ICM CONTROLS ICM531 3-Phase Delta Surge Protective Device Instruction Manual
- June 3, 2024
- ICM CONTROLS
Table of Contents
**ICM CONTROLS ICM531 3-Phase Delta Surge Protective Device Instruction Manual
**
Please follow all State, Local and National electrical codes when installing this product. Installation should only be done by a licensed electrician for Type 1 devices or a licensed HVAC technician for Type 2 devices.
ELECTRICAL SHOCK HAZARD – Before installing this unit, turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position.
- WARNING — No Serviceable Parts
- WARNING — Shock hazard — Do not open
Maintenance
Periodically check the LED status on the SPD. If the Greenlight is OFF, the protection is no longer available and the SPD needs to be replaced immediately. 12 AWG stranded copper wire or larger required. Product contains no serviceable parts. This device features an internal protection that will disconnect the surge protective component at the end of its useful life but will maintain power to the load – now unprotected.
Mode of Operation
The ICM531 is a UL Listed Type 1&2 Surge Protective Device for three phase
Delta 480 VAC or Wye 277/480 VAC three phase voltage configurations.
When a surge occurs, the ICM531 will absorb the surge up to the limits
expressed in the specifications section of this guide. The ICM531 incorporates
thermal protection on the surge elements (TMOV’s) which allows for safe
disabling of the surge elements when a surge exceeds the thermal limits of the
device. The ICM531 has a status light on the control which identifies
operational status when illuminated. The ICM531 can be installed as a Type 1
or Type 2 device for both indoor and outdoor applications. Suitable for use on
a circuit capable of delivering not more than 200kA RMS symmetrical amperes,
480V maximum (Convient à des circuits produisant au plus 200kA RMS A eff.”,
480V maximum).
Installation Instructions
The conductors used to connect the SPD shall not be any longer than necessary and shall avoid unnecessary bends.
-
Turn off the main breaker and/or main power to the service disconnect.
-
Determine if you have a Wye or Delta configuration.
-
Verify your mains voltage and match that with ICM531 ratings.
-
Remove the cover on service disconnect or the electrical panel.
-
Mount the ICM531 through the 3/4” conduit connection of the electrical panel.
-
Remove the retaining ring and washer on the ICM531.
-
Feed the wires into the electrical panel or service disconnect.
-
Re-secure the retaining ring and washer.
-
Route the white wire to the neutral lug and secure.
Wiring Type 1 installation
-
Route the three black wires to the appropriate L1, L2, L3 connections before the breaker panel as seen in the wiring diagram for Type 1 installation and according to your local, state, and national electrical codes.
-
There will be a white wire which is only used in the Wye configuration and which needs to be capped off in the Delta configuration.
Wiring Type 2 installation
-
Route and connect the three black wires (L1, L2, and L3) to the individual breakers on the circuit breaker panel as seen in the wiring diagram for Type 2 installation and according to your local, state and national electrical codes.
-
There will be a white wire which is only used in the Wye configuration and which needs to be capped off in the Delta configuration.
-
-
Reinstall cover on service disconnect or the electrical panel.
-
Restore power; Green LED should be on indicating full protection.
Specifications
Description | Ratings |
---|---|
Service Voltage (3-Phase) | 480 VAC Delta OR 277/480 VAC Wye |
Short Circuit Current Rating (SCCR) | 200 kA |
Nominal Discharge Current (In) | 20 kA |
SPD Type | Type 1 (Can also be used in Type 2 applications) |
Surge Protection Technology | TFMOV |
Protection Mode | 3 for Delta configuration |
6 for Wye configuration (neutral tied to ground)
VPR (Vpk)| VOLTS (V) MODE VPR (Vpk)
480 L-L 2500
480/277 L-L 2500
L-N 1200
Maximum Continuous Operation Voltage (MCOV)| L-L: 700 VAC
L-N: (for Wye configuration only): 350 VAC
Input Power Frequency| 50/60Hz
Diagnostics| Green LED indicates surge protection present
Enclosure Rating| NEMA/Type 4X water tight plastic enclosure for outdoor
and indoor installation
Installation Point| Electrical panel/disconnect
Dimensions| 4.3” X 4.1” X 2.3”
Operating Temperature| -40°F to 185°F (-40°C to 85°C)
Operating Humidity| Less than 85%, noncondensing
Operating Altitude| Less than 2000 meters
Agency Certification and Approvals| ANSI/UL1449 4th Edition Listed
Device cULus Listed
Wiring Diagrams
Delta Configuration
Type 1 Wiring – Fuse Disconnect
Type 2 Wiring – Circuit Breaker
Note 1:
For the ease of checking the SPD protection status, the LED display should
face outwards after installation has been complete.
Note 2:
ICM531 is a Type 1 and 2 SPD, designed to be compatible with 3-phase Delta and
3-phase Wye voltage configuration.
Please check your supply voltage configuration and voltage levels before
installing the ICM531 per wiring diagram.
Note 3:
- When installing the Surge Protecting Device (SPD), avoid sharp bends in the conduit and long line sets.
- Keep the mounting conduit straight and short in length
Legend:
BLK Black
WHT White
A,B,C Incoming phase
Ground
Wiring Diagrams
Wye Configuration
Type 1 Wiring – Fuse Disconnect
Type 2 Wiring – Circuit Breaker
Note 1:
For the ease of checking the SPD protection status, the LED display should
face outwards after installation has been complete.
Note 2:
ICM531 is a Type 1 and 2 SPD, designed to be compatible with 3-phase Delta and
3-phase Wye voltage configuration. Please check your supply voltage
configuration and voltage levels before installing the ICM531 per wiring
diagram.
Note 3:
- When installing the Surge Protecting Device (SPD), avoid sharp bends in the conduit and long line sets.
- Keep the mounting conduit straight and short in length
Legend:
BLK Black
WHT White
A,B,C Incoming phase
Ground
ICM CONTROLS
www.icmcontrols.com
7313 William Barry Blvd., North Syracuse, NY 13212
800.365.5525
LIAF274