480, 600 |
---|---|
Control Voltage | 18-30 Vac |
Frequency | 50-60 Hz |
Operating Temperature | -40ºF + 140ºF (-40ºC to 60ºC) |
Full Load Amps | 10 Amps |
Transducer Pressure Control Range | 0-500 psi |
Disable Evaporator Defrost Control
Important: For proper operation of the low ambient head pressure control
accessory in an Odyssey condenser, the Evaporator Defrost Control (EDC)
function MUST be disabled.
To disable the EDC, navigate to the “Utilities” menu on the Symbio™ 700 user
interface and change the configuration parameter “Evaporator Defrost Control”
to “Disabled”. The Symbio Service and Installation mobile application can also
be used to edit this parameter.
Parts List
Item Number | Quantity | Description |
---|---|---|
1 | 1 | BAYLOAM Control Box Assembly |
2 | 1 | Installation Guide |
3 | 1 | Wiring Diagram |
4 | 1 | Transducer(a) |
5 | 10 | Wire Tie |
6 | 1 | Snap Bushing |
7 | 1 | Tee; Pressure Tap |
8 | 1 | Label; Information BAYLOAMS10 |
9 | 4 | Screw |
ICM-CONTROLS-334-LF-Head-Pressure-Control-Kit- (1)
Installation
WARNING
Controller
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury.
Disconnect all electric power, including remote disconnects and discharge all
motor start/run capacitors before servicing. Follow proper lockout/tagout
procedures to ensure the power cannot be inadvertently energized. For variable
frequency drives or other energy storing components provided by Trane or
others, refer to the appropriate manufacturer’s literature for allowable
waiting periods for discharge of capacitors. Verify with a CAT III or IV
voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly
installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for field wiring
installation and grounding as described in NEC and your local/state/national
electrical codes.
- Prepare the unit for installation.
- Disconnect and lock out all power from the unit.
- Remove the compressor and control box access panel(s).
- Remove the snap plug and 1 screw from the unit corner post on the right side of the unit (when facing the compressor access panel). See Figure 2, p. 7. Note: If an expansion module kit is already installed, then remove the low ambient controller, sensor, and its wiring, mount it in the expansion module box. Discard the low ambient box. See Figure 3, p. 7.
- Remove the 4 screws that secure the control box mounting bracket to the kit control box and set the control box and mounting bracket to the side.
- Insert the snap bushing (provided in the kit) into the hole on the corner post. See Figure 4, p. 8.
- Using the 4 screws provided in the kit secure the control box mounting bracket to the corner post. See Figure 4, p. 8.
Transducer and Tee
WARNING
R-410A Refrigerant under Higher
Pressure than R-22!
Failure to use proper equipment or components as described below, could result
in equipment failing and possibly exploding, which could result in death,
serious injury, or equipment damage.
The units described in this manual use R-410A refrigerant which operates at
higher pressures than R-22. Use ONLY R-410A rated service equipment or
components with these units. For specific handling concerns with R-410A,
please contact your local Trane representative.
WARNING
R-454B Flammable A2L Refrigerant!
Failure to use proper equipment or components as described below could result
in equipment failure, and possibly fire, which could result in death, serious
injury, or equipment damage.
The equipment described in this manual uses R-454B refrigerant which is
flammable (A2L). Use ONLY R-454B rated service equipment and components. For
specific handling concerns with R-454B, contact your local representative.
WARNING
Risk of Fire — Flammable Refrigerant!
Failure to follow instructions below could result in death or serious injury,
and equipment damage.
- To be repaired only by trained service personnel.
- Do not puncture refrigerant tubing.
- Dispose of properly in accordance with federal or local regulations.
NOTICE
Wire Damage!
Failure to follow instructions below could result in damaged wires.
Use provided wire ties to make sure wire are secured and protected from sharp
edges and hot surfaces.
Install a tee and pressure transducer on the discharge line service port at each compressor using the following instructions:
- Remove red tags (applicable only for R–454B units) and cap nut from the unit’s high pressure service port on the discharge line that runs from the compressor.
- Install one transducer on the Tee port without the valve core and place the cap nut (that was removed from the service port) on to the port with the valve core on each Tee.
- Place the Tee flare nut with valve core depressor on the unit high pressure tap, where the cap nut is located.
- For R-454B units, install the red tag in the new service port location before installing the cap nut.
- Tighten flare nut securely to the high pressure service port and check for leaks.
- Route transducer wires through snap bushing and connector into the kit control box and make connections per diagram (supplied in kit).
- After all wires are secured to the head pressure controller and routed through the bushing and connector in the kit control box, tighten connector screws, ensure the wire protection sleeve is placed properly again to protect the wires from being pinched. Then secure kit control box to the mounting bracket on the unit using the screws that were removed earlier. See Figure 8, p. 10.
Wiring
NOTICE
Wire Damage!
Failure to follow instructions below could result in damaged wires.
Use provided wire ties to make sure wire are secured and protected from sharp
edges and hot surfaces.
Control Box Wiring
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury.
Disconnect all electric power, including remote disconnects and discharge all
motor start/run capacitors before servicing. Follow proper lockout/tagout
procedures to ensure the power cannot be inadvertently energized. For variable
frequency drives or other energy storing components provided by Trane or
others, refer to the appropriate manufacturer’s literature for allowable
waiting periods for discharge of capacitors. Verify with a CAT III or IV
voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly
installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for field wiring
installation and grounding as described in NEC and your local/state/national
electrical codes.
-
Locate the fan contactor in the control box, disconnect the fan motor quick connects and connect them to the male quick connects in the fan power harness (supplied in the kit) then connect the female quick connects in the same harness to the fan contactor. See Figure 9, p. 11.
