OVERVIEW

The ICM530, ICM531, ICM532 & ICM533 are a series of Type 1 and Type 2 three- phase surge protective devices for three-phase Delta and three-phase Wye configurations. When a surge occurs, the ICM three-phase surge protective device will absorb the surge up to the specified limitations of the device. ICM incorporates superior thermally protected metal oxide varistor technology into the three-phase surge suppressors, which allows for safe disabling of the surge elements when a surge exceeds the thermal limits of the device. There is a single status light on the controls which identifies operational status when illuminated. The ICM 3-phase surge protective device can be installed as a Type 1 or Type 2 device for both indoor and outdoor applications.

SPECIFICATIONS

  • Service voltage (3-phase): 480 VAC Delta or 277/480 VAC Wye
  • Short Circuit Current Rating (SCCR): 200 kA
  • Nominal discharge current (In): 20kA
  • Protection mode:
    • 3 for Delta configuration
    • 6 for Wye configuration (neutral tied to ground)
  • Maximum Continuous Operation Voltage (MCOV):
    • L-L: 700 VAC L-N: (for Wye configuration only): 350 VAC
  • VPR:
    • Delta L-L: 2500 VAC Wye L-L: 2500 VAC Wye L-N: 1200 VAC
  • SPD type: Type 1 (can also be used in Type 2 applications)
  • Surge protection technology: TFMOV
  • Input power frequency: 50/60 Hz
  • Dimensions: 4.30” x 4.10” x 2.30”

REPLACES

  • ABB: OVRHLDxx-277
  • ASCO: 420277Y, 420480D
  • Eaton: SP1-480Y, SP1-480D, SP2-480Y, SP2-480D
  • ERICO (Critec): TDX50C277/480
  • Intermatic: AG4803C3, L5F13Y2DG1
  • Leviton: 55480-ASA
  • Siemens: TPS3E, TPS3F
  • Square D: SDSA2040, SDSA2040D

FEATURES

  • Delta or Wye Configuration
  • NEMA Type 4X watertight plastic enclosure for outdoor and indoor installation
  • Green LED indicates surge protection present
  • Easily connects to electrical panel or disconnects for indoor and outdoor applications
  • UL Listed Type 1 or Type 2 SPD