-
Run the 24 VAC harness with the red and black wire to the unit controller in the control box and connect the 2 pin connector to the Symbio™ 700 board at P5 header. See Figure 10, p. 11.
-
Terminate the ground wire (supplied in the Kit) in the control box. See Figure 9, p. 11.
-
IN HEAT PUMP UNITS ONLY, disconnect the black wire from the switch over valve and connect it to the black wire in the switch over valve harness (supplied in kit), then connect the orange wire to the switch over valve. The switch over valve harness is not needed in cooling only units. See Figure 11, p. 12 and Figure 12,
p. 12.
Note : For TTA060, 072, 076, 090, 101, 120, 126, 150 and TWA060, 072, 076, 090, 101, 120 units with model number digit 9 equals D, two transducers should be used with one controller — in which case the controller will respond to the transducer that senses the highest pressure (see kit diagram). -
Finish wiring installation. Using wire ties, bundle and dress any excess wires away from sharp edges, moving parts, or hot tubes.
-
Apply the wiring diagram (supplied in kit) to the top part of the enclosure box door, as shown in image Figure 13, p. 13.
Controller Settings
Jumper Position for TTA Models (Cooling Only)
For non-heat pump applications, the heat pump select jumper must be in the
Default (N.O.) position, and the HP terminals must be left unconnected. See
Figure 14, p. 13.
Jumper Position for TWA Models (Heat Pump)
For heat pump applications, the heat pump select jumper must be in the (N.C.)
position, see Figure 15, p. 13. The heat pump terminals accept the 24 VAC
signal from the switch over valve holding coil.
Important: Do not apply a voltage higher than 30 VAC to the HP terminals.
Operation
The low ambient controller is used to maintain head pressure within an acceptable range when ambient temperature falls below 50°F. It reads discharge pressure from refrigeration circuit and cycles the outdoor fan motor on and off to maintain the desired discharge pressure at the selected setpoint anytime the compressor is operating.
Set Pressure Setpoint
The pressure setpoint should be adjusted to 250 psig for R-410A refrigerant
and 230 psig for R-454B refrigerant. When the ambient temperature is above
50°F (10°C), the outdoor fan motor will be energized continuously. When the
ambient temperature is below 50°F, the pressure sensor reading is used to
switch the motor on or off. When the pressure is 15psi below the set pressure
the motor will be turned off. When the pressure is 15psi above the set
pressure, the motor will be turned on.
After completion of installation and pressure setting adjustment), reinstall
the compressor and control box access panels and secure with screws that were
removed.
Reconnect all power to the unit. Refer to troubleshooting guide, if needed.
Operation and Troubleshooting
Checkout Procedure
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers,
and labels could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical,
mechanical, and chemical hazards, MUST follow precautions in this manual and
on the tags, stickers, and labels, as well as the following instructions:
Unless specified otherwise, disconnect all electrical power including remote
disconnect and discharge all energy storing devices such as capacitors before
servicing. Follow proper lockout/tagout procedures to ensure the power can not
be inadvertently energized. When necessary to work with live electrical
components, have a qualified licensed electrician or other individual who has
been trained in handling live electrical components perform these tasks.
Before leaving the installation, observe for correct operation through the
desired pressure range (see Table 3, p. 16).
Table 2. Troubleshooting guide
Problem | Possible Cause | Possible Solution |
---|
No fan operation
| No 24 volt control voltage| Check for 24 Vac between Y1 or Y2 and C terminals — it should read 24 volts.
No line voltage
| Check voltage across brown, orange, and yellow motor leads. If no voltage is present verify all wiring is correct.
Bad fan motor or controller
| If fan does not start, motor is bad and should be replaced. If motor does start, check controller settings. If motor still fails to start, replace controller.
Improper fan operation
| Heat pump jumper not configured correctly| Verify the heat pump jumper is
configured correctly.
Control is not wired correctly| See wiring diagrams. Ensure that the 24 Vac
power supply is connected.
No fan modulation
| ****
No need to modulate the fan
| If pressure is equal to or greater than the head pressure control setpoint, the fan will be operating at full speed.
No input pressure to control
| Check for proper transducer and Tee installation. Schrader valve depressor
must depress Schrader valve enough to allow refrigerant into pressure
transducer.
Heat pump inputs wired incorrectly into the controller| Check diagram and
verify heat pump inputs are properly wired into the controller.
Miswired| Check that the 24 Vac signal and the transducer are wired up
correctly into the controller.
Erratic fan operation
| Control is not wired correctly| See wiring diagrams.
Pressure transducer problem
| Check for proper transducer and Tee installation. Schrader valve depressor
must depress Schrader valve enough to allow refrigerant into pressure
transducer.
Dirty or blocked condenser coil| Clean condenser coil.
The high pressure switch trips off
| ****
Improper head pressure setpoint setting
| See unit fails to start above.
Check the setpoint and reduce it if needed.
Reduced cooling capacity at low Ambient| Evaporative Defrost Control is
active| Disable EDC function in Symbio™ 700
Table 3. Pressure vs. voltage
Pressure (psig) | Voltage (Vdc) |
---|---|
0 | 0.5 |
50 | 0.9 |
100 | 1.3 |
150 | 1.7 |
200 | 2.1 |
250 | 2.5 |
300 | 2.9 |
350 | 3.3 |
400 | 3.7 |
450 | 4.1 |
500 | 4.5 |
Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
ACC-SVN194C-EN 11 Aug 2024
Supersedes ACC-SVN194B-EN (August 2021)
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>